- Set the transformer ratios and voltage connection arrangement to match the actual circuit.
- Distinguish the measured voltage circuits from the separate auxiliary power supply.
- Include the required communication expansion module when ordering Modbus RTU, PROFINET or PROFIBUS connectivity.
- Observe the indoor panel-mounting requirements, vertical orientation and environmental limits.
7KM2112-0BA00-3AA0 SENTRON PAC3200 Power Monitoring Device
PAC3200 panel meter with LCD, 1 A/5 A current inputs, wide-range AC/DC supply and integrated Modbus TCP over RJ45.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 7KM2112-0BA00-3AA0 |
| Product Type | Power monitoring device |
| Core Function | Three-phase electrical measurement and energy monitoring |
| Application | Stationary indoor switchboards and distribution panels |
Electrical measurement
Measures voltage, current, active and reactive power, frequency and energy for distribution-system monitoring.
Ethernet integration
The integrated RJ45 interface supports Modbus TCP; optional modules add the listed Modbus RTU, PROFINET or PROFIBUS connections.
Local indication and pulses
A white-backlit LCD with four operating keys is combined with one digital input and one switching or pulse output.
Product Overview
7KM2112-0BA00-3AA0 measures electrical quantities and energy in three-phase distribution systems, presenting values on an LCD and making them available through integrated Modbus TCP communication.
The wide-range auxiliary supply, 96 mm panel format and screw terminals support switchboard integration, while current-transformer ratios and voltage connection settings must match the installation.
Key Functions
Electrical measurement
Measures voltage, current, active and reactive power, frequency and energy for distribution-system monitoring.
Ethernet integration
The integrated RJ45 interface supports Modbus TCP; optional modules add the listed Modbus RTU, PROFINET or PROFIBUS connections.
Local indication and pulses
A white-backlit LCD with four operating keys is combined with one digital input and one switching or pulse output.
Official Specifications
| Auxiliary supply | 95–240 V AC or 110–340 V DC |
|---|---|
| Rated voltage measurement | 400 V line-to-neutral; 690 V line-to-line |
| Voltage measurement range | 40–480 V line-to-neutral; 70–831 V line-to-line |
| Current input ratings | 1 A or 5 A AC |
| Relative current measurement range | 10–120% of rated input current |
| Measured line frequency | 45–65 Hz with automatic detection |
| Voltage / current measurement error | ±0.3% / ±0.2% |
| Active-energy accuracy | Class 0.5 according to IEC 62053-22 |
| Reactive-energy accuracy | Class 2 according to IEC 61557-12 / IEC 62053-23 |
| Integrated communication | 1 RJ45 interface with Modbus TCP |
| Display / operating keys | LCD, 72 × 54 mm display, white backlight; 4 keys |
| Digital I/O | 1 input and 1 switching or pulse output |
| Digital output limits | Maximum 30 V DC and maximum 27 mA at signal 1 |
| Pulse-output duration | 30–500 ms; maximum switching frequency 17 Hz |
| Measurement connection | Screw-type terminals |
| Front protection / installed protection class | IP65 / Class II |
| Dimensions / installation depth | 96 × 96 × 56 mm / 51 mm |
| Mounting position | Vertical |
| Operating temperature / humidity | −10 to +55 °C / maximum 95% at 25 °C, non-condensing |
| Maximum installation altitude | 2,000 m |
Frequently Asked Questions
Which transformer secondary ratings can be used with 7KM2112-0BA00-3AA0?
The current inputs support rated AC secondary currents of either 1 A or 5 A.
Does 7KM2112-0BA00-3AA0 require a separate module for Modbus TCP?
Modbus TCP is available through the integrated RJ45 interface.
Can 7KM2112-0BA00-3AA0 connect directly to a PROFINET network?
PROFINET requires the appropriate optional communication module rather than using the standard Modbus TCP connection alone.
What auxiliary supply can power 7KM2112-0BA00-3AA0?
The wide-range supply accepts 95–240 V AC or 110–340 V DC.
How much depth is required behind the panel for 7KM2112-0BA00-3AA0?
The specified installation depth is 51 mm within an overall housing depth of 56 mm.
Can 7KM2112-0BA00-3AA0 issue energy pulses?
Its digital output can operate as a pulse output with a selectable duration of 30–500 ms.
Is 7KM2112-0BA00-3AA0 intended for an exposed outdoor installation?
The device is specified for stationary panels in closed rooms, with IP65 protection on the front.