- Use the permitted AC or DC input range.
- Connect protective earth and use the specified terminal conductor sizes.
- Apply 3% per kelvin derating above 55 °C.
- Keep 50 mm ventilation space above and below.
- Use the specified EN 60715 DIN rail.
6EP1332-5BA10 SITOP PSU100C 24 V 4 A Power Supply
A compact 96 W supply with a regulated 24 V DC, 4 A output, wide-range AC or DC input and a 52.5 mm enclosure width.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1332-5BA10 |
| Product Type | Stabilized power supply |
| Core Function | Isolated AC or DC to DC conversion |
| Application | Industrial control-panel power circuits |
Wide-range input
Accepts 85–264 V AC or 110–300 V DC.
Adjustable output
A potentiometer trims the nominal 24 V output between 22.2 and 26.4 V.
Thermal planning
Above 55 °C the output-current rating decreases by 3% per kelvin.
Product Overview
6EP1332-5BA10 supplies regulated 24 V DC control power at up to 4 A from a single-phase AC or DC source, with electrical isolation between input and output.
The narrow DIN-rail enclosure uses natural convection and a green output-OK indicator; electronic short-circuit shutdown with automatic restart supports recovery after an output fault is removed.
Key Functions
Stabilize the control voltage
The isolated output provides a nominal 24 V DC and can be adjusted from 22.2 to 26.4 V.
Buffer short mains interruptions
At 230 V input and rated output current, the minimum mains buffering time is 20 ms.
Manage output faults
Electronic shutdown provides short-circuit protection with automatic restart, and the typical current limit is 4.8 A.
Official Specifications
| Permissible AC Input | 85–264 V AC, single phase |
|---|---|
| DC Input Range | 110–300 V DC |
| Input Frequency | 47–63 Hz |
| Rated Output | 24 V DC, 4 A; 96 W typical |
| Output Adjustment | 22.2–26.4 V via potentiometer |
| Overall Voltage Tolerance | 3% |
| Output Residual Ripple | 200 mV maximum; 80 mV typical |
| Minimum Mains Buffering | 20 ms at 230 V input and rated output current |
| Typical Efficiency | 88% |
| Maximum Inrush Current | 34 A at 25 °C |
| Typical Output Current Limit | 4.8 A |
| Output Fault Response | Electronic short-circuit shutdown with automatic restart |
| Insulation and Protection Class | Isolated SELV output; Class I |
| Enclosure Protection | IP20 |
| Operating Temperature and Derating | −20 to +70 °C; above +55 °C, 3% per kelvin; 2.2 A at +70 °C |
| Ventilation Clearance | 50 mm above and below; 0 mm at either side |
| Electrical Terminations | Screw terminals, 0.5–2.5 mm² conductors |
| Mounting Rail | EN 60715, 35 × 7.5 mm or 35 × 15 mm |
| Dimensions (W × H × D) | 52.5 × 80 × 100 mm |
| Net Weight | 0.32 kg |
Frequently Asked Questions
Can 6EP1332-5BA10 run from a DC source instead of the mains?
The supply accepts 110–300 V DC as well as its wide-range AC input.
How far can I adjust the output of 6EP1332-5BA10?
The front potentiometer adjusts the output from 22.2 to 26.4 V.
Will 6EP1332-5BA10 supply its full 4 A at 70 °C?
At 70 °C the rated output current is reduced to 2.2 A.
How much vertical clearance does 6EP1332-5BA10 require?
Leave at least 50 mm above and 50 mm below the enclosure.
How does 6EP1332-5BA10 recover after an output short circuit?
Electronic shutdown is followed by automatic restart.
Can two 6EP1332-5BA10 units increase the available output capacity?
Up to two supplies can be connected in parallel to increase power.
Which feeder breaker is recommended for 6EP1332-5BA10?
Use a miniature circuit breaker from 16 A with characteristic B or from 10 A with characteristic C.