Siemens 6ES7134-6HB00-0CA1 SIMATIC ET 200SP AI 2xU/I 2-/4-Wire High Feature Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use an A0 or A1 BaseUnit and the CC05 color-code identification.
- Match the two-wire or four-wire supply arrangement to the sensor requirements.
- Configure measurement range, filtering and diagnostics for each channel.
- Account for scaled values and quality information in the process address map.
6ES7134-6HB00-0CA1 SIMATIC ET 200SP AI 2xU/I 2-/4-Wire High Feature Module
Two differential voltage/current inputs with channel diagnostics, up to 16-bit resolution and support for two-wire and four-wire transmitters.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7134-6HB00-0CA1 |
| Product Type | Analog input module |
| Core Function | Acquiring isolated voltage and current process signals |
| Application | ET 200SP BaseUnits A0 and A1 |
Flexible signal measurement
Supports bipolar and unipolar voltage/current ranges with resolution up to 16 bits including sign.
Transmitter integration
Separate supply arrangements support two-wire current transmitters and four-wire current or voltage sensors.
Process diagnostics
Reports supply faults, overflow/underflow and range-dependent wire-break or short-circuit conditions.
Product Overview
6ES7134-6HB00-0CA1 acquires two differential analog signals with selectable voltage or current ranges and High Feature diagnostics in an ET 200SP station.
Measured-value scaling, quality information and configurable filtering support the process interface, while the sensor-supply arrangement and signal-cable limit depend on the chosen measurement mode.
Key Functions
Flexible signal measurement
Supports bipolar and unipolar voltage/current ranges with resolution up to 16 bits including sign.
Transmitter integration
Separate supply arrangements support two-wire current transmitters and four-wire current or voltage sensors.
Process diagnostics
Reports supply faults, overflow/underflow and range-dependent wire-break or short-circuit conditions.
Official Specifications
| Analog inputs | 2 differential inputs |
|---|---|
| Rated supply and permitted range | 24 V DC; 19.2–28.8 V DC |
| Supply-current consumption | 39 mA rated; 240 mA maximum |
| Typical power loss | 0.95 W |
| Voltage ranges | 0–10 V, 1–5 V, ±10 V and ±5 V |
| Current ranges | 0–20 mA, 4–20 mA and ±20 mA |
| Input resistance | 75 kΩ for voltage measurement; 130 Ω for current measurement |
| Resolution | 16 bits including sign for bipolar ranges; 15 bits for unipolar ranges |
| Two-wire transmitter supply | 24 V, maximum 20 mA per channel; up to 50 mA for less than 10 s |
| Additional four-wire sensor supply | 24 V, maximum 100 mA; up to 150 mA for less than 10 s |
| Maximum shielded cable length | 1,000 m for current measurement; 200 m for voltage measurement |
| Conversion time per channel | 0.9–68.2 ms depending on the configured interference-suppression setting |
| Smoothing | None, 2-fold, 4-fold, 8-fold, 16-fold or 32-fold |
| Operational measurement error | ±0.1% of input range for voltage and current over the overall temperature range |
| Basic error at 25 °C | ±0.05%; ±0.1% with 4.8 kHz interference suppression |
| Range-dependent diagnostics | Wire break for 4–20 mA; short circuit for 1–5 V or sensor-supply short circuit |
| Channel isolation | Between channels, from backplane and from electronics supply; 707 V DC type test |
| Address allocation | 4 bytes; an additional 4 bytes for scaling and 1 byte for quality information |
| Dimensions (W × H × D) | 15 × 73 × 58 mm |
| Approximate weight | 32 g |
Frequently Asked Questions
Can 6ES7134-6HB00-0CA1 connect to both two-wire and four-wire transmitters?
Both connection arrangements are supported with BaseUnit type A0 or A1.
How much extra address space is needed for scaling and quality information on 6ES7134-6HB00-0CA1?
Reserve an additional four bytes for scaled measured values and one byte for quality information beyond the four-byte base allocation.
Does 6ES7134-6HB00-0CA1 detect a wire break in every current range?
Wire-break detection is specified only for the 4–20 mA measurement range.
Can a voltage signal use a 1,000 m cable with 6ES7134-6HB00-0CA1?
The shielded cable limit for voltage measurement is 200 m, while current measurement permits up to 1,000 m.
Are the two input channels of 6ES7134-6HB00-0CA1 isolated from each other?
The channels are isolated from one another as well as from the backplane and electronics supply.
Can 6ES7134-6HB00-0CA1 provide a continuous 100 mA supply for a two-wire transmitter?
The two-wire supply is limited to 20 mA per channel continuously, while the additional four-wire supply permits up to 100 mA.
What smoothing choices are available when commissioning 6ES7134-6HB00-0CA1?
Select no smoothing or a 2-fold, 4-fold, 8-fold, 16-fold or 32-fold setting.