Overview
Place of Origin: |
USA |
Brand Name: |
ICS TRIPLEX |
Model Number: |
T8891C |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Parameter |
Value |
|
Part Number |
T8891C |
|
Part Name |
Trusted Speed Monitor Output FTA |
|
Dimensions |
10.2 × 18 × 12.7 cm |
|
Weight |
0.55 kg |
|
Field Common Insulation (Basic) |
250 V DC |
|
Maximum Impulse Withstand |
2500 V DC |
|
Operating Temperature |
0°C to +60°C |
|
Storage Temperature |
-25°C to +70°C |
|
Temperature Change Rate |
±0.5°C/min |
|
Relative Humidity |
10–95% RH (non-condensing) |
|
AC Rated Current |
0.1 to 3 A |
|
AC Rated Voltage |
5 to 120 / 144 V AC |
|
Breaking Capacity (Resistive Load) |
432 VA |
|
Electrical Endurance |
100,000 cycles |
|
Temporary Overload |
2× max rated current for 40 ms (repeated once per second) |
|
Nominal Coil Voltage |
24 V DC |
|
Pull-in Voltage |
18 V DC |
|
Release Voltage |
2.4 V DC |
|
Coil Resistance |
740 to 906 Ω |
|
Coil Current |
29.2 mA @ 24 V DC |
|
Nominal Coil Power |
700 mW |
Description
The T8891C Trusted Speed Monitor Output Field Termination Assembly (FTA) is a DIN-rail mounted interface module designed for high-reliability industrial speed monitoring systems. It provides a safe and flexible field output interface for rotating machinery protection within Triple Modular Redundant (TMR) architectures.
Applications
Hydropower Plants: Controls turbine trip systems during overspeed events.
Oil Refineries: Manages emergency shutdown for compressor systems.
Gas Stations: Controls remote turbine and pipeline safety systems.
Metal Smelters: Provides trip control for mills and blowers.
Marine Chemical Plants: Ensures shutdown logic in harsh offshore environments.
Features
Two online tested, fault tolerant, volt free contact output channels.
Each output can be used as either a normally open or a normally closed contact.
Fault tolerant quad redundant output relay structure.
Load feedback monitoring.
Contact status feedback.
Force guided contact, safety relays.
Standard DIN Rail mounting.
Each output rated.
Relays, fuses and current sensors can all be replaced in situ.
FAQ
Q: What are the coil rated power and pickup voltage of the T8891C relay output terminal?
A: Coil voltage is 24 V DC, power 700 mW (29.2 mA), pickup 18 V DC, release 2.4 V DC.
Q: What AC switching capability does the T8891C output FTA support?
A: It supports 5–144 V AC, 0.1–3 A, with 432 VA maximum resistive breaking capacity.
Q: What overload capability does the T8891C module have under surge conditions?
A: It tolerates 2× rated current for 40 ms, repeatable once per second.
Q: What are the electrical life and isolation ratings of the T8891C module?
A: Electrical life is 100,000 cycles; withstands 2500 V DC surge, with 250 V DC basic isolation.
Q: What environmental limits apply to the T8891C module?
A: Temperature change rate ±0.5°C/min, humidity 10%–95% non-condensing.