Siemens SIMATIC PCS 7 6ES7653-2CM00-0XB0 System Expansion Card PO 800
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the card only with SIMATIC PCS 7 CPU 410 SMART and verify the exact controller article number.
- Keep the engineered project at or below 800 PCS 7 process objects because the performance class cannot be expanded.
- Install the card in the dedicated rear system-expansion-card slot before commissioning and confirm valid recognition.
- In a redundant system, fit one card to each CPU and use the same process-object quantity on both sides.
- Do not substitute the 2CP variant or a CPU 410 Expansion Pack for this CPU 410 SMART card.
Siemens · SIMATIC PCS 7
6ES7653-2CM00-0XB0 System Expansion Card PO 800
Siemens 6ES7653-2CM00-0XB0 is the SIMATIC PCS 7 System Expansion Card PO 800 for CPU 410 SMART, setting the controller performance class to a fixed maximum of 800 PCS 7 process objects.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7653-2CM00-0XB0 |
| Product Type | PCS 7 System Expansion Card PO 800 |
| Core Function | Sets the CPU 410 SMART performance class to a maximum of 800 process objects |
| Application or Compatible Series | SIMATIC PCS 7 with CPU 410 SMART |
Exact Identification
Match the complete article number and PO 800 designation; do not substitute the similarly numbered 2CP variant.
Capacity Check
Confirm that the engineered CPU 410 SMART project remains within the fixed limit of 800 PCS 7 process objects.
Redundant Setup
For a redundant pair, install one card in each CPU and use the same process-object quantity on both sides.
Product Overview
Siemens 6ES7653-2CM00-0XB0 is the SIMATIC PCS 7 System Expansion Card PO 800 for CPU 410 SMART, setting the controller performance class to a fixed maximum of 800 PCS 7 process objects.
The card defines a maximum capacity of 800 PCS 7 process objects for the CPU 410 SMART. It installs in the system-expansion-card slot on the rear of the CPU and forms an essential part of the controller hardware. The controller checks the installed card at startup and enters STOP if a valid card is not detected.
Key Functions
Fixed 800-PO Performance Class
The card defines a maximum capacity of 800 PCS 7 process objects for the CPU 410 SMART.
Dedicated CPU Integration
It installs in the system-expansion-card slot on the rear of the CPU and forms an essential part of the controller hardware.
Startup Validation
The controller checks the installed card at startup and enters STOP if a valid card is not detected.
Official Specifications
| Hardware Functional Status | 3 |
|---|---|
| Firmware Version | V2.0 |
| PLC Basic-Unit Design | Conformal coating according to ISA-S71.04 severity levels G1, G2 and G3; operation up to 70 °C |
| Integrated Work Memory | 8 MB maximum |
| Work Memory Expansion | Not expandable |
| Maximum Data Block Size | 64 KB |
| SFC 22 CREATE_DB Total Limit | 256 KB |
| Maximum Input Address Area | 4.5 KB in CPU 410 SMART |
| Maximum Output Address Area | 4.5 KB in CPU 410 SMART |
| Operating Temperature | 0 to 70 °C |
| Width | 8 mm |
| Height | 16 mm |
| Depth | 25 mm |
| Approximate Weight | 20 g |
| ATEX Marking | II 3G Ex nA IIC T4 Gc |
| General Approvals | CE, CSA, UL, cULus, FM, RCM, KC, EAC and CCC |
Frequently Asked Questions
Which controller is 6ES7653-2CM00-0XB0 designed to work with?
It is designed specifically for the SIMATIC PCS 7 CPU 410 SMART.
Can 6ES7653-2CM00-0XB0 be expanded beyond 800 process objects?
No. The SMART PO 800 card fixes the maximum at 800 process objects, and CPU 410 Expansion Packs cannot increase it.
How should 6ES7653-2CM00-0XB0 be matched in a redundant CPU 410 SMART system?
Each CPU needs its own card, and both cards must specify the same process-object quantity.
Where is 6ES7653-2CM00-0XB0 installed?
It is inserted into the dedicated system-expansion-card slot on the rear of the CPU before commissioning.
What happens if 6ES7653-2CM00-0XB0 is not detected by the CPU?
The CPU enters STOP, requests a memory reset and records the event in the diagnostic buffer.
What memory and I/O limits should engineers consider with 6ES7653-2CM00-0XB0?
The configuration provides up to 8 MB of non-expandable work memory and up to 4.5 KB each for input and output addresses.
What environmental range applies to 6ES7653-2CM00-0XB0?
It is specified for operation from 0 to 70 °C and uses conformal coating rated to ISA-S71.04 severity levels G1, G2 and G3.