Overview

Siemens · SIMATIC S7-300

6ES7322-1FL00-0AA0 SM 322 32DO 120/230V AC 1A Module

Siemens 6ES7322-1FL00-0AA0 is the SIMATIC S7-300 SM 322 digital output module with 32 isolated 120/230 V AC outputs rated at 1 A in a double-width housing.

At a Glance

Brand Siemens
Model 6ES7322-1FL00-0AA0
Product Type Thirty-two-channel isolated AC digital output module
Core Function Switches 120 or 230 V AC industrial loads in four isolated groups
Application or Compatible Series SIMATIC S7-300 and ET 200M control systems

AC Load Review

Check every solenoid, contactor, starter, motor or lamp against the one-ampere output rating.

Group Wiring

Preserve the four groups of eight outputs, line feeds, neutral conductors and fuse arrangement.

Connector Transfer

Record both twenty-pole front-connector assignments before removing the installed module.

Product Overview

Siemens 6ES7322-1FL00-0AA0 is the SIMATIC S7-300 SM 322 digital output module with 32 isolated 120/230 V AC outputs rated at 1 A in a double-width housing.

A double-width module provides dense control of 120 or 230 V AC field loads. Outputs are fused and electrically isolated in groups of eight. Electronic switching supports controlled operation of compatible AC loads.

Ordering focus: confirm the exact SM 322 article, 120 or 230 V AC line supply, four output groups, load currents, fuses, switching frequency and both twenty-pole connector mappings.
Key Functions

Thirty-Two AC Outputs

A double-width module provides dense control of 120 or 230 V AC field loads.

Grouped Isolation

Outputs are fused and electrically isolated in groups of eight.

Zero-Cross Switching

Electronic switching supports controlled operation of compatible AC loads.

Official Specifications
Number of Digital Outputs 32
Rated Load Voltage 120 or 230 V AC
Permitted AC Voltage Range 79 to 264 V
Permitted Frequency Range 47 to 63 Hz
Rated Output Current 1 A
Minimum Load Current 10 mA
Maximum Residual Current at Signal 0 2 mA
Output Grouping 4 groups of 8
Maximum Lamp Load 50 W
Maximum Backplane Current at 5 V DC 190 mA
Typical Power Loss 25 W
Zero-Cross Switching Supported
Maximum Resistive Switching Frequency 100 Hz
Maximum Inductive Switching Frequency 0.5 Hz
Maximum Lamp Switching Frequency 10 Hz
Load Resistance Range 48 Ω to 4 kΩ
Output Delay with Resistive Load Maximum 1 AC cycle
Redundant Load Control Outputs from the same group
Front Connectors 2 x 20-pole
Module Width Double width
Frequently Asked Questions

Which loads can I switch with 6ES7322-1FL00-0AA0?

Use compatible AC solenoids, contactors, starters, fractional-horsepower motors and signal lamps within the ratings.

How are the channels grouped on 6ES7322-1FL00-0AA0?

The thirty-two outputs are arranged in four fused and electrically isolated groups of eight.

What voltage range is permitted for 6ES7322-1FL00-0AA0?

The load supply may range from 79 to 264 volts AC at 47 to 63 hertz.

Which connectors are required by 6ES7322-1FL00-0AA0?

The double-width module uses two twenty-pole front connectors.

Can two outputs on 6ES7322-1FL00-0AA0 control one load redundantly?

Yes, redundant control is permitted when both outputs belong to the same group.

What should I check before replacing 6ES7322-1FL00-0AA0?

Check the line feeds, neutral conductors, fuses, group allocation, load current and both connector mappings.

Why should switching frequency be reviewed for 6ES7322-1FL00-0AA0?

The permitted rate differs for resistive, inductive and lamp loads.

Compatibility & Ordering Notes
Before ordering 6ES7322-1FL00-0AA0: confirm the exact SM 322 article, 120 or 230 V AC line supply, four output groups, load currents, fuses, switching frequency and both twenty-pole connector mappings.

Compatibility Checklist

  • Use the exact double-width S7-300 SM 322 AC-output module entry in the hardware configuration.
  • Check all loads against voltage, current, inrush, switching frequency and group requirements.
  • Preserve both front-connector mappings, line feeds, neutral wiring and fuse arrangement.
Hot Selling Models
6EP1332-1SH43
PZE5V 474965
MBS ASK 31.3 ASK31.3 400/1A
1052560000
3RT1016-2HB42
3000-36001-2000040
GV2ME05 034303
FSM5-2FKM5.4/S55
MC17-10
40A7 DK1522
BIDEN96
159624
DILM15-10
Allen-Bradley 1771-IBD/B
3RV1011-0EA20

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.