Overview
- Configure the key panel from STEP 7 V5.5 or use the supported TIA Portal engineering environment.
- Use the combined eight-pin IO budget when assigning local inputs and outputs.
- Provide a 2–6 mm mounting plate and the specified cutout and connector clearance.
- Use the standard KP8 PN for non-safety operator functions and keep the rear protected within the enclosure.
6AV3688-3AY36-0AX0 SIMATIC HMI KP8 PN Key Panel
Eight short-stroke keys with multicolor LEDs, eight configurable digital IO pins and a two-port PROFINET switch.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6AV3688-3AY36-0AX0 |
| Product Type | PROFINET operator key panel |
| Core Function | Direct operator commands and multicolor status indication |
| Application | Compact machine operator stations with physical pushbuttons |
Physical operator commands
Eight direct keys function as S7 input IO and support user-definable key labels for machine operation.
Multicolor status signaling
Eight direct LEDs provide adjustable brightness and five selectable colors for machine state indication.
Local IO and network integration
Eight configurable IO pins and a two-port PROFINET switch combine local field signals with networked operator control.
Product Overview
6AV3688-3AY36-0AX0 provides a compact physical operator interface using eight short-stroke keys and individually controlled multicolor LEDs.
Eight configurable digital IO pins connect local signals, while the integrated PROFINET switch supports line or ring network arrangements without an additional switch at the panel.
Key Functions
Physical operator commands
Eight direct keys function as S7 input IO and support user-definable key labels for machine operation.
Multicolor status signaling
Eight direct LEDs provide adjustable brightness and five selectable colors for machine state indication.
Local IO and network integration
Eight configurable IO pins and a two-port PROFINET switch combine local field signals with networked operator control.
Official Specifications
| Short-stroke keys | 8; user-definable labels |
|---|---|
| LED status colors | Red, green, blue, yellow and white; adjustable brightness |
| Configurable digital IO | 8 pins total across inputs and outputs |
| Digital input voltage | 24 V DC |
| Digital output ratings | 24 V DC; maximum 100 mA per channel and 800 mA per group |
| Output short-circuit protection | Provided |
| Rated supply and range | 24 V DC; 20.4–28.8 V DC |
| Rated supply current | 0.3 A |
| Integrated Ethernet switch | 2 ports |
| PROFINET functions | PROFINET IO, IRT and MRP |
| Front and rear protection | IP65 front; IP20 rear |
| Operating temperature, vertical | 0–55 °C |
| Operating temperature at maximum tilt | 0–45 °C |
| Maximum tilt without external ventilation | 30° forward or backward |
| Storage/transport temperature | -20 to +60 °C |
| Maximum relative humidity | 95%, non-condensing |
| Key service life | 1,500,000 switching cycles |
| Front dimensions (W × H) | 98 × 155 mm |
| Cutout and mounting depth | 67.7 × 129.7 mm cutout; 49 mm depth including angled SIMATIC Ethernet connector |
| Weight without packaging | 270 g |
Frequently Asked Questions
Can 6AV3688-3AY36-0AX0 provide eight inputs and eight outputs simultaneously?
The configurable pins form a combined total of eight inputs and outputs.
Can 6AV3688-3AY36-0AX0 be used as a PROFIsafe emergency-stop interface?
This standard panel does not support PROFIsafe and is not suitable for safety functions.
Which LED colors can I use for status indication on 6AV3688-3AY36-0AX0?
The LEDs support red, green, blue, yellow and white with adjustable brightness.
Do I need a separate switch to continue a PROFINET line through 6AV3688-3AY36-0AX0?
The integrated two-port switch supports line and ring network arrangements without an external switch at the panel.
What cutout is required for 6AV3688-3AY36-0AX0?
Use a 67.7 by 129.7 mm cutout in a mounting plate 2 to 6 mm thick.
Can 6AV3688-3AY36-0AX0 retain the 55 °C operating limit when tilted to the maximum angle?
At the maximum permitted tilt the operating limit drops to 45 °C.
What load current can a digital output on 6AV3688-3AY36-0AX0 switch?
Each digital output supports a maximum of 100 mA, with an 800 mA maximum for the group.