Siemens 6AG1221-1BH22-2XA0 SIPLUS S7-200 EM 221 16DI Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the S7-22X expansion arrangement and the matching plug-in terminals.
- Assign the sixteen inputs and their four-channel isolation groups correctly.
- Apply the cUL temperature range where that approval is required.
- Check the field wiring distance and two-wire sensor leakage before connection.
6AG1221-1BH22-2XA0 SIPLUS S7-200 EM 221 16DI Module
SIPLUS EM 221 with sixteen sinking/sourcing 24 V DC inputs, grouped isolation and an extended −25 to +70°C operating range.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6AG1221-1BH22-2XA0 |
| Product Type | Digital input expansion module |
| Core Function | Acquisition of extended-temperature DC signals |
| Application | S7-22X CPU expansion systems |
Sixteen DC sensor inputs
The input bank accepts sinking or sourcing 24 V DC signals.
Extended environmental service
The SIPLUS operating range is −25 to +70°C, with −25 to +55°C specified for cUL applications.
Grouped optical isolation
Optocoupler isolation separates input groups of four channels.
Product Overview
6AG1221-1BH22-2XA0 extends an S7-22X CPU with sixteen digital inputs in the SIPLUS S7-200 range.
The module retains the electrical functions of its EM 221 base design while extending the environmental range for installations exposed to condensation and specified chemically active atmospheres.
Key Functions
Sixteen DC sensor inputs
The input bank accepts sinking or sourcing 24 V DC signals.
Extended environmental service
The SIPLUS operating range is −25 to +70°C, with −25 to +55°C specified for cUL applications.
Grouped optical isolation
Optocoupler isolation separates input groups of four channels.
Official Specifications
| Input channel bank | 16 sinking/sourcing inputs; IEC 61131 Type 1 |
|---|---|
| Nominal input voltage | 24 V DC |
| Input signal thresholds | Signal 0: 0–5 V; signal 1: 15–30 V |
| Typical input current at signal 1 | 4 mA |
| Maximum rising input delay | 4.5 ms |
| 5 V backplane current | 70 mA maximum |
| Typical power loss | 3 W |
| Maximum input cable | 500 m shielded; 300 m unshielded |
| Two-wire sensor leakage limit | 1 mA maximum |
| Input isolation | Optocouplers; groups of 4 channels |
| Insulation test | 500 V AC for 1 minute |
| Field terminals | Plug-in I/O terminals |
| SIPLUS operating temperature | −25 to +70°C |
| cUL application temperature | −25 to +55°C |
| Condensation | Permitted |
| Specified environmental exposure | Chloric and sulphuric atmospheres |
| Railway temperature classification | EN 50155 temperature T1, category 1 |
| Dimensions and mass | 71.2 × 80 × 62 mm (W × H × D); approximately 160 g |
Frequently Asked Questions
Which CPU family accepts 6AG1221-1BH22-2XA0?
The expansion module is intended for S7-22X CPUs.
Can 6AG1221-1BH22-2XA0 accept signals from sinking and sourcing sensors?
The sixteen 24 V DC inputs support both sinking and sourcing arrangements.
Does the +70°C limit of 6AG1221-1BH22-2XA0 also apply to a cUL installation?
The specified temperature range for cUL applications is −25 to +55°C.
Is condensation permitted around 6AG1221-1BH22-2XA0?
The SIPLUS catalog permits condensation for this module.
How are the input channels on 6AG1221-1BH22-2XA0 isolated?
The inputs use optocoupler isolation in groups of four channels.
What leakage-current limit applies to two-wire sensors on 6AG1221-1BH22-2XA0?
The maximum permissible two-wire sensor quiescent current is 1 mA.
What is the maximum rising input delay of 6AG1221-1BH22-2XA0?
The maximum signal 0 to signal 1 delay is 4.5 ms.