Siemens 6ES7322-8BF00-0AB0 SIMATIC S7-300 SM 322 8DO 24VDC 0.5A Diagnostic Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use a 20-pin front connector and the specified 24 V DC load supply.
- Check minimum load current and both channel and group-current limits.
- Configure diagnostic reporting for the required wire-break, short-circuit and missing-voltage conditions.
- Do not parallel channels for current uprating, and use the specified series-diode arrangement for redundant load control.
6ES7322-8BF00-0AB0 SIMATIC S7-300 SM 322 8DO 24VDC 0.5A Diagnostic Output Module
Eight-channel 24 V DC SM 322 output module with 0.5 A rated outputs, electronic short-circuit protection and configurable diagnostic alarms.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7322-8BF00-0AB0 |
| Product Type | Digital output module |
| Core Function | Switching DC loads with channel diagnostics |
| Application | S7-300 actuator and indication circuits |
DC actuator switching
Eight electronic outputs provide a 0.5 A rated current per channel.
Electronic load protection
Short-circuit protection operates with a typical response threshold of 0.75–1.5 A.
Fault indication and reporting
Channel fault indicators, the SF group-error LED and configurable diagnostic alarms assist service work.
Product Overview
6ES7322-8BF00-0AB0 switches eight 24 V DC field loads in one output group, with electronic short-circuit protection and configurable diagnostic information.
The individual-channel rating must be considered together with the group-current limit, which decreases to 3 A for horizontal operation at 60 °C.
Key Functions
DC actuator switching
Eight electronic outputs provide a 0.5 A rated current per channel.
Electronic load protection
Short-circuit protection operates with a typical response threshold of 0.75–1.5 A.
Fault indication and reporting
Channel fault indicators, the SF group-error LED and configurable diagnostic alarms assist service work.
Official Specifications
| Load supply L+ | 24 V DC rated; 20.4–28.8 V DC permitted |
|---|---|
| No-load L+ consumption | 90 mA maximum |
| Backplane current | 70 mA maximum from 5 V DC |
| Typical power loss | 5 W |
| Output arrangement | 8 digital outputs in one potential group |
| Per-channel current | 0.5 A rated; permissible 10 mA–0.6 A over 0 to +60 °C |
| Group-current limit | 4 A up to 40 °C horizontal or vertical; 3 A up to 60 °C horizontal |
| Electronic short-circuit threshold | 0.75–1.5 A typical |
| Inductive shutdown-voltage limitation | L+ minus 45 V |
| Signal-0 residual current | 0.5 mA maximum |
| Maximum resistive-load delay | 180 µs on; 245 µs off |
| Load-resistance range | 48 Ω–3 kΩ |
| Maximum lamp load | 5 W |
| Maximum switching frequency | 100 Hz resistive; 2 Hz inductive; 10 Hz lamp load |
| Maximum output cable length | 1,000 m shielded; 600 m unshielded |
| Diagnostic functions | Wire break, short circuit and missing load voltage; configurable diagnostic alarm |
| Indicators | Green output-status LED per channel; red channel-fault F and group-error SF LEDs |
| Backplane isolation | Optocoupler isolation; tested at 500 V DC |
| Required front connector | 20-pin |
| Dimensions and approximate weight | 40 × 125 × 120 mm (W × H × D); 210 g |
Frequently Asked Questions
Does 6ES7322-8BF00-0AB0 use relay contacts for its output channels?
The module provides electronic 24 V DC outputs.
Can all eight channels of 6ES7322-8BF00-0AB0 carry 0.5 A at 60 °C horizontally?
The group is limited to 3 A at 60 °C in horizontal installation.
What minimum load should be connected to an output of 6ES7322-8BF00-0AB0?
The specified minimum load current is 10 mA.
How do the red F and SF indicators on 6ES7322-8BF00-0AB0 differ?
F indicates a channel fault, while SF indicates a group error.
Can two outputs of 6ES7322-8BF00-0AB0 be paralleled to increase available current?
Parallel switching for current uprating is not permitted.
What output arrangement is allowed for redundant load control with 6ES7322-8BF00-0AB0?
Redundant control is permitted only with outputs having series diodes.
Which front-connector format is required for 6ES7322-8BF00-0AB0?
The module requires a 20-pin front connector.