Overview
- Use a DC source that remains within the 20–29 V input range.
- Keep the connected AS-i network load within the 3 A output rating.
- Mount the IP20 enclosure on the specified standard rail inside a suitable cabinet.
- Include the maximum 17.8 W dissipation in the cabinet thermal calculation.
3RX9501-1BA00 AS-Interface 24 V DC Input 3 A Power Supply
A DC-fed AS-i supply with integrated data decoupling, ground-fault detection and overload detection.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3RX9501-1BA00 |
| Product Type | AS-Interface power supply |
| Core Function | AS-i network power delivery |
| Application | Industrial AS-Interface networks |
DC-fed AS-i output
The unit converts nominal 24 V DC input to a 30 V DC AS-i output rated 3 A.
Integrated data decoupling
AS-i data decoupling is integrated in the power-supply assembly.
Network power monitoring
Integrated ground-fault and overload detection monitor the AS-i power circuit.
Product Overview
3RX9501-1BA00 supplies an AS-Interface network from a DC control-power source.
The enclosure integrates the data-decoupling and monitoring functions required for its AS-i output and snaps onto a standard mounting rail.
Key Functions
DC-fed AS-i output
The unit converts nominal 24 V DC input to a 30 V DC AS-i output rated 3 A.
Integrated data decoupling
AS-i data decoupling is integrated in the power-supply assembly.
Network power monitoring
Integrated ground-fault and overload detection monitor the AS-i power circuit.
Official Specifications
| DC input | 24 V nominal; 20–29 V range |
|---|---|
| AS-i output | 30 V DC, 3 A |
| Maximum power loss | 17.8 W |
| Enclosure protection | IP20 |
| Operating temperature | −10 to +70 °C |
| Storage temperature | −25 to +80 °C |
| Dimensions | 50 × 125 × 125 mm (W × H × D) |
Frequently Asked Questions
Can I supply 3RX9501-1BA00 from an ordinary 24 V DC control-power circuit?
The supply accepts 24 V DC nominal with an operating input range of 20–29 V DC.
What bus load can 3RX9501-1BA00 supply?
The AS-i output is rated for 3 A at 30 V DC.
Must I add a separate AS-i data-decoupling unit to 3RX9501-1BA00?
AS-i data decoupling is integrated in the supply.
Can 3RX9501-1BA00 detect an earth fault on the AS-i power circuit?
The supply includes integrated ground-fault detection.
Does 3RX9501-1BA00 include overload monitoring for the AS-i output?
Integrated overload detection is included.
What rail is suitable for mounting 3RX9501-1BA00?
The enclosure snaps onto a 35 × 7.5 mm standard mounting rail to DIN EN 50022.
How much cabinet width should I reserve for 3RX9501-1BA00?
The enclosure requires 50 mm of installation width.