Overview
Place of Origin: |
USA |
Brand Name: |
HONEYWELL |
Model Number: |
8C-TAIDB1 51307133-175 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Parameter |
Value |
|
Part Number |
8C-TAIDB1 51307133-175 |
|
Part Type |
Analog Input Module |
|
Dimensions |
29.5 x 12 x 7.5 cm |
|
Weight |
0.38 kg |
|
Redundancy |
Redundant |
|
Coating |
Yes |
|
Input Type |
Voltage; Current (2-wire or self-powered transmitters); Single-ended or differential inputs |
|
Input Channels |
16 (single-ended or differential) |
|
A/D Converter Resolution |
16-bit |
|
Input Range |
0–5 V; 1–5 V; 0.4–2 V; 4–20 mA (through 250 Ω) |
|
Voltage Rating |
24 V DC |
|
Module Current Rating |
310 mA |
|
Common Mode Rejection Ratio (DC to 60 Hz, 500 Ω imbalance) |
70 dB |
|
Common Mode Voltage (DC to 60 Hz) |
-6 to +5 V peak |
|
Normal Mode Rejection Ratio (60 Hz) |
19 dB |
|
Normal Mode Filter Response |
Single-pole RC, -3 dB @ 6.5 Hz |
|
Crosstalk (DC to 60 Hz, channel-to-channel) |
-60 dB |
|
Input Impedance (Voltage inputs) |
>10 MΩ (powered) |
|
Maximum Normal Mode Input |
±30 V (no damage) |
|
Input Scan Rate |
50 ms |
|
Hardware Accuracy (23.5°C ±2°C) |
±0.075% of full scale |
|
Hardware Accuracy (0 to 60°C) |
±0.15% of full scale |
|
Transmitter Field Power Conditioning |
Individually protected current limiting circuits (no fuse required) |
|
Module Removal/Insertion Under Power |
Supported |
Description
The Honeywell 8C-TAIDB1 51307133-175 is a Honeywell analog input module. This module is primarily used to build a dual-redundant signal receiving architecture, working in conjunction with two analog input cards plugged into it (primary and backup). In industrial automation control systems, it is responsible for receiving continuously changing current or voltage signals from instruments in the production field, such as electrical signals output from temperature transmitters, pressure transmitters, flow meters, and level gauges.
Applications
Large-scale Oil Refineries: Use 50 ms scanning for critical 4–20 mA process monitoring.
Precision Pharmaceutical Plants: Provide high-resolution monitoring of temperature, humidity, and pressure.
Semiconductor Wafer Fabs: Detect small voltage and current deviations in CVD processes.
Nuclear Power Plants: Use redundant architecture and ±1500 V isolation for reliable monitoring.
Notable Features
Extensive self-diagnostics
Optional redundancy
Supports either Single Ended / Differential Inputs
HART-capable, multivariable instruments and multiple modems for fast collection of control variables
Fast loop scan
FAQ
Q: 8C-TAIDB1 51307133-175 Analog Input Module how many channels does it have and does it support redundancy?
A: 16 single-ended or differential channels, supports redundancy (Redundant), coated.
Q: What is the most fundamental difference between 8C-TAIDB1 51307133-175 Analog Input Module and the previous model (8C-TAIDA1)?
A: This model supports redundancy, while TAIDA1 is non-redundant.
Q: What is the A/D conversion resolution of 8C-TAIDB1 51307133-175 Analog Input Module?
A: 16-bit.
Q: What input signal ranges are supported by 8C-TAIDB1 51307133-175 Analog Input Module?
A: Supports 0–5V, 1–5V, 0.4–2V voltage inputs and 4–20 mA current input.
Q: What are the operating voltage and module current of 8C-TAIDB1 51307133-175 Analog Input Module?
A: Operating voltage is 24 V DC, rated current is 310 mA.