Siemens 6ED1055-1MD00-0BA0 LOGO! AM2 PT100 Temperature Expansion Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use Pt100 sensors rather than current or voltage signals.
- Match the LOGO! base generation from 0BA3 onward.
- Supply the module from the specified 12 V or 24 V DC range.
- Bridge the designated terminals for two-wire sensors.
- Prefer three-wire connection when suppressing lead-resistance effects is required.
- Keep shielded sensor cables within 10 m.
6ED1055-1MD00-0BA0 LOGO! AM2 PT100 Temperature Expansion Module
A two-input Pt100 expansion module for LOGO!, with 12/24 V DC power and two- or three-wire sensor connection.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ED1055-1MD00-0BA0 |
| Product Type | Analog temperature-input expansion |
| Core Function | Acquires resistance-thermometer measurements |
| Application | LOGO! temperature-control applications |
Two temperature inputs
Each channel connects one Pt100 resistance thermometer.
Sensor-wiring options
Two-wire or three-wire connection is available.
Compact expansion
The 36 mm body occupies two DIN-rail module widths.
Product Overview
6ED1055-1MD00-0BA0 extends a compatible LOGO! base device with two Pt100 temperature inputs.
The module converts the connected sensor resistance over −50 to +200 °C, with three-wire wiring available to suppress lead-resistance influence on the temperature result.
Key Functions
Pt100 measurement conversion
Two resistance-thermometer inputs provide a −50 to +200 °C temperature range with 0.25 °C resolution.
Lead-resistance handling
Three-wire connection suppresses the influence of the measuring-cable resistance, while two-wire connection requires the specified terminal jumper.
Logic-program integration
The AM2 PT100 works with LOGO! devices from the 0BA3 generation and supports programming through LOGO! Soft Comfort.
Official Specifications
| Rated supply voltage | 12 or 24 V DC |
|---|---|
| Permissible DC ranges | 10.8–15.6 V or 20.4–28.8 V |
| Supply-current consumption | 25–50 mA |
| Typical supply interruption buffering | 5 ms |
| Power loss | 0.3–0.6 W at 12 V; 0.6–1.2 W at 24 V |
| Temperature input channels | 2 for Pt100 sensors |
| Sensor wiring | 2-wire or 3-wire |
| Measurement range | −50 to +200 °C |
| Measurement resolution | 0.25 °C |
| Measurement current | 1.1 mA |
| Typical measurement rate | 50 ms, depending on assembly |
| Measurement error limits | ±1.0% at 0…200 °C; ±1.5% at −50…200 °C, of the measurement limit value |
| Maximum shielded sensor-cable length | 10 m |
| Electrical isolation | None |
| Reverse-polarity protection | Provided |
| Operating temperature | 0–55 °C |
| Mounting | 35 mm DIN rail, 2 module widths, or wall |
| Dimensions (W × H × D) | 36 × 90 × 55 mm |
| Approximate weight | 90 g |
Frequently Asked Questions
Can I connect a 4–20 mA transmitter to 6ED1055-1MD00-0BA0?
The inputs are intended for Pt100 resistance thermometers rather than voltage or current transmitters.
Which LOGO! generation supports 6ED1055-1MD00-0BA0?
The expansion module is compatible with LOGO! devices from the 0BA3 generation.
What jumper is needed for two-wire Pt100 wiring on 6ED1055-1MD00-0BA0?
Bridge M1+ to IC1 for channel 1 or M2+ to IC2 for channel 2 when using the two-wire connection.
Why should I use three-wire wiring with 6ED1055-1MD00-0BA0?
Three-wire connection suppresses the effect of measuring-cable resistance on the temperature result.
Why can the temperature reading from 6ED1055-1MD00-0BA0 fluctuate with a floating supply?
With an ungrounded supply, connect the measuring-cable shielding to the supply negative or ground to address the stated fluctuation condition.
How far can I run a shielded Pt100 cable from 6ED1055-1MD00-0BA0?
Keep the shielded sensor cable within 10 m.
Which software version supports programming 6ED1055-1MD00-0BA0?
LOGO! Soft Comfort V3.0 supports the module, with menu-guided programming available from V3.1 plus the service pack.