Overview
Siemens · SIMATIC S7-300
6ES7322-1FL00-0AA0 SM 322 32DO 120/230V AC 1A Module
Siemens 6ES7322-1FL00-0AA0 is the SIMATIC S7-300 SM 322 digital output module with 32 isolated 120/230 V AC outputs rated at 1 A in a double-width housing.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7322-1FL00-0AA0 |
| Product Type | Thirty-two-channel isolated AC digital output module |
| Core Function | Switches 120 or 230 V AC industrial loads in four isolated groups |
| Application or Compatible Series | SIMATIC S7-300 and ET 200M control systems |
AC Load Review
Check every solenoid, contactor, starter, motor or lamp against the one-ampere output rating.
Group Wiring
Preserve the four groups of eight outputs, line feeds, neutral conductors and fuse arrangement.
Connector Transfer
Record both twenty-pole front-connector assignments before removing the installed module.
Product Overview
Siemens 6ES7322-1FL00-0AA0 is the SIMATIC S7-300 SM 322 digital output module with 32 isolated 120/230 V AC outputs rated at 1 A in a double-width housing.
A double-width module provides dense control of 120 or 230 V AC field loads. Outputs are fused and electrically isolated in groups of eight. Electronic switching supports controlled operation of compatible AC loads.
Key Functions
Thirty-Two AC Outputs
A double-width module provides dense control of 120 or 230 V AC field loads.
Grouped Isolation
Outputs are fused and electrically isolated in groups of eight.
Zero-Cross Switching
Electronic switching supports controlled operation of compatible AC loads.
Official Specifications
| Number of Digital Outputs | 32 |
|---|---|
| Rated Load Voltage | 120 or 230 V AC |
| Permitted AC Voltage Range | 79 to 264 V |
| Permitted Frequency Range | 47 to 63 Hz |
| Rated Output Current | 1 A |
| Minimum Load Current | 10 mA |
| Maximum Residual Current at Signal 0 | 2 mA |
| Output Grouping | 4 groups of 8 |
| Maximum Lamp Load | 50 W |
| Maximum Backplane Current at 5 V DC | 190 mA |
| Typical Power Loss | 25 W |
| Zero-Cross Switching | Supported |
| Maximum Resistive Switching Frequency | 100 Hz |
| Maximum Inductive Switching Frequency | 0.5 Hz |
| Maximum Lamp Switching Frequency | 10 Hz |
| Load Resistance Range | 48 Ω to 4 kΩ |
| Output Delay with Resistive Load | Maximum 1 AC cycle |
| Redundant Load Control | Outputs from the same group |
| Front Connectors | 2 x 20-pole |
| Module Width | Double width |
Frequently Asked Questions
Which loads can I switch with 6ES7322-1FL00-0AA0?
Use compatible AC solenoids, contactors, starters, fractional-horsepower motors and signal lamps within the ratings.
How are the channels grouped on 6ES7322-1FL00-0AA0?
The thirty-two outputs are arranged in four fused and electrically isolated groups of eight.
What voltage range is permitted for 6ES7322-1FL00-0AA0?
The load supply may range from 79 to 264 volts AC at 47 to 63 hertz.
Which connectors are required by 6ES7322-1FL00-0AA0?
The double-width module uses two twenty-pole front connectors.
Can two outputs on 6ES7322-1FL00-0AA0 control one load redundantly?
Yes, redundant control is permitted when both outputs belong to the same group.
What should I check before replacing 6ES7322-1FL00-0AA0?
Check the line feeds, neutral conductors, fuses, group allocation, load current and both connector mappings.
Why should switching frequency be reviewed for 6ES7322-1FL00-0AA0?
The permitted rate differs for resistive, inductive and lamp loads.
Compatibility & Ordering Notes
Compatibility Checklist
- Use the exact double-width S7-300 SM 322 AC-output module entry in the hardware configuration.
- Check all loads against voltage, current, inrush, switching frequency and group requirements.
- Preserve both front-connector mappings, line feeds, neutral wiring and fuse arrangement.