A diaphragm-operated differential pressure switch with a 100–1000 Pa setting range for air and non-corrosive gases.
At a Glance
| Brand | Siemens |
|---|---|
| Model | QBM81-10 |
| Product Type | Mechanical pressure switch |
| Core Function | Air-pressure differential monitoring |
| Application | Ventilation and air-conditioning systems |
100–1000 Pa
The adjustment range corresponds to 1–10 mbar.
Changeover contact
One single-pole changeover switch provides the electrical interface.
Vertical calibration
Horizontal mounting shifts the switching point by 11 Pa.
Product Overview
QBM81-10 monitors pressure differences in ventilation and air-conditioning equipment. A spring-loaded diaphragm operates a single-pole changeover contact, supporting filter, airflow and fan-belt monitoring.
The setpoint is adjusted beneath the cover, with automatic reset and a factory-set switching differential. Pressure tubing should rise continuously toward the switch to avoid condensation collecting in low points.
Key Functions
Detect pressure changes
The diaphragm responds to differential pressure, underpressure or overpressure in air and non-corrosive gas circuits.
Provide a switching signal
The changeover contact connects terminals 1–2 at lower pressure and 1–3 at higher pressure.
Support duct installation
The included FK-PZ3 kit provides two duct adaptors, four fixing screws and 2 m of tubing.
Official Specifications
| Pressure setting range | 100–1000 Pa; 1–10 mbar |
|---|---|
| Switch contact | Single-pole changeover, multi-layer contact |
| Contact duty at 250 V AC | 5 A maximum resistive; 3 A maximum inductive at cos φ greater than 0.6 |
| Low-voltage contact duty | 24 V AC or DC, at least 0.01 A |
| Switching reset and differential | Automatic reset; factory-set differential |
| Mechanical service life | More than 1 million switching cycles |
| Maximum unilateral overload | 7,500 Pa over −30 to +75 °C; 5,000 Pa over −30 to +85 °C |
| Housing protection | IP54 to EN 60529 |
| Electrical connection | 3 screw terminals; PG11 cable gland |
| Pressure connections | Male hose connections, 6.2 mm diameter |
| Horizontal mounting offset | Cover upward: +11 Pa; cover downward: −11 Pa |
| Operating and storage temperature | Operation: −30 to +85 °C; storage: −40 to +85 °C |
| Maximum ambient humidity | Below 90% RH, without condensation |
| Housing and cover | Glass-fiber-reinforced polycarbonate housing; polycarbonate cover |
| Packaged weight | 0.19 kg including mounting bracket |
Frequently Asked Questions
Which pressure port on QBM81-10 connects upstream of a filter?
Connect the higher upstream pressure to P1 and the lower downstream pressure to P2.
Will horizontal mounting change the setting of QBM81-10?
Relative to vertical calibration, the switching point rises by 11 Pa with the cover upward and falls by 11 Pa with the cover downward.
How should I route the tubing connected to QBM81-10?
Mount the switch above the pressure connection points and route the tubing upward without loops.
Can I use tubing longer than 2 m with QBM81-10?
Longer tubing is permitted, but lengths above 2 m increase the response time.
Does QBM81-10 require manual resetting after pressure recovers?
The switch resets automatically.
Which contact closes at the higher-pressure state of QBM81-10?
The contact changes to terminals 1–3 at higher pressure.
What external line protection is required for QBM81-10?
Use a slow fuse rated no more than 10 A or an EN 60898 type B, C or D circuit breaker rated no more than 13 A.