Siemens 6ES7138-4DA01-0AB0 SIMATIC ET 200S 1COUNT 24 V Counter Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Select the intended continuous, once-only, periodic or measurement mode and assign the corresponding control and feedback data.
- Use a suitable ET 200S terminal module and a 24 V encoder signal arrangement.
- Apply the encoder-cable limit associated with the selected input filter.
- Set the comparison-output function and CPU/master-stop response, and derate its current for the installation temperature.
6ES7138-4DA01-0AB0 SIMATIC ET 200S 1COUNT 24 V Counter Module
Single-channel 24 V pulse counter with continuous, once-only and periodic counting, frequency measurement and a comparison output.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7138-4DA01-0AB0 |
| Product Type | Counter electronics module |
| Core Function | Pulse counting and time-based measurement |
| Application | ET 200S distributed I/O stations |
Flexible count cycles
Continuous, once-only and periodic counting provide different responses to the configured count limits.
Time-oriented measurement
Frequency, rotational-speed and period measurement convert pulse timing into process values.
Gate and comparison control
The digital input can control the count gate, while the local output responds to the selected comparison function.
Product Overview
6ES7138-4DA01-0AB0 provides a distributed counting channel for 24 V pulse generators in an ET 200S station, allowing pulse acquisition to be handled at the field I/O level.
Counting modes, measurement functions and a local comparison output support tasks such as accumulating pulses, evaluating frequency and generating a response at a configured count value.
Key Functions
Flexible count cycles
Continuous, once-only and periodic counting provide different responses to the configured count limits.
Time-oriented measurement
Frequency, rotational-speed and period measurement convert pulse timing into process values.
Gate and comparison control
The digital input can control the count gate, while the local output responds to the selected comparison function.
Official Specifications
| Counter channel and range | 1 channel; 32-bit counter range |
|---|---|
| Nominal pulse signal | 24 V signals up to 100 kHz |
| Load supply | 24 V DC nominal; 20.4–28.8 V DC |
| Encoder supply | L+ minus 0.8 V; 500 mA maximum, short-circuit protected |
| Backplane current | 10 mA maximum |
| L+ current without load | 42 mA maximum |
| Typical power dissipation | 1 W |
| Counter electrical separation | Isolated from backplane bus; not isolated from load voltage |
| Input thresholds | Signal 0: −30 to +5 V; signal 1: +11 to +30 V |
| Input current | 9 mA typical for signal 1; 2 mA maximum quiescent current |
| Minimum input pulse width | 25 µs with filter enabled; 2.5 µs with filter disabled |
| Shielded encoder cable length | 50 m with 200 kHz filter; 100 m with 20 kHz filter |
| Output signal levels | Signal 0 at or below 3 V; signal 1 at or above L+ minus 1 V |
| Output-current temperature limits | 2 A at 40°C; 1 A at 50°C; 0.5 A at 60°C |
| Output off-state current | 0.5 mA maximum |
| Output switching limits | 100 Hz resistive; 2 Hz inductive; up to 10 Hz for lamp loads up to 5 W |
| Output short-circuit threshold | 2.6–4 A |
| Output wiring distances | 600 m unshielded; 1000 m shielded |
| Measurement ranges | 0.1 Hz–100 kHz frequency; 1–25000 rpm speed; 10 µs–120 s period |
| Dimensions and weight | 15 × 81 × 52 mm (W × H × D); approximately 40 g |
Frequently Asked Questions
Can 6ES7138-4DA01-0AB0 restart a count cycle automatically at its limit?
Periodic counting repeats the configured cycle, while once-only counting stops according to the selected limit behavior.
Which terminal modules can be used with 6ES7138-4DA01-0AB0?
The counter can be installed on TM-E15S24-01 or TM-E15S26-A1 terminal modules.
Can a hardware signal gate the count on 6ES7138-4DA01-0AB0?
The digital input can be assigned to the hardware-gate function.
How should I reduce the output load of 6ES7138-4DA01-0AB0 in a hot cabinet?
Reduce the rated output current from 2 A at 40°C to 1 A at 50°C or 0.5 A at 60°C.
Can 6ES7138-4DA01-0AB0 calculate speed from encoder pulses?
Rotational-speed measurement covers 1–25000 rpm.
What should I change for a longer encoder cable on 6ES7138-4DA01-0AB0?
The shielded encoder-cable limit is 50 m with the 200 kHz filter or 100 m with the 20 kHz filter.
Can I use the output of 6ES7138-4DA01-0AB0 to act on a comparison value?
The local digital output can be controlled by the configured count or measurement comparison function.