- Overview
- Specifications
- Applications
- Troubleshooting and Maintenance Recommendations
- FAQ
- Recommended Products
Overview
Place of Origin: |
Sweden |
Brand Name: |
ABB |
Model Number: |
S200-PS13 S200PS13 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Parameter |
Value |
|
Model |
S200-PS13 S200PS13 |
|
Product Type |
Power Supply Module |
|
Input Voltage |
24 V DC (19.2–30 V DC) |
|
Output Current |
Max 1.3 A (logic supply for I/O modules) |
|
Rated Power |
Designed for small to medium S200 I/O systems |
|
Status Indicator |
Green LED (power OK) |
|
Protection Features |
Overload protection, reverse polarity protection, short-circuit protection |
|
Installation Type |
Snap-on mounting on S200 terminal base |
Applications
Troubleshooting and Maintenance Recommendations
Indicator light not on: Check if the 24V DC input is normal, or if the internal fuse has blown due to overload.
Unstable output voltage: Excessive input power supply ripple or the total load of the downstream I/O modules exceeds 1.3A.
Temperature protection tripping: High ambient temperature or insufficient module spacing leading to poor heat dissipation.
FAQ
Q1: How many I/O modules can one S200-PS13 S200PS13 power?
It depends on the power consumption of each module. It can typically support 4–8 standard S200 modules, but the exact number depends on the total internal current consumption of each module.
Q2: Will the S200-PS13 S200PS13 burn out if the input voltage is reversed?
The S200-PS13 has reverse connection protection, so it usually won't be damaged, but the module will not function properly.
Q3: Why is the green light on my S200-PS13 S200PS13, but the downstream module isn't powered on?
Please check if the gold fingers connecting the power module and the terminal block are dirty or have poor contact.
Q4: Is the S200-PS13 S200PS13 hot-swappable?
While physically supported, it is recommended to replace it while the power is off to prevent surge current from impacting the downstream I/O modules.
Q5: Can the S200-PS13 S200PS13 be used to power field transmitters?
Its main function is to power the module's internal logic. If the field instruments have high power consumption, it is recommended to use a separate field power supply.