Siemens 6ES7288-1SR20-0AA0 S7-200 SMART CPU SR20 AC/DC/Relay
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the AC-powered relay-output CPU variant specified by the machine design.
- Program with STEP 7 Micro/WIN SMART and match the firmware for the required PROFINET role.
- Keep sensor-supply demand at or below 300 mA.
- Use relay outputs for the permitted switching duty and observe the lower temperature ceiling for vertical mounting.
6ES7288-1SR20-0AA0 S7-200 SMART CPU SR20 AC/DC/Relay
An AC-powered CPU SR20 with twelve 24 V DC inputs, eight relay outputs, Ethernet and an RS485 interface.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7288-1SR20-0AA0 |
| Product Type | Compact controller |
| Core Function | Machine sequence and process control |
| Application | STEP 7 Micro/WIN SMART projects |
Integrated machine I/O
Twelve DC inputs and eight relay outputs provide onboard connections for sensors and switched loads.
Counting and process functions
Six high-speed counter resources and up to eight PID loops support measurement and control tasks.
Ethernet and serial communication
One 10/100 Mbit/s Ethernet interface and one RS485 interface connect the CPU to the configured machine network.
Product Overview
6ES7288-1SR20-0AA0 combines an AC power input with DC sensor inputs and relay load switching in a compact S7-200 SMART CPU.
The controller supports high-speed counting, PID processing and Ethernet communication, while its onboard outputs provide relay switching rather than high-speed transistor pulse operation.
Key Functions
Integrated machine I/O
Twelve DC inputs and eight relay outputs provide onboard connections for sensors and switched loads.
Counting and process functions
Six high-speed counter resources and up to eight PID loops support measurement and control tasks.
Ethernet and serial communication
One 10/100 Mbit/s Ethernet interface and one RS485 interface connect the CPU to the configured machine network.
Official Specifications
| Supply voltage | 85–264 V AC, 47–63 Hz |
|---|---|
| Maximum inrush current | 9.3 A at 264 V |
| Onboard inputs | 12 inputs, 24 V DC, sinking/sourcing |
| Input filter | 0.2–12.8 ms, selectable in groups of four |
| Onboard outputs | 8 relay outputs, maximum 2 A resistive load |
| Relay switching delays | Maximum 10 ms for either transition |
| Maximum relay switching frequency | 1 Hz with resistive load |
| Sensor supply | 24 V DC, maximum 300 mA |
| User program memory | 12 KB |
| User data memory | 8 KB |
| Instruction times | Bit: 150 ns; word: 1.2 µs; floating-point: 3.6 µs, typical |
| Ethernet interface | 1 × RJ45, 10/100 Mbit/s |
| Serial interface | 1 × RS485, up to 187.5 kbit/s |
| High-speed counting | 6 counters; single-phase channels up to 200 kHz subject to channel allocation |
| PID capacity | Up to 8 control loops |
| Real-time clock backup | 7 days; no battery backup |
| Operating temperature | 0–55 °C horizontal; 0–45 °C vertical |
| Dimensions | 90 × 100 × 81 mm |
| Protection rating | IP20 |
| Approximate weight | 367.3 g |
Frequently Asked Questions
Can 6ES7288-1SR20-0AA0 be powered directly from a 230 V AC control circuit?
The CPU supply accepts 85–264 V AC at 47–63 Hz.
Can I use the relay outputs of 6ES7288-1SR20-0AA0 for high-speed pulse positioning?
The onboard relay outputs have a maximum resistive-load switching frequency of 1 Hz and are not high-speed transistor outputs.
Which engineering package should I use for 6ES7288-1SR20-0AA0?
Program the controller with STEP 7 Micro/WIN SMART.
Does 6ES7288-1SR20-0AA0 provide power for nearby 24 V sensors?
The CPU provides a 24 V DC sensor supply with a maximum current of 300 mA.
Which firmware is required for PROFINET on 6ES7288-1SR20-0AA0?
PROFINET IO Controller operation starts with firmware V2.4 and I-Device operation starts with V2.5.
How long does the real-time clock of 6ES7288-1SR20-0AA0 retain its time without power?
The real-time clock has a specified backup time of seven days.
What temperature limit applies when 6ES7288-1SR20-0AA0 is mounted vertically?
The operating range for vertical mounting is 0–45 °C.