Siemens 6ES7131-6BF01-0AA0 ET 200SP DI 8x24VDC BA
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Keep total sensor-supply current within 700 mA.
- Use AUX terminals or a potential distributor for three-wire sensors.
- Use a potential distributor with A0 for four-wire sensors.
- Apply the below-zero temperature capability only from hardware FS03.
6ES7131-6BF01-0AA0 ET 200SP DI 8x24VDC BA
Eight P-reading digital inputs with a protected sensor-supply arrangement, selectable input delay and module supply-voltage diagnostics.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7131-6BF01-0AA0 |
| Product Type | Basic digital input module |
| Core Function | Acquisition of PNP field signals |
| Application | Distributed sensor stations |
PNP signal interface
Eight sinking inputs acquire 24 V DC PNP signals.
Sensor power
The encoder supply is short-circuit protected at module level.
A0 installation
Fits BaseUnits of type A0 and uses the CC01 identification code.
Product Overview
6ES7131-6BF01-0AA0 acquires eight 24 V DC digital signals from PNP sensors in an ET 200SP station. The Basic input module combines P-reading inputs with a sensor-supply arrangement protected against short circuits at module level.
Its input filtering offers eight selectable delay settings, while supply monitoring and a group-error indication support station troubleshooting. Three-wire and four-wire sensor connections require the corresponding AUX or potential-distribution arrangement around the A0 BaseUnit.
Key Functions
Supply and read PNP sensors
The module provides eight sensor-supply outputs with a 700 mA maximum total per module and reads the connected PNP input signals.
Select the input response
Delay settings range from 0.05 to 20 ms, with another 30 to 500 µs depending on cable length.
Diagnose module supply conditions
Parameterizable supply-voltage monitoring, group-error indication and PWR/DIAG LEDs support module-level checks.
Official Specifications
| Input channel count | 8, parameterizable |
|---|---|
| Supply voltage | 24 V DC rated; permissible range 19.2–28.8 V DC |
| Input circuit | Sinking, PNP, P-reading; IEC 61131 Types 1, 2 and 3 |
| Input voltage thresholds | Signal 0: −30 to +5 V; signal 1: +11 to +30 V |
| Typical signal-1 current | 6.8 mA |
| Sensor-supply arrangement | 8 outputs; minimum output voltage 19.2 V; module-level short-circuit protection |
| Maximum sensor-supply current | 700 mA per channel and 700 mA total per module |
| Module consumption and loss | 70 mA maximum supply current; 1.6 W typical loss with eight inputs supplied from the encoder supply |
| Input-delay settings | 0.05, 0.1, 0.4, 0.8, 1.6, 3.2, 12.8 or 20 ms, plus 30–500 µs line-dependent delay |
| Maximum input-cable length | 1,000 m shielded; 600 m unshielded |
| Two-wire sensor quiescent current | 2 mA maximum |
| Input address allocation | 1 byte |
| BaseUnit identification | Type A0; CC01 color code; type A mechanical coding |
| Engineering support | TIA Portal V14 or later; STEP 7 V5.5 SP3 or later; PROFINET GSDML V2.3 |
| Diagnostic coverage | Supply-voltage monitoring and group error; no wire-break, short-circuit or channel diagnostics |
| Electrical isolation | Inputs isolated from backplane bus; no isolation between channels |
| Insulation test | 707 V DC, type test |
| Operating temperature | Horizontal: −30 to +60 °C; vertical: −30 to +50 °C; below 0 °C from FS03 |
| Dimensions and weight | 15 × 73 × 58 mm (W × H × D); approximately 28 g |
Frequently Asked Questions
Can the sensor supply of 6ES7131-6BF01-0AA0 provide 700 mA to every channel at once?
The sensor supply is limited to 700 mA per module as well as 700 mA per channel.
Which input polarity does 6ES7131-6BF01-0AA0 need from a three-wire proximity sensor?
The sinking inputs require PNP, P-reading signals.
How low can an input-on voltage fall before it leaves the guaranteed range of 6ES7131-6BF01-0AA0?
The guaranteed signal-1 voltage range starts at +11 V and extends to +30 V.
What extra terminals are needed for four-wire sensors on 6ES7131-6BF01-0AA0?
Use a type A0 BaseUnit together with a potential distributor module.
Can 6ES7131-6BF01-0AA0 locate a shorted sensor cable through channel diagnostics?
The module does not provide individual channel, wire-break or short-circuit diagnostics.
Can I configure 6ES7131-6BF01-0AA0 with TIA Portal V13?
Integrated configuration begins with TIA Portal V14.
How much input address space does 6ES7131-6BF01-0AA0 occupy in the station?
The module occupies one byte of input address space.