Siemens 6ES7193-0CA20-0XA0 ET 200B TB1-4/DC Four-Tier Terminal Block
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Preserve all fourth-tier protective-earth wiring.
- Match the 16-channel terminal layout to the removable electronics.
- Use the assigned TR5-T 1.6 A fuse.
- Apply the installation-position temperature limit and keep the station free of condensation.
6ES7193-0CA20-0XA0 ET 200B TB1-4/DC Four-Tier Terminal Block
The TB1-4/DC screw-terminal base with a four-tier arrangement, numbered signal connections and a dedicated protective-earth terminal tier.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7193-0CA20-0XA0 |
| Product Type | Digital station terminal base |
| Core Function | Connecting removable station electronics to field wiring |
| Application | ET 200B digital I/O installations |
Four-tier wiring
The lower terminal tier provides the protective-earth connections.
16-channel layout
The base is the 16-channel four-tier member of the digital terminal-block family.
Serviceable fuse
Sensor-supply protection uses the specified 1.6 A miniature fuse.
Product Overview
6ES7193-0CA20-0XA0 provides the four-tier screw-terminal wiring arrangement of the TB1-4/DC terminal base. Its numbered terminals are organized for the 16-channel digital station layout, with an additional protective-earth tier for the field wiring.
The removable electronics block contains the signal-processing functions, while the terminal base retains the wiring and station controls. The 1.6 A fuse and protective-earth arrangement must be preserved when servicing the station.
Key Functions
Provide an extra protective-earth tier
The four-tier base includes an earth-terminal row alongside the numbered field connections.
Hold the fixed station wiring
The digital electronics block can be removed from the base without reterminating every field conductor.
Protect the sensor circuit
The replaceable fuse protects the sensor supply and the internal logic supply against the specified faults.
Official Specifications
| Terminal structure | 16-channel arrangement; 4 screw-terminal tiers |
|---|---|
| Numbered terminal ranges | 1–16, 17–32 and 33–48 |
| Protective-earth tier | Additional fourth terminal tier |
| Sensor-supply fuse | TR5-T 1.6 A, 250 V miniature fuse |
| Station-number selector | 00–99 two-digit setting range |
| Module-class coding | 6-position coding slide |
| Bare terminal-block height and depth | 126.9 mm high; 56.9 mm maximum depth |
| Installed protection | IP20; protection class I |
| Operating temperature | 0–60 °C in preferred horizontal installation; 0–40 °C in other positions |
| Storage and transport temperature | −40 to +70 °C |
| Relative humidity | 15–95 %, indoor, without condensation |
| Atmospheric pressure | Operation: 795–1,080 hPa; storage/transport: 660–1,080 hPa |
| Vibration test | 0.075 mm at 10 to <57 Hz; 1 g at 57 to <150 Hz |
| Shock test | 15 g peak, 11 ms half-sine |
| Electrostatic discharge immunity | 8 kV air discharge; 4 kV contact discharge |
Frequently Asked Questions
What is the fourth terminal tier on 6ES7193-0CA20-0XA0 used for?
The additional lower tier provides protective-earth connections.
Can I use 6ES7193-0CA20-0XA0 for the 32-channel terminal arrangement?
The TB1-4/DC is the 16-channel base and the 32-channel four-tier arrangement uses TB2-4/DC.
Which numbered connections should I expect on 6ES7193-0CA20-0XA0?
The three numbered tiers run from 1 to 48 in groups of sixteen.
What sensor-supply fuse belongs in 6ES7193-0CA20-0XA0?
The assigned fuse is a TR5-T 1.6 A miniature fuse rated at 250 V.
What conductor size is required for the station ground connection at 6ES7193-0CA20-0XA0?
Use a 4–10 mm² conductor for the equipotential-bonding and ground connections.
Will replacing the electronics block on 6ES7193-0CA20-0XA0 also replace the station-number setting?
The station-number controls remain in the terminal block.
What temperature limit applies to 6ES7193-0CA20-0XA0 in a nonpreferred mounting position?
The permitted operating range is 0–40 °C outside the preferred horizontal installation.