Overview
SIEMENS SIMOVERT MASTERDRIVES

6SE7090-0XX84-0FJ0 SIMOVERT MASTERDRIVES SLB SIMOLINK Board

The SLB board links MASTERDRIVES units into a fiber-optic SIMOLINK ring for data exchange and synchronization, with external 24 V DC supply support.

At a Glance

Brand Siemens
Model 6SE7090-0XX84-0FJ0
Product Type Drive communication option board
Core Function SIMOLINK drive data exchange
Application Compatible MASTERDRIVES converters and inverters

Optical ring link

SIMOLINK uses dedicated optical input and output connections.

Dispatcher or transceiver

Parameterization selects the board role in the ring.

External supply input

A 24 V DC supply can keep the ring node active while the converter is powered down.

Product Overview

6SE7090-0XX84-0FJ0 is the SLB SIMOLINK option board for compatible SIMOVERT MASTERDRIVES units. It exchanges drive data and synchronizes participating drives to a common system clock through a closed fiber-optic ring.

The board can operate as a dispatcher or transceiver, reads ring telegrams and stores selected data, while its external supply connection supports ring continuity when the host converter is powered down.

Ordering focus: Plan a closed ring with powered nodes, correct optical input/output routing and the required external supply continuity.
Key Functions

Synchronized drive communication

The SIMOLINK ring transfers data between participating drives and provides a common system clock for synchronization.

Selectable node role

Parameterization selects dispatcher or transceiver operation, with up to 201 nodes permitted on the ring.

Power continuity and diagnostics

The external 24 V DC feed supports operation independently of host converter power, and three LEDs indicate the board operating state.

Official Specifications
Data transfer rate 11 MBaud
Maximum ring size 201 nodes
Internal supply requirement 5 V DC, maximum 600 mA
External supply requirement 24 V DC, maximum 200 mA
Maximum plastic-fiber node spacing 40 m
Maximum glass-fiber node spacing 300 m
Maximum propagation delay 3 clock times
Board size (length × width) 90 × 83 mm
Cooling Natural-air cooling
Operating temperature 0 to 70 °C
Storage and transport temperature −25 to +70 °C
Relative humidity Maximum 85% in operation; 95% in storage and transport; no condensation
Pollution degree 2
Operating climate class 3K3 according to DIN IEC 721-3-3
Frequently Asked Questions

Must I connect both optical ports on 6SE7090-0XX84-0FJ0?

Both the optical input and optical output must be connected to complete the closed SIMOLINK ring.

Which optical connector is the input on 6SE7090-0XX84-0FJ0?

The lower dark-gray connection is the input and the upper light-gray connection is the output.

Can 6SE7090-0XX84-0FJ0 keep the ring running when the host converter is off?

An external 24 V DC supply keeps the board operating so ring data transfer can continue with the converter powered down.

Can I remove the external supply from 6SE7090-0XX84-0FJ0 during normal ring operation?

Removing the external supply during bus operation is not permitted because the supply changeover resets the board and loses telegrams.

How do I select dispatcher or transceiver operation on 6SE7090-0XX84-0FJ0?

The operating role is selected through parameterization.

Can I use a 100 m plastic-fiber span between 6SE7090-0XX84-0FJ0 and the next node?

Plastic fiber is limited to 40 m between nodes, while glass fiber permits up to 300 m.

Can I install 6SE7090-0XX84-0FJ0 in slot C when a sensor board already needs that slot?

The sensor board requires slot C, so the SIMOLINK board must use another suitable option slot.

Compatibility & Ordering Notes
Before ordering 6SE7090-0XX84-0FJ0: Match the SLB board to the host MASTERDRIVES option arrangement and plan optical ring routing, node power continuity and the selected dispatcher or transceiver role.

Compatibility Checklist for 6SE7090-0XX84-0FJ0

  • Connect both optical ports in the correct transmission direction.
  • Keep every ring node powered during communication.
  • Use external 24 V DC where host-off ring continuity is required.
  • Reserve slot C for a sensor board when present and use another suitable slot for SLB.
Hot Selling Models
EEC6000-L
SC400 1203 A 40009
CFF004
LFR-D-7-MINI-A
8US1943-3AA00
09670090344
DRT-240-24
6EC1140-3A
18MR-BA-1LT-S4-C
GH20XTKEXXXF
ADVU-50-25-APA
DEA-BG06
535/2000mV DC 535-002
40.52.7.024.0000
ADN-32-60-A-PPS-A

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.