Siemens 6ES7231-4PA30-0XB0 SIMATIC S7-1200 SB 1231 RTD Signal Board
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Select Pt100, Pt200, Pt500 or Pt1000 within the supported input configuration.
- Do not use the RTD channel as a current or thermocouple input.
- Keep the shielded twisted-pair sensor cable within 100 m.
- Use the vertical-mounting limit of 50 °C where applicable.
- Process wire-break diagnostics in the application.
6ES7231-4PA30-0XB0 SIMATIC S7-1200 SB 1231 RTD Signal Board
A one-channel RTD signal-board arrangement with signed 16-bit conversion, platinum-sensor support and readable wire-break diagnostics.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7231-4PA30-0XB0 |
| Product Type | SB 1231 RTD signal board |
| Core Function | Converting resistance-thermometer signals to temperature values |
| Application | Compatible S7-1200 CPU signal-board positions |
One RTD channel
The input supports platinum resistance thermometers.
Flexible engineering units
Temperature values can be configured in degrees Celsius or Fahrenheit.
Wiring diagnostics
Wire-break diagnostics and diagnostic alarms are supported.
Product Overview
6ES7231-4PA30-0XB0 provides a one-channel resistance-thermometer input in the SB 1231 signal-board format for a compatible S7-1200 CPU.
The integrating converter supports platinum RTDs, resistance and the specified low-level voltage range, while readable diagnostics help the application respond to wiring faults.
Key Functions
Acquire a platinum sensor
The input supports Pt100, Pt200, Pt500 and Pt1000 resistance-thermometer types.
Convert the selected signal range
The integrating measurement arrangement provides 15 bits plus sign and configurable temperature engineering units.
Detect wiring faults
Readable diagnostics include wire-break detection and diagnostic alarms.
Official Specifications
| Input Channels | 1 resistance-thermometer input |
|---|---|
| Rated Supply | 24 V DC |
| Typical Supply Current | 5 mA; 20 mA from the 5 V backplane |
| Typical Power Dissipation | 0.5 W |
| Supported Platinum RTDs | Pt100, Pt200, Pt500 and Pt1000 |
| Resistance Measurement Ranges | 0–150 Ω, 0–300 Ω and 0–600 Ω |
| Voltage Measurement Range | −80 to +80 mV |
| Input Resistance in Millivolt Range | At least 10 MΩ |
| Conversion Principle | Integrating |
| Maximum Resolution | 15 bits plus sign |
| Temperature Engineering Units | Degrees Celsius or Fahrenheit |
| Maximum Shielded Cable Length | 100 m, shielded twisted pair |
| Temperature Error Relative to Input Range | ±0.1% at 25 °C; ±0.2% up to 55 °C |
| Steady-State Repeat Accuracy at 25 °C | ±0.05% of range |
| Common-Mode Interference Rejection | At least 120 dB |
| Wiring Diagnostics | Readable wire-break diagnostics and diagnostic alarm |
| Operating Temperature by Mounting Direction | Horizontal: −20 to +60 °C; vertical: −20 to +50 °C |
| Dimensions (W × H × D) | 38 × 62 × 21 mm |
| Approximate Weight | 35 g |
Frequently Asked Questions
Can 6ES7231-4PA30-0XB0 read a Pt1000 resistance thermometer?
The RTD input supports Pt1000 as well as Pt100, Pt200 and Pt500 sensors.
Can I connect a 4–20 mA transmitter to 6ES7231-4PA30-0XB0?
The input does not support current measurement.
Can 6ES7231-4PA30-0XB0 acquire a thermocouple signal as a thermocouple channel?
The board does not support thermocouple measurement.
Can I display temperatures from 6ES7231-4PA30-0XB0 in Fahrenheit?
Temperature engineering units can be selected as degrees Celsius or Fahrenheit.
Will 6ES7231-4PA30-0XB0 detect a broken sensor wire?
The board supports readable wire-break diagnostics and a diagnostic alarm.
Which cable should I select for a long connection to 6ES7231-4PA30-0XB0?
Use shielded twisted-pair cable with a maximum length of 100 m.
Does vertical mounting change the temperature limit of 6ES7231-4PA30-0XB0?
The maximum ambient temperature is 50 °C vertically and 60 °C horizontally.