Overview
Place of Origin: |
USA |
Brand Name: |
HONEYWELL |
Model Number: |
8C-TAIDA1 51307131-175 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Parameter |
Value |
|
Part Number |
8C-TAIDA1 51307131-175 |
|
Part Type |
Analog Input Module |
|
Dimensions |
22 x 12 x 8 cm |
|
Weight |
0.32 kg |
|
Redundancy |
Non-redundant |
|
Coating |
Yes |
|
Input Type |
Voltage; Current (2-wire or self-powered transmitters); Single-ended or differential inputs |
|
Input Channels |
16 (single-ended or differential) |
|
A/D Converter Resolution |
16-bit |
|
Input Range |
0–5 V; 1–5 V; 0.4–2 V; 4–20 mA (through 250 Ω) |
|
Voltage Rating |
24 V DC |
|
Module Current Rating |
310 mA |
|
Common Mode Rejection Ratio (DC to 60 Hz, 500 Ω imbalance) |
70 dB |
|
Common Mode Voltage (DC to 60 Hz) |
-6 to +5 V peak |
|
Normal Mode Rejection Ratio (60 Hz) |
19 dB |
|
Normal Mode Filter Response |
Single-pole RC, -3 dB @ 6.5 Hz |
|
Crosstalk (DC to 60 Hz, channel-to-channel) |
-60 dB |
|
Input Impedance (Voltage inputs) |
>10 MΩ (powered) |
|
Maximum Normal Mode Input |
±30 V (no damage) |
|
Input Scan Rate |
50 ms |
|
Hardware Accuracy (23.5°C ±2°C) |
±0.075% of full scale |
|
Hardware Accuracy (0 to 60°C) |
±0.15% of full scale |
|
Transmitter Field Power Conditioning |
Individually protected current limiting circuits (no fuse required) |
|
Module Removal/Insertion Under Power |
Supported |
Description
The Honeywell 8C-TAIDA1 51307131-175 is a Honeywell analog input module. This module connects to various transmitters and instruments in industrial production environments and works in conjunction with connected electronic modules. In automated control systems, it receives continuous current or voltage signals from the field, such as electrical signals output from pressure transmitters, flow meters, and level gauges.
Applications
Fine chemical plant: collects differential pressure signals from reactors for fast closed-loop control of small pressure changes.
Semiconductor plant: acquires high-sensitivity temperature and humidity signals in cleanroom environments with minimal signal distortion.
Non-ferrous metal smelting plant: corrosion-resistant coating protects the module while collecting voltage and current data from electrolytic cells.
Notable Features
Extensive self-diagnostics
Optional redundancy
Supports either Single Ended / Differential Inputs
HART-capable, multivariable instruments and multiple modems for fast collection of control variables
Fast loop scan
FAQ
Q: How many channels does 8C-TAIDA1 51307131-175 support and does it support redundancy?
A: 16 single-ended or differential channels, no redundancy support, with coating.
Q: What is the accuracy and scan rate of 8C-TAIDA1 51307131-175?
A: Accuracy ±0.075% F.S. at room temperature, scan rate 50 ms.
Q: What input signal ranges does 8C-TAIDA1 51307131-175 support?
A: 0–5 V, 1–5 V, 0.4–2 V voltage and 4–20 mA current.
Q: What is the operating voltage and module current of 8C-TAIDA1 51307131-175?
A: 24 V DC operating voltage, 310 mA rated current.
Q: Does 8C-TAIDA1 51307131-175 require fuses for field power distribution and does it support hot swapping?
A: No fuse required due to current limiting protection, supports live hot insertion/removal.