Siemens 6ES7134-6JD00-0CA1 SIMATIC ET 200SP Four-Channel RTD/TC High Feature Input
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Select an A0 or A1 BaseUnit and the appropriate CC00 color coding.
- Configure the sensor range, compensation source and wiring method for each channel.
- Reserve the additional quality-information byte and include diagnostic checks in the cycle-time calculation.
- For FS22 hardware with V3.0.0 firmware, use TIA Portal V21 with HSP0495 or integrated support from V21.1, or STEP 7 V5.7 SP3 HF3 with HSP0348 V2.0 or integrated support from V5.8.
6ES7134-6JD00-0CA1 SIMATIC ET 200SP Four-Channel RTD/TC High Feature Input
A four-channel High Feature module for RTDs, thermocouples, resistance and low-voltage signals, with per-channel diagnostics and RUN reparameterization.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7134-6JD00-0CA1 |
| Product Type | Universal temperature input module |
| Core Function | Converting thermal and resistance measurements |
| Application | ET 200SP stations with A0 or A1 BaseUnits |
Multiple sensor technologies
RTDs, thermocouples, resistors and bipolar low-voltage inputs share the configurable acquisition platform.
RUN adjustment and calibration
Reparameterization and calibration can be performed in RUN for supported configuration changes.
Channel-level condition reporting
Quality information, wire-break and range diagnostics accompany configurable limit alarms.
Product Overview
6ES7134-6JD00-0CA1 combines multiple temperature-sensor technologies in a four-channel ET 200SP module.
Two-, three- and four-wire resistance connections, selectable compensation sources and scalable measuring ranges support the configured field measurement without forcing one sensor technology across the entire application.
Key Functions
Multiple sensor technologies
RTDs, thermocouples, resistors and bipolar low-voltage inputs share the configurable acquisition platform.
RUN adjustment and calibration
Reparameterization and calibration can be performed in RUN for supported configuration changes.
Channel-level condition reporting
Quality information, wire-break and range diagnostics accompany configurable limit alarms.
Official Specifications
| Input count | 4 |
|---|---|
| Resolution | 16 bits including sign for voltage and temperature; 15 bits for resistance ranges |
| Supply voltage | 24 V DC nominal; 19.2–28.8 V range |
| Supply current | 34 mA rated; 35 mA maximum |
| Typical power loss | 0.75 W |
| Input address use | 8 bytes plus 1 byte for quality information |
| Voltage ranges | ±1 V, ±250 mV, ±80 mV and ±50 mV |
| RTD types | Cu10; Ni100, Ni120, Ni200, Ni500, Ni1000, LG-Ni1000; Pt100, Pt200, Pt500 and Pt1000 |
| Thermocouple types | B, C, E, J, K, L, N, R, S, T, U and TXK/TXK(L) |
| Resistance ranges | 0–150, 0–300, 0–600, 0–3,000 and 0–6,000 Ω; PTC |
| Input impedance | 1 MΩ |
| Typical resistance-sensor excitation | 0.7 mA; 1.7 mA for Cu10 |
| Temperature units | °C, °F or K |
| Maximum shielded cable | 200 m; 50 m for thermocouples |
| Digital smoothing | Four levels: none, 4×, 8× and 16× conversion time |
| Voltage and resistance accuracy | ±0.05% basic at 25 °C; ±0.1% operational limit |
| Additional diagnostic conversion time | 2 ms for wire-break check; additional 2 ms power-line check for 3-/4-wire resistance sensors |
| Input isolation | No channel-to-channel isolation; isolated from backplane and electronics supply |
| Isolation test | 707 V DC type test |
| Channel alarms | Two upper and two lower limits; wire-break and overflow/underflow diagnostics |
Frequently Asked Questions
Which BaseUnit families can I use with 6ES7134-6JD00-0CA1?
The module is suitable for BaseUnit types A0 and A1.
Which BaseUnit enables the internal thermocouple reference junction on 6ES7134-6JD00-0CA1?
Internal reference-junction compensation uses a type A1 BaseUnit.
Does three-wire line compensation affect the cycle time of 6ES7134-6JD00-0CA1?
Three-wire line compensation requires an additional acquisition cycle.
Does a Cu10 sensor use the ordinary excitation current on 6ES7134-6JD00-0CA1?
Cu10 sensors use a typical 1.7 mA excitation current rather than the ordinary 0.7 mA.
Can I calibrate or reparameterize 6ES7134-6JD00-0CA1 while the station is in RUN?
Both calibration and reparameterization are supported in RUN.
Is eight bytes enough address space when I use quality information from 6ES7134-6JD00-0CA1?
Quality information requires an additional byte alongside the eight bytes of input data.
Can I use the full 200 m shielded cable allowance for a thermocouple on 6ES7134-6JD00-0CA1?
Thermocouple wiring is limited to 50 m even though other supported shielded sensor circuits permit up to 200 m.