Siemens 6ES7138-4FA04-0AB0 ET 200S 4/8 F-DI PROFIsafe Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Select single-channel or two-channel operation to suit the required safety level.
- Use IM151-3 HF when integrating this module into a PROFINET station.
- Allocate six input bytes and four output bytes in the project.
- Respect the sensor-supply current rating and provide correct supply polarity.
6ES7138-4FA04-0AB0 ET 200S 4/8 F-DI PROFIsafe Module
A 30 mm fail-safe input module with eight single-channel or four two-channel inputs and configurable input filtering.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7138-4FA04-0AB0 |
| Product Type | Safety input electronics |
| Core Function | Acquire fail-safe discrete signals |
| Application | ET 200S PROFIsafe stations |
Single- or two-channel acquisition
Eight single-channel inputs or four two-channel input pairs allow the wiring architecture to follow the safety application.
Adjustable filtering
Rising- and falling-edge input delays can be parameterized from 0.3 to 17 ms.
Sensor power distribution
Two sensor supply outputs provide a rated output current of 300 mA with electronic short-circuit protection.
Product Overview
6ES7138-4FA04-0AB0 brings fail-safe 24 V DC input acquisition to an ET 200S station.
Single-channel operation reaches SIL 2, while suitable two-channel operation reaches SIL 3, with Category 4 and Performance Level e available in the applicable safety configuration.
Key Functions
Single- or two-channel acquisition
Eight single-channel inputs or four two-channel input pairs allow the wiring architecture to follow the safety application.
Adjustable filtering
Rising- and falling-edge input delays can be parameterized from 0.3 to 17 ms.
Sensor power distribution
Two sensor supply outputs provide a rated output current of 300 mA with electronic short-circuit protection.
Official Specifications
| Rated supply | 24 V DC |
|---|---|
| Sensor supply outputs | 2; output voltage at least L+ minus 1.5 V |
| Rated sensor supply current | 300 mA |
| Sensor supply short-circuit threshold | 0.7–1.8 A |
| Typical power loss | 4 W |
| Input and output address allocation | 6 input bytes and 4 output bytes |
| Input configuration | 8 single-channel inputs or 4 two-channel inputs |
| Input characteristic | IEC 61131 Type 1 |
| Signal 0 voltage | −30 to +5 V |
| Signal 1 voltage | +15 to +30 V |
| Typical input current | 3.7 mA |
| Parameterized input delay | 0.3–17 ms on rising and falling edges |
| Maximum signal cable length | 200 m, shielded or unshielded |
| Two-wire sensor connection | Not supported |
| Safety capability | SIL 2 single-channel; SIL 3 two-channel; up to Category 4 and PL e |
| Diagnostic indication | Red SF group-fault LED and green input-status LEDs |
| Electrical isolation | Isolated from the backplane bus; no isolation between channels or from L+ |
| Isolation test voltage | 500 V DC |
| Reverse polarity protection | Not provided |
| Dimensions and approximate mass | 30 × 81 × 52 mm; 78 g |
Frequently Asked Questions
Can I connect ordinary two-wire sensors to 6ES7138-4FA04-0AB0?
Two-wire sensor connection is not supported by this input module.
How do I use 6ES7138-4FA04-0AB0 for a SIL 3 input application?
Use a suitable two-channel safety configuration, since single-channel operation is limited to SIL 2.
Can 6ES7138-4FA04-0AB0 suppress a short input pulse?
Its rising- and falling-edge input delays can be parameterized between 0.3 and 17 ms.
How much process-image space should I reserve for 6ES7138-4FA04-0AB0?
Reserve six input bytes and four output bytes for the module.
Which signal voltage switches an input of 6ES7138-4FA04-0AB0 on?
A signal voltage between +15 and +30 V is interpreted as signal 1.
Can 6ES7138-4FA04-0AB0 operate in a PROFINET ET 200S station?
PROFINET operation is possible with an IM151-3 HF interface module.
How far can I run the signal cable from 6ES7138-4FA04-0AB0?
Shielded and unshielded input cables can each be up to 200 m long.