Siemens 6ES7231-7PB22-0XA8 SIMATIC S7-200 CN EM 231 Two-Channel RTD Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Choose one RTD type for both channels.
- Match the wiring switch to the actual two-, three- or four-wire connection.
- Power-cycle after DIP-switch changes.
- Disable CPU analog filtering for these RTD values.
- Read the module regularly and process its range and supply-error indications.
6ES7231-7PB22-0XA8 SIMATIC S7-200 CN EM 231 Two-Channel RTD Module
A two-input RTD module with selectable sensor characteristics, two-/three-/four-wire connections and temperature values in 0.1-degree units.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7231-7PB22-0XA8 |
| Product Type | RTD input expansion module |
| Core Function | Acquiring resistance-temperature signals |
| Application | S7-200 CN CPU expansion |
Two RTD channels
The selected sensor type applies to both measurement channels.
DIP-switch setup
Sensor type, wiring, temperature scale and error direction are selected on the module.
Direct engineering values
Temperature is represented in 0.1-degree units and resistance is scaled to 27648.
Product Overview
6ES7231-7PB22-0XA8 connects two resistance-temperature sensors to an S7-200 CN controller. Platinum, nickel and copper RTD characteristics are selectable, together with three resistance ranges.
The module uses DIP switches for sensor and wiring selection and supplies temperature or error information as signed data words. Its status indications distinguish missing user power from open-wire, out-of-range and diagnostic conditions.
Key Functions
Measure RTDs directly
The inputs support platinum, nickel and Cu10 sensor characteristics and resistance measurement.
Apply the selected connection scheme
Two-wire, three-wire and four-wire arrangements are selected with the module DIP switches.
Expose sensor faults
Range status, data-word error values and local LEDs support detection of wiring and supply faults.
Official Specifications
| RTD input channels | 2 |
|---|---|
| Selectable RTD families | Pt100/200/500/1000/10000; Ni100/120/1000; Cu10, with selectable characteristics |
| Resistance ranges | 150 Ω, 300 Ω or 600 Ω full scale |
| User supply range | 20.4–28.8 V DC |
| 5 V bus requirement | 87 mA |
| 24 V supply requirement | 60 mA |
| Power dissipation | 1.8 W |
| Conversion principle | Sigma-delta |
| Temperature representation | 0.1 °C or 0.1 °F per count |
| Resistance representation | 15 bit plus sign; nominal range 0–27648 |
| Module update time | 405 ms; 700 ms for Pt10000 |
| Maximum sensor cable length | 100 m |
| Maximum wire-loop resistance | 20 Ω; 2.7 Ω for Cu10 |
| Maximum sensor dissipation | 1 mW |
| Minimum input impedance | 10 MΩ |
| Maximum input voltage | 30 V DC at sense terminals; 5 V DC at source terminals |
| Resistance accuracy and repeatability | Basic error 0.1% full scale; repeatability 0.05% full scale |
| Interference suppression | 85 dB at 50, 60 and 400 Hz |
| Dimensions | 71.2 × 80 × 62 mm (W × H × D) |
| Weight | 210 g |
Frequently Asked Questions
Can I mix different RTD types on the two inputs of 6ES7231-7PB22-0XA8?
Both RTDs must use the same selected sensor type.
When do changed DIP-switch settings take effect on 6ES7231-7PB22-0XA8?
Power-cycle the PLC or the user 24 V supply after changing the switches.
How do I interpret a temperature value of 1002 from 6ES7231-7PB22-0XA8?
The value represents 100.2 degrees in the selected Celsius or Fahrenheit scale.
Should the PLC analog filter remain enabled for 6ES7231-7PB22-0XA8?
Disable the PLC analog filter so that it does not delay detection of module error conditions.
How can I prevent an unused input of 6ES7231-7PB22-0XA8 from reporting an open wire?
Connect a resistor matching the selected RTD nominal resistance in place of the unused sensor.
Which wiring arrangement gives the best accuracy with 6ES7231-7PB22-0XA8?
Four-wire measurement gives the highest accuracy by separating the source and sense leads.
How frequently should my program read 6ES7231-7PB22-0XA8?
Read at least once per module update period of 405 ms, or 700 ms when measuring Pt10000.