Siemens SIMATIC NET 6GK7443-5DX03-0XE0 CP 443-5 Extended PROFIBUS Processor
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Install the processor only in a supported SIMATIC S7-400 or S7-400H rack and CPU configuration.
- Reserve one single-width S7-400 module slot and verify the available 5 V backplane current.
- Use a 9-pin RS-485 PROFIBUS connector with correct shield continuity and segment termination.
- Restore the configured PROFIBUS station address, transmission rate and DP slave assignments.
- Keep the aggregate and per-slave input and output data within the stated limits.
- Confirm the STEP 7 hardware catalog entry and installed firmware before enabling DPV1 or CiR functions.
- Budget S7, FDL, PG, OP and routing connections against both CP and CPU resource limits.
- Verify redundant bus and fault-tolerant connection settings separately when used in an S7-400H system.
- Do not connect Ethernet or PROFINET cabling because the network interface is PROFIBUS only.
- Review the CPU and project migration requirements before using the 6GK7443-5DX05-0XE0 successor.
Siemens · SIMATIC NET CP 443-5 Extended
6GK7443-5DX03-0XE0 CP 443-5 Extended PROFIBUS Communications Processor
Siemens 6GK7443-5DX03-0XE0 is the SIMATIC NET CP 443-5 Extended communications processor for connecting SIMATIC S7-400 systems to PROFIBUS. It operates as a DP master class 1 and provides DPV1, S7 communication, PG and OP communication, direct data exchange, and S5-compatible SEND/RECEIVE services over FDL connections. The processor supports field-device data-record routing, time distribution, DP diagnostics and S7 routing in compatible S7-400 and S7-400H projects. Its network interface is PROFIBUS RS-485 through a 9-pin D-sub socket, so it must not be specified as an Ethernet or PROFINET communications processor; feature availability also depends on the installed firmware, with DPV1 available from V4.0 and CiR listed for V5.x.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6GK7443-5DX03-0XE0 |
| Product Type | PROFIBUS DP Communications Processor |
| Core Function | Adds PROFIBUS DP master and S7 communication services to an S7-400 controller |
| Application or Compatible Series | SIMATIC S7-400 and S7-400H automation systems |
Exact Network Interface
Use the 9-pin RS-485 PROFIBUS connection; this processor does not provide an Ethernet or PROFINET port.
Firmware Feature Check
Confirm the installed firmware because DPV1 requires V4.0 or later and CiR is listed for V5.x.
Replacement Project Review
Back up the STEP 7 station and verify the CPU, rack, bus address, transmission rate, slave map and connection resources before exchange.
Product Overview
Siemens 6GK7443-5DX03-0XE0 is the SIMATIC NET CP 443-5 Extended communications processor for connecting SIMATIC S7-400 systems to PROFIBUS. It operates as a DP master class 1 and provides DPV1, S7 communication, PG and OP communication, direct data exchange, and S5-compatible SEND/RECEIVE services over FDL connections. The processor supports field-device data-record routing, time distribution, DP diagnostics and S7 routing in compatible S7-400 and S7-400H projects. Its network interface is PROFIBUS RS-485 through a 9-pin D-sub socket, so it must not be specified as an Ethernet or PROFINET communications processor; feature availability also depends on the installed firmware, with DPV1 available from V4.0 and CiR listed for V5.x.
Operates as DP master class 1 with direct slave data exchange, SYNC, FREEZE and constant bus-cycle support. Provides S7, PG and OP communication plus S5-compatible SEND/RECEIVE over specified FDL, free layer 2, broadcast and multicast connections. Supports S7 routing, field-device data-record routing, class 2 diagnostic requests and topology measurement with a diagnostic repeater.
Key Functions
DP Master Coordination
Operates as DP master class 1 with direct slave data exchange, SYNC, FREEZE and constant bus-cycle support.
PROFIBUS Communication Services
Provides S7, PG and OP communication plus S5-compatible SEND/RECEIVE over specified FDL, free layer 2, broadcast and multicast connections.
Routing and Diagnostics
Supports S7 routing, field-device data-record routing, class 2 diagnostic requests and topology measurement with a diagnostic repeater.
Official Specifications
| PROFIBUS Transmission Rates | 9.6, 19.2, 45.45, 93.75, 187.5 and 500 kbit/s; 1.5, 3, 6 and 12 Mbit/s |
|---|---|
| PROFIBUS Connector | 9-pin D-sub female socket |
| Network Component Supply at Interface | 5 V DC, maximum 100 mA |
| Backplane Supply | 5 V DC from the S7-400 backplane bus |
| Typical Backplane Current | 1.0 A at 5 V DC |
| Power Loss | 5.5 W |
| Operating Temperature | 0 to +60 °C |
| Storage and Transport Temperature | -40 to +70 °C |
| Relative Humidity | Maximum 95% at +25 °C |
| Permitted Installation Altitude | Up to 2000 m above sea level |
| Module Dimensions | 25 × 292 × 200 mm |
| Approximate Module Weight | 800 g |
| Maximum DP Slaves | 125 |
| Total DP Input Area | Maximum 4 KB |
| Total DP Output Area | Maximum 4 KB |
| Input Area per DP Slave | Maximum 244 bytes |
| Output Area per DP Slave | Maximum 244 bytes |
| Consistent Area per Module | Maximum 128 bytes |
| FDL Connection Capacity | Maximum 32 connections |
| S7 Connections over PROFIBUS | Up to 48, depending on the CPU |
Frequently Asked Questions
Is 6GK7443-5DX03-0XE0 an Ethernet or PROFIBUS module?
It connects through a 9-pin RS-485 PROFIBUS interface and does not provide Ethernet or PROFINET connectivity.
Can 6GK7443-5DX03-0XE0 operate as a PROFIBUS DP slave?
It is specified as a DP master class 1 and is not intended to provide the DP slave role.
How many DP slaves can 6GK7443-5DX03-0XE0 control?
The configured network can contain up to 125 DP slaves within the stated input, output and connection limits.
Which PROFIBUS speeds are available on 6GK7443-5DX03-0XE0?
Selectable rates extend from 9.6 kbit/s through 12 Mbit/s using the supported PROFIBUS steps.
When can 6GK7443-5DX03-0XE0 use DPV1 services?
DPV1 requires installed firmware V4.0 or later together with a compatible CPU and STEP 7 project.
Does 6GK7443-5DX03-0XE0 support configuration changes during RUN?
CiR is listed for V5.x firmware, so verify the installed firmware and project configuration before relying on that function.
Can 6GK7443-5DX03-0XE0 be replaced by the current successor?
Siemens identifies 6GK7443-5DX05-0XE0 as the successor, but the CPU, firmware, rack and project requirements must be checked before replacement.