Omron GT1-OD32ML GT1 32-Point NPN Transistor Output Unit
Manufacturer: Omron
Condition: Brand New
Lead Time: In Stock
Origin: Japan
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Retain the exact model without adding the PNP -1 suffix.
- Select a compatible 40-contact connector or conversion cable.
- Budget 0.5 A per point and the applicable 2 A or 4 A common limit.
- Allocate two output words.
- Complete the I/O Unit interface chain and its end connection.
GT1-OD32ML GT1 32-Point NPN Transistor Output Unit
A 32-output NPN unit with a 40-contact high-density connector, photocoupler isolation and separate connector/terminal supply limits.
At a Glance
| Brand | Omron |
|---|---|
| Model | GT1-OD32ML |
| Product Type | High-density digital-output unit |
| Core Function | Driving discrete field actuators |
| Application | GT1 Multiple I/O terminals |
NPN output logic
The unit provides 32 sinking transistor outputs.
High-density connection
A 40-contact connector routes two 16-bit output words.
Supply-path current limits
The common current is limited to 2 A through connectors or 4 A through the terminal block.
Product Overview
GT1-OD32ML provides thirty-two NPN transistor outputs in an Omron MULTIPLE I/O TERMINAL. The high-density output connector connects field devices through suitable cables, I/O Blocks or Connector-Terminal Block Conversion Units.
The output circuits use photocoupler isolation. Their common-current limit depends on whether load power passes through the connector contacts or the terminal block, while local output LEDs and the TS indicator distinguish output status from I/O-interface communication status.
Key Functions
Drive NPN field loads
Thirty-two sinking transistor channels switch the connected DC loads.
Route two output words
Connector rows A and B carry the two groups of sixteen output signals.
Indicate interface conditions
Output LEDs show ON states and the TS LED identifies normal communication or an interface error.
Official Specifications
| Output channels and polarity | 32 NPN transistor outputs |
|---|---|
| Output connector | 40-contact high-density connector |
| Rated output current | 0.5 A per point |
| Maximum common current through connector | 2 A |
| Maximum common current through terminal block | 4 A |
| I/O supply range | 20.4–26.4 V DC |
| Maximum residual voltage | 1.2 V at 0.5 A DC |
| Maximum OFF-state leakage | 0.1 mA at 24 V DC |
| Maximum output response delay | ON: 0.5 ms; OFF: 1.5 ms |
| Electrical isolation | Photocoupler |
| Minimum insulation resistance | 20 MΩ at 250 V DC between isolated circuits |
| Dielectric strength | 500 V AC between isolated circuits |
| Internal-supply current | 65 mA maximum |
| I/O-supply current without load | 11 mA maximum |
| Process-data allocation | 2 output words |
| Operating temperature | −10 to +55 °C |
| Storage temperature | −25 to +65 °C |
| Operating humidity | 25–85% relative humidity, non-condensing |
| Mounting | 35 mm DIN track |
| Shock resistance | 200 m/s² |
Frequently Asked Questions
Is GT1-OD32ML the NPN or PNP version?
The model without the -1 suffix uses NPN transistor outputs.
Which common-current limit applies when I power loads through the connector of GT1-OD32ML?
Connector-fed load current must stay below 2 A, compared with the 4 A terminal-block limit.
Which plug can I use to make a cable for GT1-OD32ML?
The applicable Fujitsu plugs are FCN361J040-AU for soldering, FCN363J040-AU for crimping or FCN367J040-AU/F for pressure welding.
How many output words should I allocate to GT1-OD32ML?
The thirty-two outputs occupy two output words.
What does a red TS indicator mean on GT1-OD32ML?
A red TS indicator identifies an I/O Unit interface error.
Which cable connects GT1-OD32ML to an XW2B-40G4 or XW2B-40G5 conversion unit?
Use the appropriate XW2Z-@@@B connector cable.
Does a lit output indicator on GT1-OD32ML mean that output is ON?
Each output indicator lights when its corresponding output is ON.