Siemens SIMATIC NET 6GK7443-1EX11-0XE0 CP 443-1 Ethernet
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Product Overview
- Key Functions
- Official Specifications
- Frequently Asked Questions
- Compatibility & Ordering Notes
- Hot Selling Models
- Recommended Products
Overview
Siemens · SIMATIC NET S7-400
6GK7443-1EX11-0XE0 CP 443-1 Industrial Ethernet Processor
Siemens 6GK7443-1EX11-0XE0 is the SIMATIC NET CP 443-1 processor for S7-400 Industrial Ethernet communication using ISO transport, TCP/IP, UDP, S7 communication and SEND/RECEIVE services.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6GK7443-1EX11-0XE0 |
| Product Type | S7-400 Industrial Ethernet communication processor |
| Core Function | Connects an S7-400 controller to ISO, TCP/IP and UDP networks |
| Application or Compatible Series | SIMATIC S7-400 communication systems |
Interface Match
Confirm whether the installed connection uses RJ45, AUI or the fifteen-pin Sub-D arrangement.
Connection Capacity
Reconcile S7 and open-communication connection counts with the existing controller project.
Legacy Replacement
Review CPU compatibility, STEP 7 configuration and successor restrictions before exchanging this earlier CP generation.
Product Overview
Siemens 6GK7443-1EX11-0XE0 is the SIMATIC NET CP 443-1 processor for S7-400 Industrial Ethernet communication using ISO transport, TCP/IP, UDP, S7 communication and SEND/RECEIVE services.
ISO transport, TCP/IP, UDP and S7 communication can be used within the documented connection limits. SEND/RECEIVE, Fetch/Write, RFC1006 and multicast functions support controller data exchange. NTP and SICLOCK support allow the processor to participate in plant time synchronization.
Key Functions
Multi-Protocol Ethernet Communication
ISO transport, TCP/IP, UDP and S7 communication can be used within the documented connection limits.
Open Communication Services
SEND/RECEIVE, Fetch/Write, RFC1006 and multicast functions support controller data exchange.
Time Synchronization
NTP and SICLOCK support allow the processor to participate in plant time synchronization.
Official Specifications
| Industrial Ethernet Data Rate | 10 to 100 Mbit/s |
|---|---|
| Ethernet Interfaces | One Industrial Ethernet interface |
| Electrical Connection | RJ45 port with AUI support and 15-pin Sub-D socket for AUI or ITP |
| Backplane Supply Voltage | 5 V DC |
| Permitted Supply Tolerance | Plus or minus 5 percent |
| Typical Backplane Current | 1.4 A at 5 V DC |
| Power Loss | 8.6 W |
| Operating Temperature | 0 to 60 °C |
| Storage and Transport Temperature | -40 to 70 °C |
| Maximum Operating Humidity | 95 percent at 25 °C without condensation |
| Degree of Protection | IP20 |
| Module Format | Compact S7-400 single-width module |
| Dimensions | 25 x 290 x 210 mm |
| Net Weight | 0.7 kg |
| Maximum Modules per CPU | 14 |
| Maximum Open-Communication Connections | 64 |
| Maximum User Data per ISO, ISO-on-TCP or TCP Connection | 8 KiB |
| Maximum User Data per UDP Connection | 2 KiB |
| Maximum S7 Communication Connections | 48 |
| Required Configuration Software | STEP 7 V5.1 SP2 or higher |
Frequently Asked Questions
Which Ethernet protocols can 6GK7443-1EX11-0XE0 handle?
The processor supports ISO transport, TCP/IP, UDP, S7 communication and open SEND/RECEIVE services.
How much data can 6GK7443-1EX11-0XE0 transfer in one UDP job?
A UDP connection can carry up to two kibibytes of user data per job.
How many S7 connections are available on 6GK7443-1EX11-0XE0?
The documented maximum is forty-eight S7 communication connections.
Which STEP 7 release can configure 6GK7443-1EX11-0XE0?
Use STEP 7 V5.1 SP2 or a later version that supports the installed CPU and processor.
Does 6GK7443-1EX11-0XE0 support network time synchronization?
Yes, it supports NTP and SICLOCK-related time functions.
Can I move a project directly from an older CP to 6GK7443-1EX11-0XE0?
The hardware type, interface arrangement, CPU compatibility and connection configuration must all be reviewed before migration.
What must remain powered off when replacing 6GK7443-1EX11-0XE0?
Remove rack power before extracting or inserting the communication processor to avoid peripheral faults.
Compatibility & Ordering Notes
Compatibility Checklist
- Check the installed S7-400 CPU and firmware against the processor compatibility list.
- Document the IP address, protocol connections, time settings and access restrictions before replacement.
- Power down the rack before removing or inserting the module.