Siemens 6ES7144-4FF01-0AB0 SIMATIC ET 200pro 4AI U High Feature Voltage Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Order the required 6ES7194-4..00-0AA0 IO connection module separately.
- Use shielded analog signal cables no longer than 30 m.
- Match the input range, integration time and smoothing to the measurement task.
- Check the shared analog reference and enable only the diagnostics supported by the selected range.
6ES7144-4FF01-0AB0 SIMATIC ET 200pro 4AI U High Feature Voltage Input Module
Four High Feature voltage inputs for ±10 V, 0–10 V, ±5 V and 1–5 V measurement, with a bus module included and an IO connection module ordered separately.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7144-4FF01-0AB0 |
| Product Type | Analog voltage input module |
| Core Function | Acquiring voltage signals with channel diagnostics |
| Application | Decentralized ET 200pro analog measurement |
Selectable voltage ranges
Supports ±10 V, 0–10 V, ±5 V and 1–5 V input ranges across four analog inputs.
Measurement filtering
Configurable smoothing uses none, low, medium or high settings corresponding to 1, 4, 16 or 64 measurement cycles.
Channel diagnostics
Diagnostic alarms can be parameterized, with wire-break and short-circuit detection available in the 1–5 V range and a limit interrupt configurable for channel 0.
Product Overview
6ES7144-4FF01-0AB0 acquires four analog voltage signals in an ET 200pro station, combining selectable bipolar and unipolar input ranges with parameterized diagnostics.
Selectable integration and smoothing settings allow the measurement behavior to be matched to the process, while the IO connection module and signal shielding must suit the installed wiring.
Key Functions
Selectable voltage ranges
Supports ±10 V, 0–10 V, ±5 V and 1–5 V input ranges across four analog inputs.
Measurement filtering
Configurable smoothing uses none, low, medium or high settings corresponding to 1, 4, 16 or 64 measurement cycles.
Channel diagnostics
Diagnostic alarms can be parameterized, with wire-break and short-circuit detection available in the 1–5 V range and a limit interrupt configurable for channel 0.
Official Specifications
| Analog inputs | 4 voltage inputs |
|---|---|
| Rated supply | 24 V DC |
| Input voltage ranges | ±10 V; 0–10 V; ±5 V; 1–5 V |
| Typical supply / backplane current | 40 mA from 1L+; 12 mA from the 3.3 V backplane |
| Typical power loss | 1.1 W |
| Address allocation | 8 bytes |
| Sensor supply | 4 outputs; maximum output current 1 A up to 55 °C |
| Measurement method | Integrating |
| Resolution | 15 bits plus sign for ±10 V and ±5 V; 15 bits for 0–10 V and 1–5 V |
| Integration settings | 60, 20, 16.7 or 0.3 ms |
| Conversion time per channel | 60.8, 20.8, 17.5 or 1.1 ms according to integration setting |
| Smoothing factors | 1, 4, 16 or 64 measurement cycles |
| Operational voltage error | ±0.1% of input range over the overall temperature range |
| Basic voltage error at 25 °C | ±0.075% of input range |
| Linearity error | ±0.0075% of input range |
| Maximum shielded signal cable | 30 m |
| Diagnostics / limit interrupt | Parameterized diagnostic alarm; limit-value interrupt configurable for channel 0 |
| Channel isolation | No isolation between inputs; isolated from backplane bus |
| Dimensions (W × H × D) | 45 × 130 × 35 mm |
| Approximate weight | 150 g |
Frequently Asked Questions
Can 6ES7144-4FF01-0AB0 measure a 4–20 mA signal directly?
The specified measurement ranges are voltage ranges, so select a current-input module when direct current measurement is required.
Which unipolar ranges can be configured on 6ES7144-4FF01-0AB0?
The module supports 0–10 V and 1–5 V in addition to the bipolar ±10 V and ±5 V ranges.
Is the IO connection module included with 6ES7144-4FF01-0AB0?
The bus module is included, while the matching IO connection module must be ordered separately.
When can 6ES7144-4FF01-0AB0 report wire breaks and short circuits?
These diagnostics are available when the input is configured for the 1–5 V range.
Can every channel on 6ES7144-4FF01-0AB0 generate a limit-value interrupt?
The parameterizable limit-value hardware interrupt is specified for channel 0.
How does the high smoothing setting affect 6ES7144-4FF01-0AB0?
The high setting smooths measured values over 64 measurement cycles.
Are the analog channels of 6ES7144-4FF01-0AB0 isolated from one another?
The input channels are not mutually isolated, although they are isolated from the backplane bus.