Siemens 6EP1332-2BA20 SITOP PSU100S 24V DC 2.5A Fons Potentiae
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Connect the protective conductor with the AC input because the power supply is protection Class I.
- Use the specified 35 mm EN 60715 DIN rail and maintain 50 mm clearance above and below the unit.
- Keep the 24 V OK relay circuit within its 60 V DC and 0.3 A contact rating.
- Apply the stated temperature derating and additional output-voltage or low-input-voltage limitations when operating away from nominal conditions.
- Si augmentat potestatem exire per operationem parallelam, observa limitem fabricantis de duobus subministrationibus parallelis et utere dispositione suffultam.
6EP1332-2BA20 SITOP PSU100S 24V DC 2.5A Power Supply
A compact SITOP smart supply with automatic 120/230 V AC range selection, adjustable DC output and a 24 V OK signalling contact.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6EP1332-2BA20 |
| Typus Producti | Stabilized single-phase power supply |
| Functio principalis | Converting AC mains to isolated DC power |
| Applicatio | 24 V DC industrial control circuits |
Automatic AC range selection
Accepts 85–132 V AC or 170–264 V AC without a manual range selector.
DC reserve
Provides 2.5 A rated current and overload capability for temporary load demand.
Status contact
A green LED and normally open relay contact indicate 24 V OK.
Product Overview
6EP1332-2BA20 supplies regulated 24 V DC at 2.5 A from a single-phase AC mains connection, with automatic selection between the 120 V and 230 V input ranges.
The 32.5 mm-wide unit mounts on a standard DIN rail and includes an output-adjustment potentiometer, short-circuit protection and a relay contact for monitoring the DC supply.
Key Functions
Adjust the DC output for the control circuit
The front potentiometer adjusts the output from 22.8 to 28 V DC around the 24 V nominal value.
Support temporary load peaks
The supply provides 150% of rated output current for up to 5 seconds per minute, with the permitted continuous current depending on ambient temperature.
Monitorare la linea a 24 V
Un LED verde «24 V OK» e un contatto di relè normalmente aperto forniscono indicazione locale e cablata dello stato.
Official Specifications
| Nominale AC Ingang | 120/230 V CA; selezione automatica della gamma |
|---|---|
| Gamme di ingresso CA | 85–132 V CA e 170–264 V CA |
| Frequencia lineae permissa | 47–63 Hz |
| Evaluatus Input Correntia | 1,25 A a 120 V CA; 0,74 A a 230 V CA |
| Maxima Currus Inrumpens | 33 A a 25 °C |
| Bufferisation minimal del rete | 20 ms alla corrente di uscita nominale e all’ingresso di 93/187 V |
| Uscita CC nominale | 24 V CC; 2,5 A; 60 W |
| Intervalum regulandi output | 22.8–28 V DC per potentiometrum |
| Current output dependens a temperaturam | Usque ad 3 A ad +45 °C; decrementum 3%/K ab +60 ad +70 °C |
| Capacitas temporanea supra oneris | 150% currentis nominalis pro usque ad 5 s/min |
| Ripple residuum maximum et vertex tensionis | 150 mV ripple; 240 mV vertex |
| Efficientia typica et peregrinatio energiae | 85%; 10 W ad currentem nominalem |
| Contactus signali DC OK | Relais apertum normaliter; 60 V DC, 0.3 A |
| Tutela Exitus | Characteristicam curtocircuiti ad currentem constantem; tensionem supra 33 V limitatam pro defectu interno |
| Classis Isolationis et Protectionis Inter Intram et Extram | Isolatum galvanice; Classis I; custodia IP20 |
| Operans ambientium temperatus | −25 ad +70 °C cum convectione naturali et deductione applicabili |
| Temperatura servandi et transportandi | −40 ad +85 °C |
| Terminus conductoris | Terminales vitreae pro conductoribus 0.5–2.5 mm² |
| Dimensiones Custodiae et Pondus Netum | 32.5 × 125 × 120 mm; 0.32 kg |
| Spatium ad installationem | 50 mm supra et infra; 0 mm ad sinistram et dexteram |
Quaestiones Frequenter Rogatae
Num oportet me commutare 6EP1332-2BA20 manu inter 120 V et 230 V?
The supply automatically selects between its 85–132 V AC and 170–264 V AC input ranges.
Can I trim the output of 6EP1332-2BA20 above 24 V?
The front potentiometer adjusts the output between 22.8 and 28 V DC.
How much cooling space should I leave around 6EP1332-2BA20?
Leave 50 mm above and below the enclosure, while adjacent installation is permitted with no required side clearance.
Can 6EP1332-2BA20 continuously deliver 3 A at 70 °C?
Continuous 3 A operation is specified only up to +45 °C, and the output is derated by 3% per kelvin from +60 to +70 °C.
How can a PLC monitor the output condition of 6EP1332-2BA20?
Use the normally open 24 V OK relay contact within its 60 V DC and 0.3 A rating.
What reserve does 6EP1332-2BA20 provide for a brief load peak?
The supply permits 150% of rated output current for up to five seconds per minute.
Which mounting rail accepts 6EP1332-2BA20?
The enclosure snaps onto an EN 60715 DIN rail of 35 × 7.5 mm or 35 × 15 mm.