Siemens 6ES7460-1BA00-0AB0 SIMATIC S7-400 IM 460-1 Local Expansion Send Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Install the send interface in the central rack and the IM 461-1 receive interface in each connected expansion rack.
- Keep each expansion line within 1.5 m and its module demand within 5 V/5 A.
- Do not fit a separate power supply in a power-transferred expansion rack.
- Check receiver revision, termination and unique rack numbering before restoring power.
6ES7460-1BA00-0AB0 SIMATIC S7-400 IM 460-1 Local Expansion Send Module
IM 460-1 send interface with two local expansion connections, transferring the P bus and 5 V power over links up to 1.5 m per line.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7460-1BA00-0AB0 |
| Product Type | Expansion send interface module |
| Core Function | Linking a central rack to local expansion racks |
| Application | S7-400 expansion with transferred 5 V power |
Two local expansion lines
Front connectors X1 and X2 provide separate lines, each serving one expansion rack.
Transferred rack power
Each line carries the P bus and supplies 5 V at up to 5 A to the connected expansion rack.
Link indication
Green C1/C2 LEDs indicate line state and the red EXTF LED indicates an external line fault.
Product Overview
6ES7460-1BA00-0AB0 links the S7-400 central rack to IM 461-1 receive interfaces in nearby expansion racks, transferring both the P bus and 5 V power through the expansion cable.
Each line serves one expansion rack with a 5 V, 5 A supply limit, so the rack arrangement must be planned without a separate expansion-rack power supply or communication-bus transfer.
Key Functions
Two local expansion lines
Front connectors X1 and X2 provide separate lines, each serving one expansion rack.
Transferred rack power
Each line carries the P bus and supplies 5 V at up to 5 A to the connected expansion rack.
Link indication
Green C1/C2 LEDs indicate line state and the red EXTF LED indicates an external line fault.
Official Specifications
| Expansion connections | 2 front connections, X1 and X2 |
|---|---|
| Expansion racks per line | 1 |
| Maximum line length | 1.5 m total per line |
| Power transferred to each rack | 5 V DC, maximum 5 A per line |
| 24 V power transfer | Not provided |
| Communication-bus transfer | Not provided |
| Backup-current transfer | Not provided |
| Current from 5 V backplane | Typically 50 mA; maximum 85 mA |
| Module power loss | Typically 250 mW; maximum 425 mW |
| Connection-cable family | 6ES7468-3... for P-bus and power transfer |
| Line indicators | C1 and C2 green; EXTF red |
| Dimensions (W × H × D) | 25 × 290 × 280 mm |
| Weight | 600 g |
Frequently Asked Questions
Can two expansion racks be connected to one line of 6ES7460-1BA00-0AB0?
Each line permits only one expansion rack, although the sender provides two separate lines.
Should a power supply be installed in the rack connected through 6ES7460-1BA00-0AB0?
A separate power supply must not be installed in an expansion rack powered through the IM 461-1 link.
Does 6ES7460-1BA00-0AB0 transfer the communication bus for CP or FM requirements?
The link transfers the P bus and 5 V power but does not transfer the communication bus.
How far can the expansion rack be placed from 6ES7460-1BA00-0AB0?
Keep the total connection length within 1.5 m on each line.
Which cable family should be selected for 6ES7460-1BA00-0AB0?
Use the 6ES7468-3 cable family intended for P-bus and power transfer with IM 460-1 and IM 461-1.
Does a receiver used with 6ES7460-1BA00-0AB0 always need an external terminator?
The older IM 461-1 1BA00 receiver uses terminator 6ES7461-1BA00-7AA0, while the 1BA01 revision integrates termination.
Can the expansion cable of 6ES7460-1BA00-0AB0 be changed with the racks energized?
Switch off the affected central and expansion-rack supplies before changing interface modules or their connecting cables.