Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
siemens 6es7141 5bf00 0ba0 simatic et 200al di 8x24vdc m8 input module-0

For SIEMENS

Home >  Products >  For SIEMENS

Siemens 6ES7141-5BF00-0BA0 SIMATIC ET 200AL DI 8x24VDC M8 Input Module

Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months

  • Overview
  • Hot Selling Models
  • Recommended Products
Overview
SIMATIC ET 200AL

6ES7141-5BF00-0BA0 SIMATIC ET 200AL DI 8x24VDC M8 Input Module

Compact IP65/67 input block with eight 24 V DC inputs, eight M8 sensor sockets and shielded ET-Connection interfaces.

At a Glance

Brand Siemens
Model 6ES7141-5BF00-0BA0
Product Type Digital input field module
Core Function Acquisition of DC sensor signals
Application ET 200AL distributed I/O stations

Individual M8 sensor connections

Eight three-pole M8 sockets provide access to the 24 V DC input channels.

Sensor supply monitoring

Electronic short-circuit protection monitors the sensor supply to M at module level and supports configurable diagnostic alarms.

Compact field integration

The 30 mm wide housing uses M8 power and shielded ET-Connection sockets for distributed machine installation.

Product Overview

6ES7141-5BF00-0BA0 collects eight digital sensor signals close to the machine through individual three-pole M8 connections, reducing the need for sensor wiring to a central cabinet.

The 30 mm wide ET 200AL module combines Type 3 input characteristics, sensor-supply short-circuit diagnostics and channel indication in a field-installable IP65/67 housing.

Ordering focus: Plan eight M8 sensor connections, keep the combined sensor supply within 0.7 A and use the ET-Connection wiring required by the ET 200AL station.
Key Functions

Individual M8 sensor connections

Eight three-pole M8 sockets provide access to the 24 V DC input channels.

Sensor supply monitoring

Electronic short-circuit protection monitors the sensor supply to M at module level and supports configurable diagnostic alarms.

Compact field integration

The 30 mm wide housing uses M8 power and shielded ET-Connection sockets for distributed machine installation.

Official Specifications
Input channels and characteristic 8 P-reading digital inputs; IEC 61131 Type 3
Load supply range 24 V DC nominal; 20.4–28.8 V DC
No-load current consumption 25 mA rated
Supply through-current limits 4 A maximum for 1L+ and 4 A maximum for 2L+
Sensor power outputs 8 outputs with 0.7 A maximum combined current
Typical power loss 1.9 W
Input voltage thresholds Signal 0: −30 to +5 V; signal 1: +11 to +30 V
Typical signal-high current 3.2 mA
Input transition delay 1.2–4.8 ms for rising and falling transitions
Unshielded sensor cable length 30 m maximum
Two-wire sensor quiescent current 1.5 mA maximum
Channel and module indicators Green channel LEDs; green/red module diagnostic LED
Electrical separation Channels isolated from the backplane bus; no channel-to-channel isolation
Insulation test voltage 707 V DC type test
Protection class IP65/67
Operating temperature −30 to +55°C
Maximum operating altitude 5000 m, with additional restrictions above 2000 m
Connection types 3-pole M8 inputs; 4-pole M8 supply; shielded 4-pin M8 ET-Connection
Identification records I&M0–I&M3
Dimensions and mass 30 × 159 × 40 mm (W × H × D); approximately 145 g
Frequently Asked Questions

Which sensor connector should I select for 6ES7141-5BF00-0BA0?

Use a three-pole M8 connection for each digital input.

How much combined sensor current can 6ES7141-5BF00-0BA0 provide?

The eight sensor power outputs share a maximum total current of 0.7 A.

Can 6ES7141-5BF00-0BA0 use a two-wire sensor with a small off-state current?

Two-wire sensors are supported when their quiescent current does not exceed 1.5 mA.

Which engineering versions support 6ES7141-5BF00-0BA0?

The module can be configured with STEP 7 TIA Portal V13 SP1 or later, or STEP 7 V5.5 SP4 Hotfix 3 or later.

Will 6ES7141-5BF00-0BA0 identify a sensor-supply short circuit by individual channel?

Sensor-supply short-circuit detection operates at module level rather than identifying a separate fault for each channel.

Can 6ES7141-5BF00-0BA0 acquire all eight inputs at 55°C?

All eight inputs may be active at the maximum specified ambient temperature of +55°C.

What response delay should I allow for inputs on 6ES7141-5BF00-0BA0?

Allow 1.2–4.8 ms for either input transition at rated voltage.

Compatibility & Ordering Notes
Before ordering 6ES7141-5BF00-0BA0: Plan eight M8 sensor connections, keep the combined sensor supply within 0.7 A and use the ET-Connection wiring required by the ET 200AL station.

Before installation

  • Connect the input sensors with three-pole M8 connectors and keep unshielded sensor runs within 30 m.
  • Limit the total current of the eight sensor supply outputs to 0.7 A.
  • Use the correct STEP 7 release or the matching GSD revision 5 / GSDML V2.3.1 device description.
  • Configure the diagnostic alarm and assemble the M8 power and ET-Connection cables for the station layout.
Hot Selling Models
BES027K BES M30MF-GSC15B-BX00.3-GS04-U
3UA60 00-2H 55-80A
6GK5602-0BA10-2AA3
WAGO 2006-1292
3UF1900-1KA00
1P28B
6502999019 KIB-D03PS/0.6-KL2PU
IEPL04D1
3RV1331-4HC10
517-132-P3-H
0000000.9101.02400
NCN15-30GM60-Z0
AY13E
1070050634-212
910346 2100

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop