Siemens 6ES5304-3UB11 SIMATIC S5 IM 304 Interface Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Set the cable-length jumpers for the actual expansion-link length.
- Use the appropriate IM314, IM314H/R or IM324U/R receiving interface for the system.
- Fit the correct terminator to the final receiver of every group.
- Lock front connectors with their metal catches and provide equipotential bonding between S5 devices.
6ES5304-3UB11 SIMATIC S5 IM 304 Interface Module
An IM 304 central-side interface for symmetrical distributed S5 bus connections over distances of up to 600 m per expansion interface.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES5304-3UB11 |
| Product Type | Central-rack interface electronics |
| Core Function | Extend the controller bus |
| Application | S5 central controllers and expansion units |
Distributed expansion links
Up to four receiving IM314 or IM314H/R modules can be connected per interface, over a maximum distance of 600 m to the last receiver.
Multiplexed S5 bus transfer
The 16-bit address bus and 16-bit data bus share 16 transmission lines using time-division multiplexing.
Fault-tolerant controller coupling
The lower X4 connector supports the appropriate IM324U/R coupling arrangement for compatible fault-tolerant systems.
Product Overview
6ES5304-3UB11 extends the central-controller bus to compatible S5 expansion equipment through symmetrical RS485 signaling.
Two parallel interfaces transmit a 16-bit address bus and a 16-bit data bus by time-division multiplexing, while front jumpers adapt operation to the cable length and system arrangement.
Key Functions
Distributed expansion links
Up to four receiving IM314 or IM314H/R modules can be connected per interface, over a maximum distance of 600 m to the last receiver.
Multiplexed S5 bus transfer
The 16-bit address bus and 16-bit data bus share 16 transmission lines using time-division multiplexing.
Fault-tolerant controller coupling
The lower X4 connector supports the appropriate IM324U/R coupling arrangement for compatible fault-tolerant systems.
Official Specifications
| Expansion interface count | 2 parallel symmetrical interfaces |
|---|---|
| Electrical transmission standard | Differential RS485 |
| Address and data width | 16-bit address bus and 16-bit data bus |
| Multiplexing | Time-division multiplexing over 16 common lines |
| Transmission-rate range | 100 kB/s–2 MB/s |
| Maximum expansion-link length | 600 m per interface to the last IM314 or IM314H/R |
| Receiver capacity | Maximum 4 receiving interface modules per interface |
| Maximum IM324U link | 100 m through X4 |
| Maximum IM324R link | 10 m through X4 |
| Approximate module current | 1.2 A |
| Backplane connectors | Two 48-pin connectors, ES902 row 2 |
| Front connectors | Two 50-pin male connectors |
| Front-panel width | 20.32 mm; 1⅓ standard slots |
| Circuit-board format | Double Eurocard, 233.4 × 160 mm |
| Operating temperature | 0 to +55 °C |
| Maximum relative humidity | 95% at 25 °C, non-condensing |
| Maximum operating altitude | 1,500 m above sea level |
| Permitted device potential difference | Maximum 7 V |
| Approximate module mass | 360 g |
Frequently Asked Questions
Which receiver should I pair with 6ES5304-3UB11 for a standard expansion unit?
Use an IM314-3UA11 on the expansion-unit side of the symmetrical connection.
How far can the last expansion receiver be from 6ES5304-3UB11?
The maximum cable length per interface is 600 m and the actual length must be set at the central-side module.
How many expansion receivers can I chain from one interface of 6ES5304-3UB11?
A maximum of four IM314 or IM314H/R receiving modules can be connected per interface.
Which connector on 6ES5304-3UB11 handles fault-tolerant controller coupling?
Use the lower front connector X4 for the compatible IM324U/R controller link.
Which terminator finishes a standard IM314 chain driven by 6ES5304-3UB11?
The final IM314 in each group requires a 6ES5760-1AA11 terminator.
Which termination is required for an IM314H/R chain connected to 6ES5304-3UB11?
The final IM314H/R requires the 6ES5760-0HA11 terminator.
What potential difference can the connected S5 devices tolerate with 6ES5304-3UB11?
The potential difference between two connected S5 devices must not exceed 7 V.