Siemens 6ES7332-5HD01-0AB0 SIMATIC S7-300 SM 332 Four-Channel Analog Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Configure the intended voltage or current range for every channel.
- Select the matching 20-pin front connector and shielded signal cables.
- Check resistance, capacitance and inductance against the selected output mode.
- Use hot insertion only in the supported active-backplane station arrangement.
6ES7332-5HD01-0AB0 SIMATIC S7-300 SM 332 Four-Channel Analog Output Module
SM 332 with four isolated-to-backplane voltage/current output channels, configurable ranges and a 20-pin front connector.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7332-5HD01-0AB0 |
| Product Type | Analog output signal module |
| Core Function | Generation of voltage and current setpoints |
| Application | S7-300 and compatible active-backplane stations |
Selectable analog setpoints
Each output supports the specified voltage or current measuring ranges.
Voltage-line compensation
Four-wire voltage connections compensate for the voltage drop in the load conductors.
Configured fault response
Diagnostic functions and substitute values support a defined response to station or output faults.
Product Overview
6ES7332-5HD01-0AB0 generates four analog output signals for voltage or current-controlled field equipment.
The SM 332 supports selectable unipolar and bipolar ranges, configurable substitute values and diagnostics, with voltage compensation available through four-wire connections.
Key Functions
Selectable analog setpoints
Each output supports the specified voltage or current measuring ranges.
Voltage-line compensation
Four-wire voltage connections compensate for the voltage drop in the load conductors.
Configured fault response
Diagnostic functions and substitute values support a defined response to station or output faults.
Official Specifications
| Output channel count | 4 voltage/current channels |
|---|---|
| Voltage ranges | 0–10 V; 1–5 V; ±10 V |
| Current ranges | 0–20 mA; 4–20 mA; ±20 mA |
| Load supply | 24 V DC; reverse-polarity protection |
| Load-supply current | 240 mA maximum without load |
| 5 V backplane current | 60 mA maximum |
| Power loss | 3 W typical |
| Voltage-output wiring | 4-wire connection |
| Current-output wiring | 2-wire connection |
| Voltage-load limits | At least 1 kΩ; up to 1 µF capacitance |
| Current-load limits | Up to 500 Ω; up to 10 mH inductance |
| Voltage-output short-circuit current | 25 mA maximum |
| Current-output no-load voltage | 18 V maximum |
| Maximum shielded cable | 200 m |
| Resolution | 12 bits for 0–10 V and 0–20 mA; 11 bits plus sign for the other listed ranges |
| Conversion time | 0.8 ms per channel |
| Operational error limit | ±0.5% voltage; ±0.6% current |
| Isolation | From backplane bus and load supply; no channel-to-channel isolation |
| Front connector | 20-pin |
| Dimensions and mass | 40 × 125 × 117 mm (W × H × D); approximately 220 g |
Frequently Asked Questions
How can I compensate a voltage lead drop with 6ES7332-5HD01-0AB0?
Use the four-wire voltage-output connection to sense the voltage at the load.
What maximum load resistance may I use for a current output of 6ES7332-5HD01-0AB0?
The maximum permitted load resistance is 500 Ω.
Are the four channels of 6ES7332-5HD01-0AB0 isolated from one another?
The channels share their output reference and are isolated from the backplane bus and load supply rather than from each other.
Does every range on 6ES7332-5HD01-0AB0 use the same resolution?
The 0–10 V and 0–20 mA ranges use twelve bits while the other listed ranges use eleven bits plus sign.
What voltage can appear on an unloaded current output of 6ES7332-5HD01-0AB0?
The specified maximum no-load voltage is 18 V.
What connector is needed for field wiring to 6ES7332-5HD01-0AB0?
Use the matching 20-pin front connector.
Can 6ES7332-5HD01-0AB0 be inserted during operation in an active-backplane station?
The stated hot-insertion function applies when the module is used with a suitable active backplane.