Siemens 6ES7322-1FF01-0AA0 SIMATIC S7-300 SM 322 AC Digital Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use a 93 to 264 V AC load supply at 47 to 63 Hz.
- Respect the 10 mA minimum channel load and temperature-dependent current limits.
- Retain the specified group fuse arrangement.
- Allow up to one AC cycle for output switching.
6ES7322-1FF01-0AA0 SIMATIC S7-300 SM 322 AC Digital Output Module
SM 322 provides eight isolated AC output channels for 120/230 V loads, a 20-pin front connector and group diagnostics for the fuse and load voltage.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7322-1FF01-0AA0 |
| Product Type | AC digital output module |
| Core Function | Switching of AC process loads |
| Application | S7-300 automation I/O systems |
Eight AC outputs
The load supply covers 93 to 264 V AC at 47 to 63 Hz.
Temperature-dependent current
Channel and output-group limits depend on ambient temperature and mounting.
Fuse monitoring
The module monitors a blown fuse and missing load voltage.
Product Overview
6ES7322-1FF01-0AA0 is an isolated SM 322 output module for 120/230 V AC loads in SIMATIC S7-300 systems. Its eight outputs use a 20-pin front connector and are isolated in groups of four.
Zero-crossing switching, group fusing and fuse/load-voltage diagnostics distinguish this AC output module from DC transistor and relay output variants.
Key Functions
AC process output control
Eight outputs switch AC loads over a permissible 93 to 264 V supply range, with switching delays up to one AC cycle.
Grouped load management
Four-output potential groups and temperature-dependent aggregate-current limits govern the permitted loading.
Fuse and voltage supervision
PWR, FSG, SF and channel-status LEDs support checks for load voltage, fuse condition and output state.
Official Specifications
| AC output channels | 8; isolated in groups of 4 |
|---|---|
| Load voltage | 120/230 V AC nominal; permissible 93 to 264 V AC |
| Load frequency | 47 to 63 Hz |
| Maximum backplane current | 100 mA at 5 V DC |
| Maximum no-load L1 current | 2 mA |
| Typical power loss | 8.6 W |
| Channel current at 0 to 40 °C | 10 mA to 2 A |
| Channel current at 40 to 60 °C | 10 mA to 1 A |
| Output-group total current | Horizontal: 4 A up to 40 °C, 2 A up to 60 °C; vertical: 2 A up to 40 °C |
| Maximum surge current | 20 A for at most 1 AC cycle |
| Maximum lamp load | 50 W |
| Maximum OFF residual current | 2 mA |
| Maximum switching delay | 1 AC cycle in either direction |
| Maximum switching frequency | 10 Hz resistive; 0.5 Hz inductive; 1 Hz lamp loads |
| Group fuse | 8 A, 250 V; quick-response replacement fuse |
| Maximum output cable length | 1000 m shielded; 600 m unshielded |
| Isolation test voltage | 1500 V AC |
| Front connector | 20-pin |
| Dimensions (W × H × D) | 40 × 125 × 120 mm |
| Approximate weight | 275 g |
Frequently Asked Questions
Can I use 6ES7322-1FF01-0AA0 to switch 24 V DC solenoids?
The output stage is intended for 120/230 V AC loads within a 93 to 264 V AC supply range.
How should I load 6ES7322-1FF01-0AA0 in a horizontal rack at 60 °C?
At that temperature the limit is 1 A per channel and 2 A total per four-output group.
Can I parallel outputs on 6ES7322-1FF01-0AA0 to increase the current rating?
Parallel outputs may provide redundant control of a load but cannot be used for uprating.
Why might an OFF channel on 6ES7322-1FF01-0AA0 still pass a small current?
The AC output stage permits a maximum OFF-state residual current of 2 mA.
Which faults can I diagnose locally on 6ES7322-1FF01-0AA0?
The module detects a blown fuse and missing load voltage and provides FSG, PWR and SF indicators.
Can 6ES7322-1FF01-0AA0 switch an inductive actuator at 2 Hz?
The maximum inductive-load switching frequency is 0.5 Hz.
What front connector is required for 6ES7322-1FF01-0AA0?
The module requires a 20-pin front connector.