- Assign all sixteen channels in the engineering configuration and document which channels operate as inputs, outputs or counters.
- Calculate 1L+, 2L+, sensor-supply and output-group currents separately.
- Use the prescribed ET 200AL M8/M12 connectors and suitable sealing arrangements for the installed environment.
- Check the input delay required by each connected sensor, especially on channels 8–15.
6ES7143-5AH00-0BA0 SIMATIC ET 200AL DIQ 16x24VDC/0.5A Digital I/O Module
Sixteen configurable DIQ channels combine digital sensing and 0.5 A switching in a compact IP65/IP67 module with eight M12 connections.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7143-5AH00-0BA0 |
| Product Type | Digital input/output module |
| Core Function | Configurable acquisition and switching of digital signals |
| Application | Distributed machine I/O outside the control cabinet |
Flexible channel assignment
Configure the sixteen DIQ channels for the required mix of digital inputs and outputs rather than treating them as two independent sixteen-channel banks.
Pulse counting
Use up to four 32-bit up/down counters for pulse signals up to 2 kHz.
Distributed load switching
Switch 24 V DC loads at up to 0.5 A per channel within the 4 A limit of each eight-output group.
Product Overview
6ES7143-5AH00-0BA0 provides sixteen configurable digital channels for an ET 200AL installation, allowing the station configuration to assign the available channels to sensing or switching duties.
Separate 1L+ and 2L+ supplies support the distributed load arrangement, while counter operation adds pulse acquisition for suitable machine signals.
Key Functions
Flexible channel assignment
Configure the sixteen DIQ channels for the required mix of digital inputs and outputs rather than treating them as two independent sixteen-channel banks.
Pulse counting
Use up to four 32-bit up/down counters for pulse signals up to 2 kHz.
Distributed load switching
Switch 24 V DC loads at up to 0.5 A per channel within the 4 A limit of each eight-output group.
Official Specifications
| Digital channels | 16 configurable DIQ channels |
|---|---|
| Rated supply / permissible range | 24 V DC / 20.4–28.8 V DC for 1L+ and 2L+ |
| No-load supply current | Typically 60 mA from 1L+ and 40 mA from 2L+ |
| Maximum current per supply | 4 A for 1L+; 4 A for 2L+ |
| Sensor supply | 8 outputs; 1.4 A total and maximum 0.7 A per load-voltage supply |
| Typical power loss | 4 W |
| Input characteristic | IEC 61131 Type 3, P-reading |
| Input signal thresholds | Signal 0: −3 to +5 V; signal 1: 11–30 V |
| Configurable input delay | 0.05–20 ms; minimum 1.6 ms for channels 8–15 |
| Counter resources | Up to 4 counters, 32 bits including sign, maximum 2 kHz |
| Rated output current | 0.5 A per channel |
| Output group current | Maximum 4 A per group of 8 outputs |
| Short-circuit protection | Per channel; typical response threshold 0.7 A |
| Rated lamp load | 5 W |
| Switching frequency | 100 Hz resistive; 0.5 Hz inductive; 1 Hz lamp load |
| Maximum unshielded signal cable | 30 m |
| Connection system | 5-pole M12 I/O; 4-pole M8 supply; shielded 4-pin M8 ET connection |
| Protection / operating temperature | IP65/IP67 / −30 to +55 °C |
| Dimensions (W × H × D) | 45 × 159 × 40 mm |
| Approximate weight | 195 g |
Frequently Asked Questions
Can 6ES7143-5AH00-0BA0 provide sixteen inputs and sixteen outputs simultaneously?
The module has sixteen configurable DIQ channels in total, so the input/output assignment must stay within that shared channel count.
How should the load current be checked for 6ES7143-5AH00-0BA0?
Check both the 0.5 A limit of each output and the 4 A total limit of its eight-output group.
Can 6ES7143-5AH00-0BA0 count pulses from a machine sensor?
Up to four counters support pulse frequencies of 2 kHz with 32-bit up/down counting.
Why can an input-delay setting differ between channels on 6ES7143-5AH00-0BA0?
Channels 8–15 require a minimum delay of 1.6 ms even though the overall configurable range begins at 0.05 ms.
How far can an unshielded sensor cable run from 6ES7143-5AH00-0BA0?
The maximum specified unshielded signal-cable length is 30 m.
Which connectors are required when wiring 6ES7143-5AH00-0BA0?
The module uses five-pole M12 I/O connectors and four-pole M8 supply connections with a shielded four-pin M8 ET connection.
What temperature range should be allowed around 6ES7143-5AH00-0BA0?
Design the installation for the specified operating range of −30 to +55 °C while observing the channel and current limits.