Overview
Place of Origin: |
Sweden |
Brand Name: |
ABB |
Model Number: |
PU516 3BSE013064R1 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Parameter |
Value |
|
Model |
PU516 3BSE013064R1 |
|
Product Type |
Engineering Board |
|
Dimensions |
2 x 32.3 x 12.6 cm |
|
Weight |
0.34 kg |
|
Bus Type |
5V 32-bit 33 MHz PCI bus |
|
Communication Interfaces |
1 x MB300, 1 x RS-232 |
|
Memory |
16 MB |
|
Compatibility |
ABB Advant Master process control system |
|
WEEE Category |
5. Small Equipment (≤50 cm) |
|
Number of Batteries |
0 |
Description
The ABB PU516 3BSE013064R1 is an Engineering Board primarily used to connect computers to ABB industrial machinery. It typically connects via a PCI slot on the computer motherboard, providing engineers with a way to program, configure, and monitor machine equipment. This Engineering Board allows technicians to monitor, program, and troubleshoot automation systems with direct access to controller parameters and diagnostic data. Its PCI slot compatibility ensures straightforward installation in standard industrial computers, eliminating complex setup procedures.
Applications
Large thermal power plants: As the core of the operator station, it collects and displays the real-time operating status of boilers and turbines.
Oil refineries: Acting as an accelerator in complex AF100 networks, ensuring rapid response from remote I/O stations.
Steel smelting plants: Used in high-magnetic-interference environments to transmit data from field controllers to the monitoring center at high speed.
Fertilizer production plants: Manage the backbone network communication of the plant's distributed control system (DCS).
Paper machinery plants: Used to coordinate the logical synchronization between various drive nodes of the paper machine and the host computer.
Troubleshooting
Unrecognized Hardware: Check if the board is fully inserted into the PCI slot, or clean the oxide layer on the gold fingers; check for hardware conflicts in Windows Explorer.
Interrupted Communication: Check if the terminating resistor at the end of the AF100 cable is loose, or if the external adapter is loose.
Software Driver Errors: Confirm that the Control IT or Advant software version matches the board firmware version.
Slow Data Transfer: Check the PCI interrupt number (IRQ) settings to avoid resource contention with other hardware devices.
FAQ
Q: Can the PWD86 57087234 PU516 run on a regular commercial computer motherboard?
A: It is physically compatible with PCI slots, but requires ABB's proprietary driver software and engineering license to function properly.
Q: Do I need to rewrite the program after replacing the PWD86 57087234 PU516?
A: No. It's just a physical communication channel. Just ensure the new card's Station ID is set identically to the original.
Q: Does the PWD86 57087234 PU516 card support hot-swapping?
A: Absolutely not. Replacement must be performed with the workstation powered off; operating it while powered on will damage the PCI interface.
Q: What's the difference between the PWD86 57087234 PU516 and an Ethernet card?
A: The PU516 runs the proprietary AF100 protocol, whose physical characteristics and signal standards are completely incompatible with standard Ethernet.
Q: What is the maximum communication distance of the PWD86 57087234 PU516?
A: Without repeaters, AF100 networks typically support 2000 meters (twisted pair) or longer (coaxial cable), depending on cable quality.