- Keep the AC supply within one of the two permitted input windows.
- Apply the temperature-dependent output limits when sizing continuous and overload demand.
- Connect the 24 V OK relay contact within its DC switching rating.
- Maintain 50 mm free space above and below the DIN-rail-mounted supply.
6EP1333-2BA20 SITOP PSU100S 24 V 5 A Power Supply
A narrow SITOP smart supply with automatic 120/230 V AC range selection, adjustable 24 V DC output and a 24 V OK relay contact.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1333-2BA20 |
| Product Type | Stabilized DIN-rail power supply |
| Core Function | Isolated DC control power |
| Application | Industrial control cabinets |
Automatic AC range selection
The supply selects between the 85–132 V and 170–264 V AC input ranges without a manual input selector.
Power reserve for load transients
The output supports a 150% rated-current overload for up to 5 seconds per minute under the specified operating conditions.
Remote DC status
A normally open 24 V OK relay contact provides a separate status signal rated for 60 V DC at 0.3 A.
Product Overview
6EP1333-2BA20 supplies stabilized DC power with automatic selection between the 120 V and 230 V AC input ranges.
The 50 mm-wide housing combines an adjustable output, overload capability and a relay signal for remote monitoring of the DC supply, supporting control circuits that need both power and a status indication.
Key Functions
Automatic AC range selection
The supply selects between the 85–132 V and 170–264 V AC input ranges without a manual input selector.
Power reserve for load transients
The output supports a 150% rated-current overload for up to 5 seconds per minute under the specified operating conditions.
Remote DC status
A normally open 24 V OK relay contact provides a separate status signal rated for 60 V DC at 0.3 A.
Official Specifications
| Nominal AC input | 120/230 V AC, single phase, automatic range selection |
|---|---|
| Permissible input windows | 85–132 V AC or 170–264 V AC |
| Line frequency | 47–63 Hz; nominal 50/60 Hz |
| Rated output | 24 V DC, 5 A |
| Output adjustment | 22.8–28 V DC by potentiometer |
| Additional continuous output | Up to 6 A at ambient temperatures up to 45 °C |
| Overload duty | 150% of rated output current for up to 5 s per minute |
| Mains buffering | At least 20 ms at rated output current and 93/187 V input |
| Maximum residual ripple | 150 mV; typically 30 mV |
| DC status contact | Normally open relay contact; 60 V DC, 0.3 A |
| Typical efficiency | 88% |
| Typical rated-load power loss | 16 W |
| Current limitation | Constant-current characteristic; response 6–7.1 A |
| Protection | IP20; electrical protection class I |
| Operating temperature | −25 to +70 °C with natural convection; output derating applies |
| Dimensions | 50 × 125 × 120 mm |
| Ventilation clearance | 50 mm above and below; no side spacing required |
| Terminal conductors | 0.5–2.5 mm², screw terminals |
| Mounting rail | EN 60715, 35 × 7.5/15 mm |
| Net weight | 0.5 kg |
Frequently Asked Questions
Do I need to change an input selector when moving 6EP1333-2BA20 from 120 V to 230 V AC?
The supply selects the appropriate input range automatically.
Can 6EP1333-2BA20 operate at any AC voltage between 85 and 264 V?
The permitted input windows are 85–132 V and 170–264 V AC rather than one continuous range.
How can a PLC monitor the output status of 6EP1333-2BA20?
Use the normally open 24 V OK relay contact within its rating of 60 V DC and 0.3 A.
Can 6EP1333-2BA20 continuously supply 6 A in a cool cabinet?
The output range extends to 6 A at ambient temperatures up to 45 °C.
How much short-duration overload is available from 6EP1333-2BA20?
The normal-operation overload capability is 150% of rated output current for up to 5 seconds per minute.
What free space should I keep above and below 6EP1333-2BA20?
Provide 50 mm of ventilation clearance above and below the housing.
Can the DC output of 6EP1333-2BA20 be adjusted below 24 V?
The output potentiometer permits adjustment from 22.8 to 28 V DC.