Siemens 6EP1331-1SH03 LOGO!Power 24 V 1.3 A Power Supply
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Set the output voltage for the actual load and account for the 2%/K current derating above 55 °C.
- Follow the manufacturer parallel-connection instructions when using two supplies for increased power.
- Use the L/N input and specified output screw terminals with conductors in the documented range.
- Snap the supply onto a suitable 35 mm DIN rail, keeping 20 mm above and below for natural convection.
6EP1331-1SH03 LOGO!Power 24 V 1.3 A Power Supply
LOGO!Power supply with 24 V, 1.3 A output, 22.2–26.4 V adjustment, Class II construction and a 54 mm wide DIN-rail housing.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1331-1SH03 |
| Product Type | Regulated DIN-rail power supply |
| Core Function | Isolated adjustable 24 V DC supply |
| Application | LOGO! and compact industrial control circuits |
Adjustable control voltage
The output can be set from 22.2 to 26.4 V using the potentiometer.
Supply continuity and soft start
Minimum mains buffering is 40 ms at 187 V input and rated load, and the output starts without voltage overshoot.
Compact isolated power
The Class II design supplies isolated low voltage without a protective conductor and supports the documented two-unit parallel arrangement.
Product Overview
6EP1331-1SH03 is a regulated LOGO!Power supply with a nominal 24 V DC, 1.3 A output. Its wide AC/DC input and compact DIN-rail form suit control circuits that need an isolated low-voltage supply.
The output voltage can be trimmed through a potentiometer, and Siemens allows two units in parallel for increased power. Above 55 °C, output current must be reduced according to the stated 2% per kelvin derating up to 70 °C.
Key Functions
Adjustable control voltage
The output can be set from 22.2 to 26.4 V using the potentiometer.
Supply continuity and soft start
Minimum mains buffering is 40 ms at 187 V input and rated load, and the output starts without voltage overshoot.
Compact isolated power
The Class II design supplies isolated low voltage without a protective conductor and supports the documented two-unit parallel arrangement.
Official Specifications
| Rated AC input | 100–240 V AC; permissible range 85–264 V |
|---|---|
| DC input range | 110–300 V DC |
| Input frequency | 47–63 Hz |
| Rated output | 24 V DC, 1.3 A |
| Output adjustment | 22.2–26.4 V through potentiometer |
| Typical output power | 30 W |
| Output-current derating | 2% per kelvin from +55 to +70 °C |
| Parallel operation | Two units permitted for increased power |
| Input current | 0.7 A at 120 V AC; 0.35 A at 230 V AC |
| Maximum inrush current | 25 A at 25 °C |
| Minimum mains buffering | 40 ms at 187 V input and rated output current |
| Output ripple / voltage peak | 200 mV / 300 mV maximum |
| Start-up behavior | Soft start without output overshoot; maximum delay 0.5 s |
| Efficiency | 85% |
| Power loss | 6 W typical at rated load; 2 W maximum at no load |
| Short-circuit protection | Constant-current characteristic; typical 1.7 A |
| Electrical protection | Class II without protective conductor; isolated safety extra-low output; IP20 |
| Operating / storage temperature | −20 to +70 °C with natural convection / −40 to +85 °C |
| Dimensions and weight | 54 × 90 × 52.6 mm (W × H × D); 0.17 kg |
| Installation clearance | 20 mm above and below; 0 mm on either side |
Frequently Asked Questions
How is the output of 6EP1331-1SH03 set above its nominal 24 V?
Use the potentiometer within the specified 22.2–26.4 V adjustment range and confirm the load voltage requirement.
What current reduction is required for 6EP1331-1SH03 at high ambient temperature?
Reduce output current by 2% per kelvin above 55 °C up to the 70 °C operating limit.
How many units of 6EP1331-1SH03 can be connected in parallel for more power?
Two supplies can be connected in parallel for increased power.
Is a protective conductor required by the insulation class of 6EP1331-1SH03?
No; the supply is Class II without a protective conductor.
Does 6EP1331-1SH03 have a soft-start output characteristic?
Yes; the specified start-up characteristic has no output-voltage overshoot.
How many DC output terminals are provided on 6EP1331-1SH03?
The supply provides two positive and two negative screw terminals for the specified 0.5–2.5 mm² conductors.
Which feeder circuit breakers are recommended for 6EP1331-1SH03?
Use a miniature circuit breaker from 6 A characteristic B or 2 A characteristic C.