Overview
Place of Origin: |
USA |
Brand Name: |
GE |
Model Number: |
IC697MDL940 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Model: |
IC697MDL940 |
|
Module Type |
Relay Output Module |
|
Dimensions (HxWxD): |
4 x 22 x 29.1 cm |
|
Weight: |
0.66 kg |
|
Relay Type: |
Fixed coil, moving armature |
|
Outputs per Module: |
16 (8 points Form C, 8 points Form A) |
|
Isolation: |
1500 V any output to backplane; 500 V between Form C circuits or Form A groups |
|
Maximum Load Current (Resistive): |
Per Module: 16 A; Per Group (Form A): 4 A |
|
Nominal Voltage Rating: |
120/240 VAC or 5/24/125 VDC |
|
Maximum Power: |
480 VA (AC loads) or 60 W (DC loads) |
|
Maximum Load Current (Resistive): |
2 A from 5–265 VAC (47–63 Hz), 2 A from 5–30 VDC, 0.2 A from 31–125 VDC, 0.2 A from 31–150 VDC (Form A only) |
|
Minimum Load Current: |
10 mA |
|
Maximum Output Leakage: |
1 mA at 120 VAC |
|
Response Time-On: |
10 ms maximum |
|
Response Time-Off: |
10 ms maximum |
|
Switching Frequency: |
20 cycles/minute (inductive load) |
|
Contact Type: |
Silver alloy |
|
Contact Resistance: |
0.2 Ω maximum |
|
Contact Life: |
Mechanical: 20 × 10^6 operations; Electrical: 10^5 operations at rated resistive load |
|
Protection: |
3 A fuse per output; Snubber R=47 Ω, C=0.015 µF |
|
Current Required from 5V Bus: |
0.75 A |
|
Standards Compliance: |
VME System designed to support VME standard C.1 |
Description
The IC697MDL940 is a Series 90-70 Programmable Logic Controller (PLC) module, specifically a Relay output module with a total of Sixteen (16) relay output channels. Specifically, it has Eight (8) Form C Contact outputs and Eight (8) Form A or Normally Open (N.O.) in Two (2) groups of Four (4) Form A contacts each channel. This module has a nominal voltage rating of 120/240 VAC or 5/24/125 VDC with a maximum power consumption of 480 VA for AC loads or 60 watts for DC loads. It has maximum load current ratings of 2.0 amps from 5 to 265 VAC at 47-63 Hz; 2.0 amps from 5 to 30 VDC; 0.2 amps from 31 to 125 VDC and 0.2 amps from 31 to 150 VDC applicable for Form A contact outputs only while the module’s minimum load current is 10 mA. Each output channel has a maximum response time of 10 ms for both On and Off signal transition and switching frequency of 20 Cycles per minute when used with an inductive load.
Applications
Large metallurgical plants: Used to drive AC contactors, DC solenoid valves, and indicator lights in high-dust environments.
Paper and pulp mills: Manage interlocks of motor starters of different voltage levels in automated production lines.
Oil and chemical plants: Perform complex logical switching and control various pump sets in non-explosion-proof areas.
Features
16 points - 8 isolated Form C
- 2 groups of 4 Form A
2 amp per point switching capacity
RC snubber and fuse protection per point
No user power required
Removable field wiring terminal
Functions
The 16 point Relay Output Module is versatile, rugged, and easy to use. It will switch a variety of low to medium power loads such as relays, contactors, and lamps. The resistive rating of the module is 2 amps per point at 120/240 VAC or 24 VDC and 0.2 amps per point for 125 VDC. Power to energize the relay coils is supplied by the module and each output is individually fused and suppressed with an RC snubber. LED indicators which display the ON - OFF status of each point on the logic (PLC) side of the circuit are located at the top of the module.
Module Mechanical Keying
This module includes a mechanical key that prevents inadvertent substitution of one module type for another in a given slot. The key fits a uniquely shaped area on the board below the connector. Each module has a key packaged with it. When the module is first installed, the key latches onto the backplane center rail. When the module is extracted, the key remains in the center rail, configuring the slot to accept only identical module types. If it is necessary to change the module location in the rack after the key has been latched onto the center rail of the rack, the key can be removed by pushing it upward to unhook the latch while pulling it off the rail. It may then be reinserted onto the module and the module inserted into the rack in the desired location.
FAQ
Q: Does the IC697MDL940 come with a warranty?
A: Yes, the IC697MDL940 includes a 1-year warranty.
Q: What is the output contact form of this module?
A: This module has Eight (8) isolated Form C contacts and Eight (8) Form A contacts in Two (2) groups of Four (4) channels.
Q: What are the maximum load current of the IC697MDL940’s output channels?
A: Maximum load current per channel are 2.0 amps from 5 to 265 VAC (maximum), 47-63 Hz; 2.0 amps from 5 to 30 VDC (maximum); 0.2 amps from 31 to 125 VDC (maximum); 0.2 amps from 31 to 150 VDC (maximum, Form A only).
Q: What is the operating voltage of the relay output channels?
A: The IC697MDL940 relay output channels are operable with 120/240 VAC or 5/24/125 VDC.
Q: What is the output configuration of the IC697MDL940?
A: The output configuration of the IC697MDL940 consists of Eight (8) individually isolated Form C relay outputs and Two (2) groups of Four (4) Form A outputs.
Q: What are the maximum current ratings of the IC697MDL940?
A: The IC697MDL940 maximum current ratings are 2.0 amps from 5 to 265 VAC (maximum), 47-63 Hz; 2.0 amps from 5 to 30 VDC (maximum); 0.2 amps from 31 to 125 VDC (maximum); 0.2 amps from 31 to 150 VDC (maximum, Form A only).
Q: Does the IC697MDL940 come with individual output fuse?
A: Yes. Each channel of the IC697MDL940 has an integrated 3 A fuse.