- Connect the input sensors with three-pole M8 connectors and keep unshielded sensor runs within 30 m.
- Limit the total current of the eight sensor supply outputs to 0.7 A.
- Use the correct STEP 7 release or the matching GSD revision 5 / GSDML V2.3.1 device description.
- Configure the diagnostic alarm and assemble the M8 power and ET-Connection cables for the station layout.
6ES7141-5BF00-0BA0 SIMATIC ET 200AL DI 8x24VDC M8 Input Module
Compact IP65/67 input block with eight 24 V DC inputs, eight M8 sensor sockets and shielded ET-Connection interfaces.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7141-5BF00-0BA0 |
| Product Type | Digital input field module |
| Core Function | Acquisition of DC sensor signals |
| Application | ET 200AL distributed I/O stations |
Individual M8 sensor connections
Eight three-pole M8 sockets provide access to the 24 V DC input channels.
Sensor supply monitoring
Electronic short-circuit protection monitors the sensor supply to M at module level and supports configurable diagnostic alarms.
Compact field integration
The 30 mm wide housing uses M8 power and shielded ET-Connection sockets for distributed machine installation.
Product Overview
6ES7141-5BF00-0BA0 collects eight digital sensor signals close to the machine through individual three-pole M8 connections, reducing the need for sensor wiring to a central cabinet.
The 30 mm wide ET 200AL module combines Type 3 input characteristics, sensor-supply short-circuit diagnostics and channel indication in a field-installable IP65/67 housing.
Key Functions
Individual M8 sensor connections
Eight three-pole M8 sockets provide access to the 24 V DC input channels.
Sensor supply monitoring
Electronic short-circuit protection monitors the sensor supply to M at module level and supports configurable diagnostic alarms.
Compact field integration
The 30 mm wide housing uses M8 power and shielded ET-Connection sockets for distributed machine installation.
Official Specifications
| Input channels and characteristic | 8 P-reading digital inputs; IEC 61131 Type 3 |
|---|---|
| Load supply range | 24 V DC nominal; 20.4–28.8 V DC |
| No-load current consumption | 25 mA rated |
| Supply through-current limits | 4 A maximum for 1L+ and 4 A maximum for 2L+ |
| Sensor power outputs | 8 outputs with 0.7 A maximum combined current |
| Typical power loss | 1.9 W |
| Input voltage thresholds | Signal 0: −30 to +5 V; signal 1: +11 to +30 V |
| Typical signal-high current | 3.2 mA |
| Input transition delay | 1.2–4.8 ms for rising and falling transitions |
| Unshielded sensor cable length | 30 m maximum |
| Two-wire sensor quiescent current | 1.5 mA maximum |
| Channel and module indicators | Green channel LEDs; green/red module diagnostic LED |
| Electrical separation | Channels isolated from the backplane bus; no channel-to-channel isolation |
| Insulation test voltage | 707 V DC type test |
| Protection class | IP65/67 |
| Operating temperature | −30 to +55°C |
| Maximum operating altitude | 5000 m, with additional restrictions above 2000 m |
| Connection types | 3-pole M8 inputs; 4-pole M8 supply; shielded 4-pin M8 ET-Connection |
| Identification records | I&M0–I&M3 |
| Dimensions and mass | 30 × 159 × 40 mm (W × H × D); approximately 145 g |
Frequently Asked Questions
Which sensor connector should I select for 6ES7141-5BF00-0BA0?
Use a three-pole M8 connection for each digital input.
How much combined sensor current can 6ES7141-5BF00-0BA0 provide?
The eight sensor power outputs share a maximum total current of 0.7 A.
Can 6ES7141-5BF00-0BA0 use a two-wire sensor with a small off-state current?
Two-wire sensors are supported when their quiescent current does not exceed 1.5 mA.
Which engineering versions support 6ES7141-5BF00-0BA0?
The module can be configured with STEP 7 TIA Portal V13 SP1 or later, or STEP 7 V5.5 SP4 Hotfix 3 or later.
Will 6ES7141-5BF00-0BA0 identify a sensor-supply short circuit by individual channel?
Sensor-supply short-circuit detection operates at module level rather than identifying a separate fault for each channel.
Can 6ES7141-5BF00-0BA0 acquire all eight inputs at 55°C?
All eight inputs may be active at the maximum specified ambient temperature of +55°C.
What response delay should I allow for inputs on 6ES7141-5BF00-0BA0?
Allow 1.2–4.8 ms for either input transition at rated voltage.