Siemens 6ES7521-1BH00-0AB0 SIMATIC S7-1500 ET 200MP DI 16x24VDC HF Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Provide a suitable front connector in addition to the included U-connector.
- Check two-wire sensor leakage and wire-break detection requirements.
- Match the configured input delay to the process response and isochronous timing.
- Check the hardware functional status for low-temperature operation and use a suitable safety module for safety functions.
6ES7521-1BH00-0AB0 SIMATIC S7-1500 ET 200MP DI 16x24VDC HF Input Module
Sixteen-channel 24 V DC HF input module with adjustable filtering, diagnostics, hardware interrupts and isochronous operation in a 35 mm housing.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7521-1BH00-0AB0 |
| Product Type | Digital input module |
| Core Function | Acquiring digital field signals with diagnostics |
| Application | Modular machine and distributed I/O stations |
Adjustable signal filtering
Input delay is configurable from 0.05 to 20 ms for the required signal response.
Channel and module diagnostics
Supply monitoring, wire-break detection and channel fault LEDs support maintenance.
Synchronized acquisition
Isochronous mode and hardware interrupts support time-coordinated digital-signal processing.
Product Overview
6ES7521-1BH00-0AB0 acquires sixteen 24 V DC digital signals in an S7-1500 or ET 200MP station, with channel filtering, diagnostics and hardware-interrupt functions.
The inputs share one sixteen-channel potential group, while the backplane is isolated; the U-connector is included and the front connector is selected separately.
Key Functions
Adjustable signal filtering
Input delay is configurable from 0.05 to 20 ms for the required signal response.
Channel and module diagnostics
Supply monitoring, wire-break detection and channel fault LEDs support maintenance.
Synchronized acquisition
Isochronous mode and hardware interrupts support time-coordinated digital-signal processing.
Official Specifications
| Input arrangement | 16 sinking, P-reading inputs in one group; IEC 61131 type 3 |
|---|---|
| Electronics supply | 24 V DC rated; 19.2–28.8 V DC permitted |
| Maximum supply current | 20 mA at 24 V DC |
| Backplane power consumption | 1.1 W |
| Typical power loss | 2.6 W |
| Input thresholds | Signal 0: −30 to +5 V; signal 1: +11 to +30 V |
| Typical signal-1 input current | 2.5 mA |
| Input-delay settings | 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms |
| Two-wire sensor leakage limit | 1.5 mA maximum quiescent current |
| Maximum input cable length | 1,000 m shielded; 600 m unshielded |
| Counter functions | Up to 2 upward counters, 32-bit width, with gate start/stop |
| Isochronous timing | 80 µs minimum TCI at 50 µs filtering; 250 µs minimum bus cycle |
| Diagnostics and interrupts | Diagnostic alarms, hardware interrupts and supply-voltage monitoring |
| Wire-break detection | Input current below 350 µA |
| Short-circuit diagnostics | Not provided |
| Isolation | One group of 16; isolated from backplane, not between channels or from electronics supply; 707 V DC type test |
| Safety-function suitability | Not suitable for safety functions |
| Operating temperature | From FS05: −30 to +60 °C horizontal; −30 to +40 °C vertical |
| Connection hardware | U-connector included; front connector not included |
| Dimensions and approximate weight | 35 × 147 × 129 mm (W × H × D); 240 g |
Frequently Asked Questions
Does the included U-connector of 6ES7521-1BH00-0AB0 replace the front connector?
The U-connector is included, but the front connector must be selected separately.
What leakage current is allowed for a two-wire sensor on 6ES7521-1BH00-0AB0?
The sensor quiescent current must not exceed 1.5 mA.
At what input current can 6ES7521-1BH00-0AB0 detect a wire break?
The specified wire-break threshold is below 350 µA.
What is the shortest configurable input delay on 6ES7521-1BH00-0AB0?
The minimum configurable input delay is 0.05 ms.
Can 6ES7521-1BH00-0AB0 serve as a safety input module?
The module is not suitable for safety functions.
Are all sixteen input channels of 6ES7521-1BH00-0AB0 mutually isolated?
The channels share one potential group and are isolated from the backplane rather than from each other.
Does the −30 °C operating limit apply to every hardware revision of 6ES7521-1BH00-0AB0?
The −30 °C minimum applies from hardware functional status FS05.