Siemens 6EP1332-2BA20 SITOP PSU100S 24V DC 2.5A Power Supply
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Connect the protective conductor with the AC input because the power supply is protection Class I.
- Use the specified 35 mm EN 60715 DIN rail and maintain 50 mm clearance above and below the unit.
- Keep the 24 V OK relay circuit within its 60 V DC and 0.3 A contact rating.
- Apply the stated temperature derating and additional output-voltage or low-input-voltage limitations when operating away from nominal conditions.
- If increasing output power by parallel operation, observe the manufacturer’s limit of two parallel supplies and use the supported arrangement.
6EP1332-2BA20 SITOP PSU100S 24V DC 2.5A Power Supply
A compact SITOP smart supply with automatic 120/230 V AC range selection, adjustable DC output and a 24 V OK signaling contact.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1332-2BA20 |
| Product Type | Stabilized single-phase power supply |
| Core Function | Converting AC mains to isolated DC power |
| Application | 24 V DC industrial control circuits |
Automatic AC range selection
Accepts 85–132 V AC or 170–264 V AC without a manual range selector.
DC reserve
Provides 2.5 A rated current and overload capability for temporary load demand.
Status contact
A green LED and normally open relay contact indicate 24 V OK.
Product Overview
6EP1332-2BA20 supplies regulated 24 V DC at 2.5 A from a single-phase AC mains connection, with automatic selection between the 120 V and 230 V input ranges.
The 32.5 mm-wide unit mounts on a standard DIN rail and includes an output-adjustment potentiometer, short-circuit protection and a relay contact for monitoring the DC supply.
Key Functions
Adjust the DC output for the control circuit
The front potentiometer adjusts the output from 22.8 to 28 V DC around the 24 V nominal value.
Support temporary load peaks
The supply provides 150% of rated output current for up to 5 seconds per minute, with the permitted continuous current depending on ambient temperature.
Monitor the 24 V rail
A green 24 V OK LED and a normally open relay contact provide local and wired status indication.
Official Specifications
| Nominal AC Input | 120/230 V AC; automatic range selection |
|---|---|
| AC Input Ranges | 85–132 V AC and 170–264 V AC |
| Permissible Line Frequency | 47–63 Hz |
| Rated Input Current | 1.25 A at 120 V AC; 0.74 A at 230 V AC |
| Maximum Inrush Current | 33 A at 25 °C |
| Minimum Mains Buffering | 20 ms at rated output current and 93/187 V input |
| Rated DC Output | 24 V DC; 2.5 A; 60 W |
| Output Adjustment Range | 22.8–28 V DC via potentiometer |
| Temperature-Dependent Output Current | Up to 3 A at +45 °C; derating 3%/K from +60 to +70 °C |
| Temporary Overload Capability | 150% of rated output current for up to 5 s/min |
| Maximum Residual Ripple and Voltage Peak | 150 mV ripple; 240 mV peak |
| Typical Efficiency and Power Loss | 85%; 10 W at rated output |
| DC OK Signaling Contact | Normally open relay; 60 V DC, 0.3 A rating |
| Output Protection | Constant-current short-circuit characteristic; overvoltage limited below 33 V for an internal fault |
| Input-to-Output Isolation and Protection Class | Galvanically isolated; Class I; IP20 enclosure |
| Operating Ambient Temperature | −25 to +70 °C with natural convection and applicable derating |
| Storage and Transport Temperature | −40 to +85 °C |
| Conductor Termination | Screw terminals for 0.5–2.5 mm² conductors |
| Enclosure Dimensions and Net Weight | 32.5 × 125 × 120 mm; 0.32 kg |
| Installation Clearance | 50 mm above and below; 0 mm left and right |
Frequently Asked Questions
Must I switch 6EP1332-2BA20 manually between 120 V and 230 V mains?
The supply automatically selects between its 85–132 V AC and 170–264 V AC input ranges.
Can I trim the output of 6EP1332-2BA20 above 24 V?
The front potentiometer adjusts the output between 22.8 and 28 V DC.
How much cooling space should I leave around 6EP1332-2BA20?
Leave 50 mm above and below the enclosure, while adjacent installation is permitted with no required side clearance.
Can 6EP1332-2BA20 continuously deliver 3 A at 70 °C?
Continuous 3 A operation is specified only up to +45 °C, and the output is derated by 3% per kelvin from +60 to +70 °C.
How can a PLC monitor the output condition of 6EP1332-2BA20?
Use the normally open 24 V OK relay contact within its 60 V DC and 0.3 A rating.
What reserve does 6EP1332-2BA20 provide for a brief load peak?
The supply permits 150% of rated output current for up to five seconds per minute.
Which mounting rail accepts 6EP1332-2BA20?
The enclosure snaps onto an EN 60715 DIN rail of 35 × 7.5 mm or 35 × 15 mm.