Siemens 6ES7132-4HB01-0AB0 ET 200S 2-Channel Relay Output Modules, Pack of 5
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Allow two relay channels per module and five modules per packing unit.
- Match the ET 200S station terminal arrangement and 24 V DC power-module supply.
- Keep each load within the 5 A rating and above the 8 mA minimum.
- Provide load-circuit protection and suitable suppression for inductive loads.
- Configure the intended 0 or 1 substitute values and address packing.
6ES7132-4HB01-0AB0 ET 200S 2-Channel Relay Output Modules, Pack of 5
A five-unit pack of 15 mm ET 200S electronic modules, each providing two 5 A relay outputs with configurable substitute values.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-4HB01-0AB0 |
| Product Type | Two-channel relay output electronic module, five-unit pack |
| Core Function | Switches two relay outputs per module |
| Application | ET 200S distributed control of AC and DC switching loads |
Two outputs per module
Each electronic module has two relay output channels.
Five-unit order pack
The order number covers five electronic modules.
Substitute-value operation
Each output supports configurable substitute values of 0 or 1.
Product Overview
6ES7132-4HB01-0AB0 is a five-unit pack of ET 200S relay output electronic modules for switching field loads through two channels per module.
The 15 mm modules obtain their 24 V DC electronics supply from the power module and provide isolated relay channels, output status indication and selectable substitute values.
Key Functions
Relay load switching
Two relay outputs per module switch loads within the specified 24 V DC to 230 V AC and 5 A ratings, with a minimum load current of 8 mA.
Configured fallback behavior
Substitute values of 0 or 1 can be assigned to the outputs for the configured substitute-value response.
Compact ET 200S integration
A 15 mm module width and a packed address allocation of two bits support compact ET 200S station layouts.
Official Specifications
| Rated electronics supply | 24 V DC from power module; reverse-polarity protection |
|---|---|
| Maximum no-load current from L+ | 30 mA |
| Maximum 3.3 V backplane current | 10 mA |
| Typical power loss | 0.6 W |
| Address allocation | Maximum 1 byte per module; 2 bits with packing |
| Relay switching voltage | 24 V DC to 230 V AC |
| Rated output current and thermal continuous current | 5 A |
| Minimum load current | 8 mA |
| Maximum resistive-load and lamp-load switching frequency | 2 Hz |
| Maximum inductive-load switching frequency | 0.5 Hz |
| Short-circuit protection | No integrated protection |
| Inductive shutdown-voltage limitation | Not integrated |
| Maximum output cable length | 1,000 m shielded; 600 m unshielded |
| Configurable substitute values | 0 or 1 |
| Output status indication | Green LED |
| Channel isolation | Between channels, and from backplane bus and load voltage L+ |
| Dimensions per module (W × H × D) | 15 × 81 × 52 mm |
| Approximate weight per module | 50 g |
Frequently Asked Questions
Does an order for 6ES7132-4HB01-0AB0 contain two outputs or five modules?
One packing unit contains five modules, each with two relay outputs.
Can 6ES7132-4HB01-0AB0 reliably switch a very small sensing load?
The connected load must satisfy the specified minimum current of 8 mA.
How much output address space does 6ES7132-4HB01-0AB0 use when packing is enabled?
Each module uses two output bits with packing enabled, compared with a maximum allocation of one byte per module.
What fallback output levels can be selected for 6ES7132-4HB01-0AB0?
The configurable substitute values are 0 and 1.
Does 6ES7132-4HB01-0AB0 include short-circuit protection for the load circuit?
The relay outputs have no integrated short-circuit protection, so the load circuit requires appropriate external protection.
What changes when 6ES7132-4HB01-0AB0 switches an inductive load instead of a resistive load?
The maximum switching rate falls from 2 Hz for a resistive load to 0.5 Hz for an inductive load, and inductive shutdown-voltage limitation is not integrated.
Where does 6ES7132-4HB01-0AB0 obtain its electronics supply?
The electronics receive a rated 24 V DC supply from the ET 200S power module.