Siemens 6ES7194-4DD00-0AA0 ET 200pro CM IO 16 x M12 Connection Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the connection assignment for EM 8/16 F-DI DC24V PROFIsafe and the selected 1oo1 or 1oo2 evaluation.
- Check secondary pin assignments before using a double-assigned socket; pin 2 and pin 5 assignments depend on the socket group.
- Keep sensor supplies and 1M returns associated with the correct group, and terminate the shield for functional grounding.
- Apply all port and module labels, then check the mechanical connection and screws before commissioning.
6ES7194-4DD00-0AA0 ET 200pro CM IO 16 x M12 Connection Module
Sixteen M12 field sockets with grouped sensor supplies, channel wiring and shield-based functional grounding for the ET 200pro fail-safe input assembly.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7194-4DD00-0AA0 |
| Product Type | CM IO connection module |
| Core Function | Connects field sensors through 16 M12 sockets |
| Application | Distributed fail-safe digital input stations |
Sixteen field connections
M12 sockets X1 through X16 provide the field connection points for the input assembly.
Paired-signal wiring
Double-assigned sockets X1–X4 and X9–X12 can carry paired signals for 1oo2 evaluation through one sensor cable.
Grouped sensor supplies
The connection assignment separates sensor-supply groups and provides functional grounding through the cable shield.
Product Overview
6ES7194-4DD00-0AA0 is the CM IO connection module used with the EM 8/16 F-DI DC24V PROFIsafe electronics module in a SIMATIC ET 200pro station. It provides the field-side sockets and plugs into the electronic module before being secured with screws.
The connector layout supports individual input channels and double-assigned sockets for paired sensor signals. Port labels and the separate module label help maintain a clear relationship between cabinet documentation, channel numbers and field wiring.
Key Functions
Sixteen field connections
M12 sockets X1 through X16 provide the field connection points for the input assembly.
Paired-signal wiring
Double-assigned sockets X1–X4 and X9–X12 can carry paired signals for 1oo2 evaluation through one sensor cable.
Grouped sensor supplies
The connection assignment separates sensor-supply groups and provides functional grounding through the cable shield.
Official Specifications
| Field connectors | 16 M12 circular sockets, X1–X16 |
|---|---|
| Primary sensor-supply pin | Pin 1: Vs1 at X1–X4; Vs2 at X5–X8; Vs3 at X9–X12; Vs4 at X13–X16 |
| Sensor-supply ground | Pin 3: 1M |
| Primary signal assignment | Pin 4: input channels 0–15 at X1–X16 respectively |
| Secondary signal assignment | Pin 2 at X1–X4: channels 4–7; pin 2 at X9–X12: channels 12–15 |
| Functional grounding | Through the cable shield |
| Connection cable | 3-, 4- or 5-core copper cable, according to the required assignment |
| Identification labels | 16 port labels and one module label |
| Dimensions (W × H × D) | 90 × 130 × 39 mm |
| Weight | 505 g |
Frequently Asked Questions
Which electronics module accepts 6ES7194-4DD00-0AA0?
The connection module mates with the EM 8/16 F-DI DC24V PROFIsafe electronic module.
How many M12 field sockets are available on 6ES7194-4DD00-0AA0?
There are sixteen sockets, identified as X1 through X16.
Which sockets on 6ES7194-4DD00-0AA0 support paired input signals?
Sockets X1–X4 and X9–X12 are double assigned, allowing paired signals to be wired through one cable for 1oo2 evaluation.
Where does input channel 0 connect on 6ES7194-4DD00-0AA0?
Channel 0 is assigned to pin 4 of socket X1.
Which pin provides the sensor-supply return on 6ES7194-4DD00-0AA0?
Pin 3 is the 1M sensor-supply ground connection.
How is functional ground carried through 6ES7194-4DD00-0AA0?
Functional grounding is provided through the shield, so the shield connection must be included in the installation plan.
How is 6ES7194-4DD00-0AA0 attached to the station?
Plug the connection module onto its matching electronics module and secure the assembly with the specified screws.