- Match sourcing positive logic to the field loads.
- Provide the external 19.2–30 V DC supply.
- Keep within 0.5 A per channel and 4 A per group.
- Provide 5 A group fusing and assess the recommended point fuses.
- Allocate two output words and include 330 mA in the rack power budget.
140DDO35300 Modicon Quantum 32-Point DC Output Module
A 32-channel positive-logic output module arranged in four groups of eight, with 0.5 A per channel and two output words.
At a Glance
| Brand | Schneider Electric |
|---|---|
| Model | 140DDO35300 |
| Product Type | Solid-state output module |
| Core Function | Driving discrete field actuators |
| Application | Modicon Quantum I/O systems |
Positive output logic
The module provides sourcing outputs for 24 V DC field circuits.
Four load groups
Eight outputs share each group’s current budget.
Separate load supply
The field circuit requires a 19.2–30 V DC external supply.
Product Overview
140DDO35300 switches thirty-two positive-logic DC outputs in a Modicon Quantum system. The channels are arranged in four groups of eight, with a 0.5 A channel limit and a 4 A group limit.
The output data occupies two words. Rack power budgeting must include the module’s 330 mA bus requirement, while the external field supply and circuit fusing are checked separately from the backplane supply.
Key Functions
Switch positive DC loads
Solid-state sourcing outputs control the connected 24 V field devices.
Organize grouped circuits
Four groups of eight channels separate common connections and load-current budgets.
Exchange rack output data
Two output words carry the channel states from the Quantum controller.
Official Specifications
| Output channel arrangement | 32 channels in 4 groups of 8 |
|---|---|
| Output logic | Positive, sourcing |
| Rated field voltage and external supply range | 24 V DC; 19.2–30 V DC |
| Maximum load currents | 0.5 A per channel; 4 A per group; 16 A per module |
| Process-data allocation | 2 output words |
| Bus current requirement | 330 mA |
| Power dissipation | 1.75 + (0.4 × total module load current in A), in W |
| Field terminal interface | 40-way screw terminal block |
Frequently Asked Questions
Can I use 140DDO35300 where negative-logic outputs are required?
This module has positive sourcing outputs, so the field circuit must match that logic.
How much load can one group of 140DDO35300 carry?
Each eight-channel group is limited to 4 A with no channel exceeding 0.5 A.
What external supply should I provide for 140DDO35300?
Provide a DC field supply within 19.2–30 V.
Which external fuses should I plan for 140DDO35300?
The selection data specifies 5 A per group and recommends 3 A per point.
How many output words does 140DDO35300 use?
The module occupies two output words.
How do I estimate the cabinet heat contribution of 140DDO35300?
Use 1.75 W plus 0.4 times the total module load current in amperes.
Does the 330 mA bus requirement of 140DDO35300 replace its field-load supply?
The 330 mA figure is the backplane requirement and the output loads use a separate external DC supply.