- Overview
- Specifications
- Description
- Applications
- Installation
- Key Features
- FAQ
- Recommended Products
Overview
Place of Origin: |
USA |
Brand Name: |
GE |
Model Number: |
IC693MDL940 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Parameter |
Value |
|
Module Name |
IC693MDL940 Relay Output Module |
|
Module Type |
Relay Output Module |
|
Dimensions |
3.5 x 13 x 13.5 cm |
|
Weight |
0.4 kg |
|
Rated Voltage |
24 V DC; 120/240 V AC (nominal) |
|
Operating Voltage |
5–30 V DC; 5–250 V AC, 50/60 Hz |
|
Outputs per Module |
16 (four groups of 4 outputs each) |
|
Isolation |
Field to logic side: 1500 V; Between groups: 500 V |
|
Maximum Load |
2 A per output (pilot duty); 4 A max per common |
|
Minimum Load |
10 mA |
|
Maximum Inrush |
5 A |
|
On Response Time |
15 ms max |
|
Off Response Time |
15 ms max |
|
Internal Power Consumption |
7 mA (all outputs on) from 5 V bus; 135 mA (all outputs on) from relay 24 V bus |
Description
The IC693MDL940 2 Amp Relay Output module for the Series 90-30 Programmable Logic Controller provides 16 normally-open relay circuits for controlling output loads provided by the user. The output switching capacity of each output is 2 amps. The output points are arranged in four groups of four points each. Each group has a common power output terminal. The relay outputs can control a wide range of user-supplied load devices, such as: motor starters, solenoids, and indicators. Power for the internal relay circuits is provided by the +24 volt DC bus on the backplane. The user must supply the AC or DC power to operate field devices. There are no fuses on this module. LED indicators which provide the ON/OFF status of each point are located at the top of the module. The LEDs are arranged in two horizontal rows with eight green LEDs in each row; the top row labeled A1 through 8 (points 1 through 8) and the bottom row labeled B1 through 8 (points 9 through 16). An insert goes between the inside and outside surface of the hinged door. The surface towards the inside of the module (when the hinged door is closed) has circuit wiring information, and circuit identification information can be recorded on the outside surface. The outside left edge of the insert is color-coded red to indicate a high-voltage module. This module can be installed in any I/O slot of a 5 or 10-slot baseplate in a Series 90-30 PLC system.
Applications
Various industrial automation:Temperature control,Motor speed control,Electric heating control,Light intensity control
Manufacturing
Chemical industry
Food industry
Installation
1 General Installation Requirements
This product is intended for use with a Series 90-30 or RX3i system. Its components are considered open equipment [having live electrical parts that may be accessible to users] and must be installed in an ultimate enclosure that is manufactured to provide safety. As a minimum, the enclosure shall provide a degree of protection against solid objects up to 12mm (e.g. fingers). This equates to a NEMA/UL Type 1 enclosure or an IP20 rating (IEC60529) providing at least a pollution degree 2 environment.
2 Installation in Hazardous Areas
The system containing the MDL940 module must be mounted within an ultimate enclosure that can be accessed only by the use of a tool.
Key Features
Sixteen NO relay outputs: Supports AC or DC load switching.
Four isolated groups: Allows different voltages per group for flexible wiring.
Wide operating voltage range: 5–30 VDC and 5–250 VAC compatibility.
2-ampere per-channel rating: Suitable for a variety of low-power industrial actuators.
LED channel indicators: Provides real-time output status monitoring.
15 ms switching response: Ensures consistent relay actuation timing.
High isolation levels: 1500 V field-to-logic and 500 V group-to-group separation.
Standard 90-30 rack integration: Occupies a single PLC slot for streamlined installation.
FAQ
Q: What is an IC693MDL940?
A: The IC693MDL940 is a 2 Amp Relay Output module for the GE Fanuc Series 90-30. It provides 16 normally-open relay circuits for controlling output loads provided by the user.
Q: What is the output switching capacity for each circuit?
A: 2 amps.
Q: What can the relay outputs control?
A: They can control motor starters, solenoids, and indicators.
Q: What kind of power does the IC693MDL940 use?
A: Power to operate IC693MDL940 must be supplied by the user and be either AC or DC power.
Q: Are there fuses on this module?
A: No.
Q: What is the rated voltage for IC693MDL940?
A: 24 volts DC or 120/240 volts AC.
Q: What is the operating voltage for IC693MDL940?
A: 5 to 30 volts DC or 5 to 250 volts AC, 50/60 Hz.