Siemens 3RK1308-0AB00-0CP0 SIMATIC ET 200SP High Feature Motor Starter
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Select the motor-starter BaseUnit compatible with the ET 200SP starter assembly.
- Set the overload protection to the connected motor rating within 0.3–1 A.
- Provide the required upstream short-circuit protection for the selected feeder and coordination arrangement.
- Allow 50 mm above and below and apply orientation, temperature and altitude derating.
3RK1308-0AB00-0CP0 SIMATIC ET 200SP High Feature Motor Starter
High Feature hybrid starter for 0.3–1 A motor feeders, with electronic overload protection and 0.09–0.25 kW motor ratings at 400 V.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3RK1308-0AB00-0CP0 |
| Product Type | Direct-on-line motor starter |
| Core Function | Switching and overload monitoring of a motor feeder |
| Application | ET 200SP distributed motor-control stations |
Hybrid direct starting
Electronic switching and bypass operation control a motor feeder without a reversing function.
Electronic motor protection
The adjustable overload range covers 0.3–1 A motors and provides the monitoring needed for the feeder configuration.
Station and energy integration
The starter exchanges I/O data through ET 200SP and supports PROFIenergy measurement and shutdown.
Product Overview
3RK1308-0AB00-0CP0 combines motor switching and electronic overload monitoring in a 30 mm wide ET 200SP motor-starter assembly.
The direct-on-line starter uses hybrid switching for three-phase loads, exchanges control and diagnostic data through the station and provides PROFIenergy measurement and shutdown functions.
Key Functions
Hybrid direct starting
Electronic switching and bypass operation control a motor feeder without a reversing function.
Electronic motor protection
The adjustable overload range covers 0.3–1 A motors and provides the monitoring needed for the feeder configuration.
Station and energy integration
The starter exchanges I/O data through ET 200SP and supports PROFIenergy measurement and shutdown.
Official Specifications
| Current adjustment range | 0.3–1 A |
|---|---|
| Rated operational current | 1 A at 400 V |
| Motor power at 400 V / 50 Hz | 0.09–0.25 kW |
| Main circuit | 3 poles; 48–500 V AC ±10% |
| Main-circuit frequency | 50/60 Hz ±5% |
| Maximum starting current | 10 A |
| Auxiliary supply | 24 V DC nominal; 20.4–28.8 V DC |
| Auxiliary current | 50 mA in standby and operation; 140 mA during motor switch-on |
| Power loss | 1.2 W with bypass off; 3.4 W with bypass on |
| Switching delays | 20 ms switch-on; 35–50 ms switch-off |
| Overload protection | Electronic |
| Process-data allocation | 4 input bytes and 2 output bytes |
| Optional local inputs | 4 digital inputs with the optional 3DI/LC module |
| Unshielded motor cable | 200 m maximum |
| Operating ambient | −25 to +60°C with derating |
| Storage and transport ambient | −40 to +70°C |
| Maximum altitude | 4000 m with derating |
| Required vertical clearance | 50 mm above and below |
| Dimensions | 30 × 142 × 150 mm (W × H × D) |
| Weight | 0.412 kg |
Frequently Asked Questions
Can 3RK1308-0AB00-0CP0 reverse the direction of a three-phase motor?
This direct-on-line starter provides a single starting direction and does not include a reversing function.
Which motor currents fit the setting range of 3RK1308-0AB00-0CP0?
The electronic overload setting covers motor rated currents from 0.3 to 1 A.
Does 3RK1308-0AB00-0CP0 connect directly to a PROFINET cable?
Communication runs through the ET 200SP station rather than through a separate Ethernet port on the starter.
How can I add local digital inputs to 3RK1308-0AB00-0CP0?
The optional 3DI/LC module provides four digital inputs and local-control functionality.
How much PLC address space does 3RK1308-0AB00-0CP0 require?
Allocate four bytes of input data and two bytes of output data for the starter.
Can 3RK1308-0AB00-0CP0 be mounted in either orientation?
Vertical and horizontal installation are possible when the applicable temperature and current derating is observed.
Does 3RK1308-0AB00-0CP0 support energy-management shutdown?
The High Feature starter supports PROFIenergy measurement and shutdown.