- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the 100–120 V AC, 50/60 Hz input rating.
- Reserve sixteen input points.
- Use 0.3–0.75 mm² conductors and the permitted unsleeved crimp terminals.
- Apply the simultaneous-input derating curve at the actual voltage and temperature.
QX10 MELSEC-Q 16-Point AC Input Module
A 16-point AC input module for 100–120 V AC signals, with one common group, photocoupler isolation and an 18-point screw terminal block.
At a Glance
| Brand | Mitsubishi Electric |
|---|---|
| Model | QX10 |
| Product Type | AC input module |
| Core Function | Acquisition of AC field-switch states |
| Application | MELSEC-Q controller stations |
100–120 V AC
The input circuit is designed for 50 or 60 Hz AC signals.
16-point group
All sixteen inputs share common terminal TB17.
Local indication
Individual LEDs show the input ON state.
Product Overview
QX10 acquires sixteen AC input signals in a MELSEC-Q controller station. It uses a photocoupler input circuit and an 18-point terminal block, with sixteen inputs assigned to one common.
The module occupies sixteen input points in the I/O assignment. Signal-device selection needs to account for the ON and OFF thresholds, frequency-dependent input current, switching delay and the simultaneous-input derating curve.
Key Functions
Acquire AC switching states
The inputs accept 100–120 V AC at 50/60 Hz, with ON recognition from 80 V AC and 5 mA.
Interface through a terminal block
The 18-point screw terminal block assigns TB1–TB16 to the inputs and TB17 to common.
Indicate channel activity
Input LEDs turn on when the corresponding input state is ON.
Official Specifications
| Input points and common | 16 inputs; 16 points per common at TB17 |
|---|---|
| Rated input supply | 100–120 V AC, +10/−15%; 50/60 Hz ±3 Hz |
| Maximum input-voltage distortion | 5% |
| Rated input current at 100 V AC | Approximately 8 mA at 60 Hz; 7 mA at 50 Hz |
| Maximum inrush current | 200 mA within 1 ms at 132 V AC |
| ON threshold | At least 80 V AC and 5 mA |
| OFF threshold | No more than 30 V AC and 1.7 mA |
| Input impedance | Approximately 12 kΩ at 60 Hz; 15 kΩ at 50 Hz |
| Maximum response time | OFF to ON: 15 ms; ON to OFF: 20 ms at 100 V AC, 50/60 Hz |
| Input isolation | Photocoupler |
| Dielectric withstand voltage | 1,780 V AC rms for 3 cycles at 2,000 m altitude |
| Insulation resistance | At least 10 MΩ |
| External terminal block | 18-point screw terminal block |
| Applicable conductor size | 0.3–0.75 mm²; maximum outside diameter 2.8 mm |
| Applicable crimp terminal | R1.25-3; sleeved crimp terminals cannot be used |
| Occupied I/O allocation | 16 input points |
| Internal 5 V DC current | 50 mA typical with all points ON |
| Module weight | 0.17 kg |
Frequently Asked Questions
Can I connect a 24 V DC proximity sensor directly to QX10?
The input circuit is rated for 100–120 V AC rather than 24 V DC.
Which terminal is common for the sixteen inputs on QX10?
All sixteen input points share common terminal TB17.
Will a 10 ms AC pulse always be captured by QX10?
The OFF-to-ON response can take up to 15 ms at 100 V AC and 50 or 60 Hz.
What residual voltage must a field switch stay below to turn QX10 off?
The OFF condition requires no more than 30 V AC and 1.7 mA.
Can I use insulated-sleeve crimp terminals on QX10?
The specified R1.25-3 crimp terminals must be used without an insulating sleeve.
How many controller input addresses should I reserve for QX10?
Assign the module as a sixteen-point input module.
Can I keep all inputs of QX10 on at any cabinet temperature?
The permitted simultaneous ON ratio depends on the input voltage and ambient temperature and must remain within the module’s derating curve.