Siemens 6ES7138-4DC01-0AB0 ET 200S 1 STEP Stepper Positioning Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Select an external power unit with a differential RS422 pulse-and-direction interface.
- Keep the motor-command cable within 100 m and use paired twisted shielding.
- Assign the two digital inputs to the required reference or stop functions in the project.
- Provide the 24 V DC load supply and allow for the 15 mm module width.
6ES7138-4DC01-0AB0 ET 200S 1 STEP Stepper Positioning Module
Single-channel stepper positioning module with a 5 V/204 kHz interface, RS422 differential pulse/direction signals and two digital inputs.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7138-4DC01-0AB0 |
| Product Type | Single-axis stepper positioning module |
| Core Function | Pulse-and-direction command generation |
| Application | ET 200S external stepper power stages |
Differential step commands
PULSE/notPULSE and DIR/notDIR signals connect to an RS422-compatible stepper power stage.
Machine reference and stop inputs
Two digital inputs can serve reference cams, pulse suppression, an external stop or limit switches.
Local motion status
RDY, POS, SF and input-state LEDs support positioning and wiring checks.
Product Overview
6ES7138-4DC01-0AB0 generates pulse and direction commands for an external stepper motor power unit from an ET 200S station.
Two 24 V digital inputs support functions such as reference cam, pulse suppression, external stop and limit switch, while dedicated indicators show readiness, positioning mode and group fault.
Key Functions
Differential step commands
PULSE/notPULSE and DIR/notDIR signals connect to an RS422-compatible stepper power stage.
Machine reference and stop inputs
Two digital inputs can serve reference cams, pulse suppression, an external stop or limit switches.
Local motion status
RDY, POS, SF and input-state LEDs support positioning and wiring checks.
Official Specifications
| Load Supply | 24 V DC with reverse-polarity protection |
|---|---|
| Typical Load-Supply Current | 40 mA without load |
| Maximum Backplane Consumption | 10 mA from 3.3 V DC |
| Typical Power Loss | 1.5 W |
| Stepper Command Interface | 5 V differential RS422 pulse and direction |
| Maximum Pulse Frequency | 204 kHz |
| Digital Inputs | 2 inputs; 24 V DC nominal |
| Input Signal Levels | Signal 0: −30 to +5 V; signal 1: +11 to +30 V |
| Typical High-State Input Current | 9 mA |
| Maximum Input Delay | 4 ms for either transition |
| Maximum Input Repeat Frequency | 100 Hz |
| Maximum Digital Input Cable | 1,000 m shielded; 600 m unshielded |
| Maximum Stepper Interface Cable | 100 m, twisted and shielded in pairs |
| Dimensions and Approximate Weight | 15 × 81 × 52 mm; 40 g |
Frequently Asked Questions
Can 6ES7138-4DC01-0AB0 drive the motor windings directly?
The module sends pulse and direction commands to an external stepper power unit.
Which command interface must the power stage accept for 6ES7138-4DC01-0AB0?
The power stage must accept RS422 differential PULSE/notPULSE and DIR/notDIR signals.
How long can the stepper command cable be for 6ES7138-4DC01-0AB0?
The command cable can extend up to 100 m when the conductors are twisted and shielded in pairs.
Can I connect a reference cam to 6ES7138-4DC01-0AB0?
The digital inputs support reference-cam functions as well as pulse suppression, external stop and limit-switch functions.
What input voltage should I use for stop and reference signals on 6ES7138-4DC01-0AB0?
The digital inputs are designed for 24 V DC signals with a high-state range of +11 to +30 V.
Which indicators help me troubleshoot positioning on 6ES7138-4DC01-0AB0?
The module provides RDY, green POS, red SF and green digital-input indicators.
How many motion axes can 6ES7138-4DC01-0AB0 command?
The module provides one stepper motor positioning channel.