- Use the matching S7-400 station and the specified twenty-four-volt DC load circuit.
- Observe output grouping, current loading and the permitted load-specific switching frequency.
- Do not parallel channels for current uprating; redundant control is limited to outputs in the same group.
- Plan the field-cable length and controller fault handling without assuming a module diagnostics function.
6ES7422-1BH11-0AA0 SIMATIC S7-400 SM 422 Digital Output Module
SM 422 with sixteen 24 V DC / 2 A outputs, electronic short-circuit protection and potential separation in groups of eight.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7422-1BH11-0AA0 |
| Product Type | Digital output module |
| Core Function | DC actuator signal switching |
| Application | S7-400 rack-based control systems |
Sixteen DC output channels
Rated two-ampere outputs switch compatible twenty-four-volt field loads.
Electronic load-fault protection
Clocked electronic short-circuit protection responds at the specified threshold range.
Grouped potential separation
Groups of eight outputs are isolated within the module arrangement and from the backplane bus.
Product Overview
6ES7422-1BH11-0AA0 provides sixteen DC load outputs for an S7-400 station.
The module combines two-ampere rated channels with defined load-switching limits, electronic fault-current protection and grouped potential separation from the backplane.
Key Functions
Sixteen DC output channels
Rated two-ampere outputs switch compatible twenty-four-volt field loads.
Electronic load-fault protection
Clocked electronic short-circuit protection responds at the specified threshold range.
Grouped potential separation
Groups of eight outputs are isolated within the module arrangement and from the backplane bus.
Official Specifications
| Load supply | 24 V DC; permitted 20.4–28.8 V |
|---|---|
| Maximum no-load current | 30 mA from L+; 160 mA from the 5 V backplane |
| Typical power loss | 5 W |
| Output channels and rated current | 16 outputs; 2 A per channel |
| Permitted on-state current | 5 mA to 2.4 A |
| Maximum off-state residual current | 0.5 mA |
| Minimum on-state voltage | L+ minus 0.5 V |
| Clocked short-circuit response | Electronic; typical threshold 2.8–6 A |
| Inductive turn-off voltage limit | −30 V |
| Maximum lamp load | 10 W per output |
| Load resistance range | 24 Ω to 4 kΩ |
| Output delays | Maximum 1 ms for both on and off transitions with resistive load |
| Resistive and lamp switching | Maximum 100 Hz resistive; 10 Hz lamp load |
| DC13 inductive switching | Maximum 0.2 Hz at 1 A; 0.1 Hz at 2 A |
| Maximum output cable | 1000 m shielded or 600 m unshielded |
| Potential separation and test | Groups of 8; isolated from the backplane; 500 V DC isolation test |
| Dimensions and approximate weight | 25 × 290 × 210 mm (W × H × D); 600 g |
Frequently Asked Questions
Should I treat every output on 6ES7422-1BH11-0AA0 as an individually isolated circuit?
Potential separation is provided in groups of eight and between the outputs and the backplane bus.
How frequently can 6ES7422-1BH11-0AA0 switch a two-ampere DC13 inductive load?
The maximum DC13 switching frequency at two amperes is one-tenth hertz.
Can I rely on 6ES7422-1BH11-0AA0 for a diagnostic function in the controller?
The module does not provide a diagnostics function.
Is a five-hundred-metre unshielded output cable within the limit for 6ES7422-1BH11-0AA0?
The stated maximum unshielded output-cable length is six hundred metres.
What unloaded current should I budget for 6ES7422-1BH11-0AA0 on the two supplies?
Allow up to thirty milliamperes from the load supply and one hundred sixty milliamperes from the five-volt backplane.
Can I connect a twenty-watt lamp directly to an output of 6ES7422-1BH11-0AA0?
The specified maximum lamp load is ten watts per output.
Can I parallel two outputs of 6ES7422-1BH11-0AA0 to increase the load-current rating?
Parallel switching for current uprating is not permitted.