Overview
SIEMENS LOGO! 0BA3

6ED1052-2FB00-0BA3 LOGO! 230RCo Logic Module without Display

A displayless LOGO! 230RCo basic module with eight digital inputs and four relay outputs for 115/240 V AC/DC supply systems.

At a Glance

Brand Siemens
Model 6ED1052-2FB00-0BA3
Product Type Displayless logic module
Core Function Executing local logic and timed switching
Application Compact relay-control systems

Eight inputs

The basic module has eight digital input channels for its high-voltage signal range.

Four relay outputs

Each relay has a maximum continuous-current rating of 10 A.

PC or program module

Programs are loaded through LOGO! Soft Comfort or a prepared program module.

Product Overview

6ED1052-2FB00-0BA3 is the displayless LOGO! 230RCo basic unit of the 0BA3 generation. It combines eight digital inputs, four isolated relay outputs and a real-time clock for compact switching and timing applications.

The module has no front display or operating keys. A PC with LOGO! Soft Comfort or a prepared LOGO! program module provides the program-transfer route; the installed application and startup behavior therefore need to be checked when replacing the unit.

Ordering focus: Retain the 230RCo and 0BA3 generation, confirm the high-voltage input range, and prepare the correct program-transfer method before replacement.
Key Functions

Run compact logic

The basic unit processes eight digital inputs and controls four relay outputs.

Switch isolated output circuits

The relay outputs are individually isolated and have load-dependent switching-frequency limits.

Load a prepared application

LOGO! Soft Comfort and the program-module interface support programming without front keys or a display.

Official Specifications
Nominal supply 115/240 V AC/DC
Permitted supply range 85–253 V AC or 85–253 V DC
Permitted AC supply frequency 47–63 Hz
Supply current at 115 V AC 10–30 mA
Supply current at 240 V AC 10–20 mA
Supply current at 115 V DC 5–15 mA
Supply current at 240 V DC 5–10 mA
Typical supply-interruption bridging 10 ms at 115 V AC/DC; 20 ms at 240 V AC/DC
Power loss by supply condition 1.1–3.5 W at 115 V AC; 2.4–4.8 W at 240 V AC; 0.5–1.8 W at 115 V DC; 1.2–2.4 W at 240 V DC
Digital inputs 8, without galvanic isolation
Input signal thresholds AC: signal 0 <40 V, signal 1 >79 V; DC: signal 0 <30 V, signal 1 >79 V
Input current thresholds Signal 0 <0.03 mA; signal 1 >0.08 mA
Typical input delay 50 ms for both 0→1 and 1→0 transitions
Maximum unshielded input cable length 100 m
Relay outputs and isolation 4 outputs, individually isolated
Maximum continuous current per relay 10 A
Incandescent-lamp load at 25000 operations 1000 W at 230/240 V; 500 W at 115/120 V
Maximum switching frequency Mechanical 10 Hz; resistive/lamp load 2 Hz; inductive load 0.5 Hz
Clock reserve at 25 °C Typically 80 h
Real-time clock accuracy Maximum ±5 s/day
Frequently Asked Questions

How do I load a program into the displayless 6ED1052-2FB00-0BA3?

Use LOGO! Soft Comfort on a PC or transfer a prepared program from a LOGO! program module.

Can I start or stop 6ED1052-2FB00-0BA3 with front-panel keys?

The RCo version has no operating keys for starting or stopping the program.

What happens if a program module is fitted when 6ED1052-2FB00-0BA3 is powered up?

The program on the inserted module is copied into the unit and overwrites its existing program.

Can I use ordinary 24 V DC input signals with 6ED1052-2FB00-0BA3?

The high-voltage inputs require more than 79 V AC or DC for signal 1.

May I parallel the relay outputs of 6ED1052-2FB00-0BA3 to increase current capacity?

Paralleling outputs for increased power is not permitted.

Which switching limit should I use for an inductive load on 6ED1052-2FB00-0BA3?

The specified maximum switching frequency for an inductive load is 0.5 Hz.

Does 6ED1052-2FB00-0BA3 accept a DC supply as well as AC?

The permitted supply range is 85–253 V for either AC or DC.

Compatibility & Ordering Notes
Before ordering 6ED1052-2FB00-0BA3: Match the complete 230RCo 0BA3 order number, supply and input voltage, relay load, program-transfer equipment and stored application.

Compatibility Checklist for 6ED1052-2FB00-0BA3

  • Confirm the displayless RCo operating arrangement.
  • Prepare the PC software/cable or compatible program module for application transfer.
  • Check the 85–253 V supply and high-voltage input thresholds.
  • Apply the relay load and switching-frequency limits to the connected loads.
  • Check inserted program-module contents before applying power.
Hot Selling Models
200PRO 6ES7141-4BF00-0AA0
1110130000
RQ3018-1AB00
R162211320
LR-M2-G1/2-04
R162219422 KWD-015-SNS-C0-N-1
6ES5951-7ND12
P2HZX1
DSLFLÜ02
6GK5005-0BA00-1AB2
BES01EL BES 516-329-BO-C-PU-05
JDB8010
1/018.100.2 8185947
0522-03.03
84988129XX

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.